Chateau Estates Clubhouse - Whirlpool
1101 84 Street NE Calgary AB T2A 7X2 · Aquatic Facility
16 inspections
- Risk Management Inspection
2 infractions
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- **OUTSTANDING**1. Turnover rate for the whirlpool calculated at 31 minutes. **June 15, 2026: the operational flow rate measured 45 GPM, and the calculated turnover rate was 26 minutes.COMPLETE THE FOLLOWING:1. Please adjust whirlpool flow rate so that turnover is within 20 minutes. The flow rate needs to be maintained between 59 GPM - 98 GPM.
- 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
- **OUTSTANDING**1. The anti-entrapment plan is missing information including: - The drain covers' certificate of compliance- Plumbing schematics of the whirlpool showing the drains and pipe connections- Sump dimensions (sump depth, sump exit orientation, sump exit diameter)COMPLETE THE FOLLOWING:1. Locate and provide all the requested documents to the district Inspector.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Risk Management Inspection
5 infractions
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- 1. The total alkalinity measured 24ppm.COMPLETE THE FOLLOWING:1. Ensure the total alkalinity is maintained between 60ppm - 180ppm.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- **OUTSTANDING**1. Turnover rate for the whirlpool calculated at 31 minutes. **June 15, 2026: the operational flow rate measured 45 GPM, and the calculated turnover rate was 26 minutes.COMPLETE THE FOLLOWING:1. Please adjust whirlpool flow rate so that turnover is within 20 minutes. The flow rate needs to be maintained between 59 GPM - 98 GPM.
- 13. Are the general safety devices and physical conditions in this pool providing a safe environment (Non-Critical)?
- 1. There was no clock in the whirlpool room.COMPLETE THE FOLLOWING:1. Replace the clock.
- 16. Are proper testing, monitoring, and other records being properly maintained?
- 1. The water chemistry is not being tested daily.2. Setpoints for pH and ORP at the automated controller are not checked and recorded in the log sheet. COMPLETE THE FOLLOWING:1. Ensure the water is tested daily and record the results in the log sheet.2. Check the ORP and pH setpoints and record in the log sheet.
- 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
- **OUTSTANDING**1. The anti-entrapment plan is missing information including: - The drain covers' certificate of compliance- Plumbing schematics of the whirlpool showing the drains and pipe connections- Sump dimensions (sump depth, sump exit orientation, sump exit diameter)COMPLETE THE FOLLOWING:1. Locate and provide all the requested documents to the district Inspector.
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- Demand Inspection
7 infractions
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- The water sample collected on June 10, 2026 was unsatisfactory. The results indicate pseudomonas isolated.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- The water sample collected on June 10, 2026 was unsatisfactory. The results indicate a heterotrophic plate count of >57,000 CFU/mL, which is above the reference range of <=100 CFU/mL.
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- 1. The total alkalinity measured 24ppm.COMPLETE THE FOLLOWING:1. Ensure the total alkalinity is maintained between 60ppm - 180ppm.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- **OUTSTANDING**1. Turnover rate for the whirlpool calculated at 31 minutes. **June 15, 2026: the operational flow rate measured 45 GPM, and the calculated turnover rate was 26 minutes.COMPLETE THE FOLLOWING:1. Please adjust whirlpool flow rate so that turnover is within 20 minutes. The flow rate needs to be maintained between 59 GPM - 98 GPM.
- 13. Are the general safety devices and physical conditions in this pool providing a safe environment (Non-Critical)?
- 1. There was no clock in the whirlpool room.COMPLETE THE FOLLOWING:1. Replace the clock.
- 16. Are proper testing, monitoring, and other records being properly maintained?
- 1. The water chemistry is not being tested daily.2. Setpoints for pH and ORP at the automated controller are not checked and recorded in the log sheet. COMPLETE THE FOLLOWING:1. Ensure the water is tested daily and record the results in the log sheet.2. Check the ORP and pH setpoints and record in the log sheet.
- 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
- **OUTSTANDING**1. The anti-entrapment plan is missing information including: - The drain covers' certificate of compliance- Plumbing schematics of the whirlpool showing the drains and pipe connections- Sump dimensions (sump depth, sump exit orientation, sump exit diameter)COMPLETE THE FOLLOWING:1. Locate and provide all the requested documents to the district Inspector.
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Demand Inspection
5 infractions
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- The water sample collected on June 10, 2026 was unsatisfactory. The results indicate pseudomonas isolated.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- The water sample collected on June 10, 2026 was unsatisfactory. The results indicate a heterotrophic plate count of >57,000 CFU/mL, which is above the reference range of <=100 CFU/mL.
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- The Combine Chlorine was measured at 2.45 ppm - Ensure that the Combine chloring is as low as possible.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Turnover rate for the whirlpool calculated at 31 minutes. -Please adjust whirlpool flow rate so that turnover is within 20 minutes.*Outstanding violation since 2024.
- 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
- Send the whirlpool anti-entrapment compliance plan with all applicable documentation to the district inspector including:1. the drain covers' compliance certificate, 2. schematic drawing of the whirlpool showing the drains and pipes connections, and 3. pump and its specification.- All documents must be present.
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Demand Inspection
4 infractions
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- 1. The water sample collected on June 3, 2026 was present for total coliforms.
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- The Combine Chlorine was measured at 2.45 ppm - Ensure that the Combine chloring is as low as possible.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Turnover rate for the whirlpool calculated at 31 minutes. -Please adjust whirlpool flow rate so that turnover is within 20 minutes.*Outstanding violation since 2024.
- 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
- Send the whirlpool anti-entrapment compliance plan with all applicable documentation to the district inspector including:1. the drain covers' compliance certificate, 2. schematic drawing of the whirlpool showing the drains and pipes connections, and 3. pump and its specification.- All documents must be present.
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Demand Inspection
4 infractions
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- 1. The water sample collected on May 20 had a heterotrophic plate count of 1,130 colony forming units/mL.
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- The Combine Chlorine was measured at 2.45 ppm - Ensure that the Combine chloring is as low as possible.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Turnover rate for the whirlpool calculated at 31 minutes. -Please adjust whirlpool flow rate so that turnover is within 20 minutes.*Outstanding violation since 2024.
- 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
- Send the whirlpool anti-entrapment compliance plan with all applicable documentation to the district inspector including:1. the drain covers' compliance certificate, 2. schematic drawing of the whirlpool showing the drains and pipes connections, and 3. pump and its specification.- All documents must be present.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Demand Inspection
4 infractions
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- 1. The water sample collected on February 25, 2026 was present for total coliforms.
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- The Combine Chlorine was measured at 2.45 ppm - Ensure that the Combine chloring is as low as possible.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Turnover rate for the whirlpool calculated at 31 minutes. -Please adjust whirlpool flow rate so that turnover is within 20 minutes.*Outstanding violation since 2024.
- 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
- Send the whirlpool anti-entrapment compliance plan with all applicable documentation to the district inspector including:1. the drain covers' compliance certificate, 2. schematic drawing of the whirlpool showing the drains and pipes connections, and 3. pump and its specification.- All documents must be present.
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Demand Inspection
4 infractions
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- 1. The sample collected on January 26, 2026 was not tested, because the sample was received by the lab on January 28, 2026, which was more than 24 hours after collection.
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- The Combine Chlorine was measured at 2.45 ppm - Ensure that the Combine chloring is as low as possible.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Turnover rate for the whirlpool calculated at 31 minutes. -Please adjust whirlpool flow rate so that turnover is within 20 minutes.*Outstanding violation since 2024.
- 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
- Send the whirlpool anti-entrapment compliance plan with all applicable documentation to the district inspector including:1. the drain covers' compliance certificate, 2. schematic drawing of the whirlpool showing the drains and pipes connections, and 3. pump and its specification.- All documents must be present.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Demand Inspection
4 infractions
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- 1. Sample collected on January 7, 2026 had a heterotrophic plate count of 150 colony forming units/mL. Operator informed to submit a re-sample.
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- The Combine Chlorine was measured at 2.45 ppm - Ensure that the Combine chloring is as low as possible.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Turnover rate for the whirlpool calculated at 31 minutes. -Please adjust whirlpool flow rate so that turnover is within 20 minutes.*Outstanding violation since 2024.
- 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
- Send the whirlpool anti-entrapment compliance plan with all applicable documentation to the district inspector including:1. the drain covers' compliance certificate, 2. schematic drawing of the whirlpool showing the drains and pipes connections, and 3. pump and its specification.- All documents must be present.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Demand Inspection
4 infractions
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- The water sample collected on November 17, 2025 was not tested, because it was received by the lab on November 19, 2025, which is more than 24 hours after collection.
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- The Combine Chlorine was measured at 2.45 ppm - Ensure that the Combine chloring is as low as possible.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Turnover rate for the whirlpool calculated at 31 minutes. -Please adjust whirlpool flow rate so that turnover is within 20 minutes.*Outstanding violation since 2024.
- 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
- Send the whirlpool anti-entrapment compliance plan with all applicable documentation to the district inspector including:1. the drain covers' compliance certificate, 2. schematic drawing of the whirlpool showing the drains and pipes connections, and 3. pump and its specification.- All documents must be present.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Demand Inspection
3 infractions
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- The Combine Chlorine was measured at 2.45 ppm - Ensure that the Combine chloring is as low as possible.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Turnover rate for the whirlpool calculated at 31 minutes. -Please adjust whirlpool flow rate so that turnover is within 20 minutes.*Outstanding violation since 2024.
- 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
- Send the whirlpool anti-entrapment compliance plan with all applicable documentation to the district inspector including:1. the drain covers' compliance certificate, 2. schematic drawing of the whirlpool showing the drains and pipes connections, and 3. pump and its specification.- All documents must be present.
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- Monitoring Inspection
2 infractions
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Turnover rate for the whirlpool calculated at 28 minutes. -Please adjust whirlpool flow rate so that turnover is within 20 minutes.*Outstanding violation since 2024.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Whirlpool's flow meter was not working at the time of the inspection.-Please repair or replace the flow meter and ensure its proper working condition to assure pool's turnover rate.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Demand Inspection
2 infractions
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Sample was not processed because the sample requisition bottle was dated incorrectly.-Please submit another sample and ensure proper sampling procedures are followed.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Turnover rate for the whirlpool calculated at 28 minutes. -Please adjust whirlpool flow rate so that turnover is within 20 minutes.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Risk Management Inspection
1 infraction
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Turnover rate for the whirlpool calculated at 28 minutes. -Please adjust whirlpool flow rate so that turnover is within 20 minutes.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Demand Inspection
4 infractions
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Sample collected on April 03, 2024 was not processed because the date/time of sample collection was later than the date/time of receipt.-Please submit a new sample.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Turnover rate for the whirlpool calculated at 28 minutes. -Please adjust whirlpool flow rate so that turnover is at 20 minutes.
- 10. Are general nuisance conditions, other than those noted in other violations, being prevented at this pool (Non-Critical)?
- Chemical reagents used for daily pool water testing were all expired or gone past the best before dates.-Please replace the water testing reagents with effective ones to ensure accurate water testing/monitoring results.
- 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
- There is no anti-entrapment plan for the whirlpool. Ensure this is completed and returned by the response date or a closure order may be issued.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Monitoring Inspection
3 infractions
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Turnover rate for the whirlpool calculated at 28 minutes. -Please adjust whirlpool flow rate so that turnover is at 20 minutes.
- 10. Are general nuisance conditions, other than those noted in other violations, being prevented at this pool (Non-Critical)?
- Chemical reagents used for daily pool water testing were all expired or gone past the best before dates.-Please replace the water testing reagents with effective ones to ensure accurate water testing/monitoring results.
- 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
- There is no anti-entrapment plan for the whirlpool. Ensure this is completed and returned by the response date or a closure order may be issued.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?