Dr. Duncan Murray Recreational Centre - Whirlpool

805 Switzer Drive Hinton AB T7V 1V1 · Aquatic Facility

18 inspections

  1. Monitoring Inspection

    0 infractions

  2. Risk Management Inspection

    0 infractions

  3. Monitoring Inspection

    2 infractions

    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • The total alkalinity measured to be at 29 ppm. The standard level for Total Alkalinity is between 60 and 180 ppm.Please resolve the issue and inform the PHI.
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • Turnover period is calculated to be ~ 27 minutes.Please adjust the flow rate of the whirlpool to ensure the turnover period is adequate to maintain water quality.
  4. Monitoring Inspection

    0 infractions

  5. Risk Management Inspection

    0 infractions

  6. Demand Inspection

    1 infraction

    • 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
      • Water sample collected on December 23 was not satisfactory - Total Coliforms present.
  7. Risk Management Inspection

    0 infractions

  8. Monitoring Inspection

    2 infractions

    • 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
      • The pH of the water in the pool was 6.5. Please maintain pH between 6.8 and 7.6.
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • Turnover period is calculated to be ~ 50 minutes. Please adjust the flow rate of the whirlpool to ensure the turnover period is adequate to maintain water quality.
  9. Demand Inspection

    1 infraction

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • Sample collected on August 20 was unsatisfactory - HPC: 130.
  10. Demand Inspection

    1 infraction

    • 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
      • The microbiological water sample result submitted on 2024-Jun-25 was unsatisfactory.Pseudomonas: ISOLATEDPlease review the water chemistry and treat the hot tub. Take a re-sample once treatment is complete and the water chemistry is rebalanced.
  11. Monitoring Inspection

    0 infractions

  12. Risk Management Inspection

    0 infractions

  13. Demand Inspection

    1 infraction

    • 16. Are proper testing, monitoring, and other records being properly maintained?
      • Accession: WE-24-0022236Sample was not processed.Sample was received more than 24 hours after collection.
  14. Monitoring Inspection

    0 infractions

  15. Risk Management Inspection

    0 infractions

  16. Demand Inspection

    1 infraction

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • Water sample from October 10, 2023, was not processed, no time of collection indicated on the bottle. Re-sample next week.
  17. Risk Management Inspection

    0 infractions

  18. Monitoring Inspection

    3 infractions

    • 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
      • PH was measured at 6.7
    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • Total Alkalinity was measured at 42 PPMPlease ensure the alkalinity is maintained between 60 - 180 ppm at all times.
    • 09. Are general nuisance conditions, other than those noted in other violations, being prevented at this pool (Critical)?
      • Sodium Bicarbonate in the chemical storage room container is leaking from the broken plastic container. This can cause a chemical reaction between the chemicals in the storage room.Ensure to repair/replace the broken storage container to prevent mixing up of chemicals and possible fire in the storage room.