Calgary Winter Club - Whirlpool

4611 14 Street NW Calgary AB T2K 1J7 · Aquatic Facility

Inspection summary

Calgary Winter Club - Whirlpool has been inspected 16 times by Alberta Health Services (Environmental Public Health) since November 2, 2023. The most recent inspection, on November 14, 2025, found no infractions.

1 of 16 inspections on record found no infractions at all. In the past 12 months there were 2 inspections with 1 infraction recorded. The higher-risk findings here relate to: Pool and spa water quality and Chemicals and toxic substances.

The number of infractions per inspection has stayed roughly the same over time.

What these findings mean

Health authorities word their findings differently, so we group them by what they mean for the people using the facility. Higher-risk findings are the ones that could directly cause illness or injury, such as water that is not properly treated.

  • Pool and spa water qualityHigher risk

    For pools, spas and splash pads, inspectors test disinfectant levels, pH and water clarity, and check safety equipment. Water that is not properly treated can spread skin, ear and stomach infections.

    Recorded 20 times across 14 separate inspections, most recently on November 5, 2025. For example: Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?

  • Chemicals and toxic substancesHigher risk

    Pool chemicals such as chlorine and acid must be labelled, stored apart from each other and handled safely. Mixing them by mistake can release toxic gas, so storage and handling problems are treated seriously.

    Recorded 5 times across 5 separate inspections, most recently on October 1, 2025. For example: Is the chemical quality of the water in this pool satisfactory (Non-Critical)?

About this data

These results come from Alberta Health Services (Environmental Public Health), which inspects food premises and other public facilities in this area. We republish the authority's public disclosure data and refresh it regularly; the official record is the final word.

16 inspections

  1. Risk Management Inspection

    0 infractions

  2. Monitoring Inspection

    1 infraction

    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • The turnover rate of the hot tub with a volume greater than 4 m3 (1056 USG) must be 20 minutes. The turnover rate of the hot tub with a volume 3000USG is 24.78 minutes.
  3. Demand Inspection

    2 infractions

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • Water sample collected on 30/09/2025 was rejected due to non-urgent sample received during the weekend/holiday without approval.Resample
    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • Alkalinity was too low, measured at 34 mg/L.Adjust alkalinity and ensure it is maintained between 60mg/L to 180 mg/L.
  4. Demand Inspection

    2 infractions

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • Water sampling collected on 06/05/2025 was cancelled due to time of collection not indicated on the requisition form.Resample
    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • Alkalinity was too low, measured at 34 mg/L.Adjust alkalinity and ensure it is maintained between 60mg/L to 180 mg/L.
  5. Demand Inspection

    2 infractions

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • Water sample collected on 15/04 09:01 was cancelled due to no identification number on the bottle.
    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • Alkalinity was too low, measured at 34 mg/L.Adjust alkalinity and ensure it is maintained between 60mg/L to 180 mg/L.
  6. Demand Inspection

    2 infractions

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • Description: Water sample collected on Jan 07/25 was not processed because the collection time was not indicated.
    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • Alkalinity was too low, measured at 34 mg/L.Adjust alkalinity and ensure it is maintained between 60mg/L to 180 mg/L.
  7. Monitoring Inspection

    1 infraction

    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • Alkalinity was too low, measured at 34 mg/L.Adjust alkalinity and ensure it is maintained between 60mg/L to 180 mg/L.
  8. Demand Inspection

    2 infractions

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • Sample not processed as the time of collection was not indicated and there was no access number provided. Informed Anna to submit a resample tomorrow - Aug 21/24.
    • 06. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Critical)?
      • 2 of 4 skimmers in whirpool were not operational at time of inspection. Ensure that skimmers are operational for adequate removal of surface contamination.
  9. Risk Management Inspection

    1 infraction

    • 06. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Critical)?
      • 2 of 4 skimmers in whirpool were not operational at time of inspection. Ensure that skimmers are operational for adequate removal of surface contamination.
  10. Demand Inspection

    3 infractions

    • 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
      • Water sampled collected on Jun 28, 2024 had Pseudomonas and >57000 CFU/mLID: 24ES-180E00089
    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • Water sampled collected on Jun 28, 2024 had Pseudomonas and >57000 CFU/mLID: 24ES-180E00089
    • 06. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Critical)?
      • 2 of 4 skimmers in whirpool were not operational at time of inspection. Ensure that skimmers are operational for adequate removal of surface contamination.
  11. Risk Management Inspection

    1 infraction

    • 06. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Critical)?
      • 2 of 4 skimmers in whirpool were not operational at time of inspection. Ensure that skimmers are operational for adequate removal of surface contamination.
  12. Demand Inspection

    2 infractions

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • WC-24-0021094 HPC 250CFU/mLTreat and submit a resample
    • 06. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Critical)?
      • 2 of 4 skimmers in whirpool were not operational at time of inspection. Ensure that skimmers are operational for adequate removal of surface contamination.
  13. Demand Inspection

    2 infractions

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • WC-24-0013943Sample not processed no time of collection Submit a resample
    • 06. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Critical)?
      • 2 of 4 skimmers in whirpool were not operational at time of inspection. Ensure that skimmers are operational for adequate removal of surface contamination.
  14. Demand Inspection

    2 infractions

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • WC-24-0007957Sample not processed - No time of collection recorded on bottle. Submit a resample with time of collection recorded.
    • 06. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Critical)?
      • 2 of 4 skimmers in whirpool were not operational at time of inspection. Ensure that skimmers are operational for adequate removal of surface contamination.
  15. Monitoring Inspection

    1 infraction

    • 06. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Critical)?
      • 2 of 4 skimmers in whirpool were not operational at time of inspection. Ensure that skimmers are operational for adequate removal of surface contamination.
  16. Demand Inspection

    1 infraction

    • 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
      • October 31 sample had Pseudomonas aeruginosa isolated. Please treat and resample.