CEFA Early Learning - Daycare

410 - 1155 Cornerstone Boulevard NE Calgary AB T3N 2E9 · Child Care Facility

5 inspections

  1. Risk Management Inspection

    0 infractions

  2. Monitoring Inspection

    5 infractions

    • 03. Are clients at this facility being protected from hazards (Critical)?
      • - A bottle of alcohol, hydrogen peroxide, baby oil, and other chemicals were stored in the unlocked cabinet under the sink in the JK3 room. ** Please relocate the chemicals or install a child safety lock for the cabinet to prevent access. **This was corrected at the time of the inspection. -
    • 08. Is this facility properly constructed (Non-Critical)?
      • - 1. JK3 Room: The wall underneath the paper towel dispenser in the washroom, closest to the door, was deteriorating as the paint was missing and the surface is no longer smooth/ easy to clean. ** Please apply a proper finish on the wall and ensure the surface is made smooth/ easy to clean. 2. JK1C Room: The yellow wall had paint chipping off. ** Please apply a proper finish on the wall and ensure the surface is made smooth/ easy to clean. 3. JK3 Room: Water staining was observed on the ceiling tile outside the washroom. ** Please investigate the source of moisture/ water causing the staining, assess for any potential mould growth, remediate if necessary, and properly abate the leak/moisture. Then, remove the water-stained ceiling tile and replace with all new materials. -
    • 18. Is the facility and equipment being maintained in a suitable manner (Non-Critical)?
      • - 1. JK2A room: There were 2 larger visible stains on the carpets in the room. Staff mentioned there was a urine incident but it had already been cleaned up.** Please properly clean and disinfect the carpet and remove the stains. 2. JK3 room: The second furthest hand sink in the washroom was damaged/ cracked. ** Please repair or replace the handsink. 3. JK1A room: The furthest left handsink in the washroom was damaged/cracked. ** Please repair or replace the handsink. 4. CEFA Baby Room: The diapering mat was torn on the surface and corners. The damaged sections were taped up. ** Please replace the diapering mat so it is in good repair and easy to clean. -
    • 25. Are there adequate storage areas sufficient for the operation of the facility?
      • - 1. JK1B room: there was a child's water bottle that was not labelled with their name. ** Please label all water bottles. **This was corrected at the time of the inspection.2. JK2B Room: there were two children's water bottles that was not labelled with their names. **Please label all water bottles. **This was corrected at the time of the inspection. 3. JK2B Room: There was a container of vaseline that was stored underneath the handsink in the washroom that was unlabelled. Staff mentioned it belonged to a child. **Please ensure the vaseline bottle is labelled with the child's name. **This was corrected at the time of the inspection.-
    • 29. Are washrooms / bathing facilities properly constructed, maintained and supplied (Non-Critical)?
      • - JK3 Room: The middle toilet stall in the washroom was plugged up and unable to flush waste out properly. **Please repair so the toilet is operating properly. -
  3. Monitoring Inspection

    2 infractions

    • 17. Is the facility and equipment being maintained in a suitable manner (Critical)?
      • When asked to explain toy sanitizing procedures, staff indicated that after cleaning, the toys are sanitized using a spray bottle. Many of the toys (e.g. plastic horse) has several bends and curves, making it difficult to verify if toys are properly sanitized. Additionally, staff create a pile the toys in the sink and spray them down, creating additional complications whether the sanitizer will reach all parts of the toy.The Inspector directed the operators to switch to submersing toys in a sanitizer solution for 2 minutes. This will allow a more consistent method to ensure all parts of a toy get sanitized and will be more time efficient.This concern is considered corrected during the inspection, unless demonstrated otherwise.
    • 22. Is the plumbing system adequate and being properly maintained (Non-Critical)?
      • In the washroom between rooms JK1B & C, the centre tap's maximum temperature at the tap spiked from 33.6C to 53.6C for approximately 20 seconds; this concern occurred twice while testing.There may be an issue with the mixing valve improperly distributing water.REQUIREMENT: Investigate and determine the cause of the temperature spikes. Make any necessary repairs to stabilize the temperature.
  4. Initial Inspection

    0 infractions

  5. Demand Inspection

    0 infractions