Fairmont Banff Springs - Willow Stream Womens' Changeroom Whirlpool
405 Spray Avenue Banff AB T1L 1J4 · Aquatic Facility
8 inspections
- Demand Inspection
1 infraction
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- June 15/26; Sample not processed; no time on requisition. Resample on Thursday this week.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Monitoring Inspection
0 infractions
- Demand Inspection
0 infractions
- Demand Inspection
1 infraction
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Dec.1/25; Pseudomonas isolated.
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Monitoring Inspection
0 infractions
- Monitoring Inspection
1 infraction
- 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
- Chlorine level was measured at 0.67ppm, 0.48ppm and 0.3ppm. Level must stay above 2ppm at all times. Check automated system and adjust chlorine levels immediately.
- 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
- Demand Inspection
4 infractions
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Mar.11/24; TC positive. Check systems, treat, and resample.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Sample not processed 09/06/23. "No sample submitted."- Resample and submit on Thursday.
- 12. Are the general safety devices and physical conditions in this pool providing a safe environment (Critical)?
- 1. Clarify which drains are connected to jets/which drains are recirculation. If jet flow of 150gpm is only pulling through 2 drains, each cover would need to be rated for 150gpm (currently at 125gpm). When replacing covers, ensure that they are rated for a high enough flow. If recirculation pump is pulling through 2 drains, the drain covers would be adequate (65gpm).2. Secondary anti-entrapment system (VacAlert) not working. Repair and replace.
- 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
- Update anti-entrapment plan with both jet and recirculation flow.
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Demand Inspection
3 infractions
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Sample not processed 09/06/23. "No sample submitted."- Resample and submit on Thursday.
- 12. Are the general safety devices and physical conditions in this pool providing a safe environment (Critical)?
- 1. Clarify which drains are connected to jets/which drains are recirculation. If jet flow of 150gpm is only pulling through 2 drains, each cover would need to be rated for 150gpm (currently at 125gpm). When replacing covers, ensure that they are rated for a high enough flow. If recirculation pump is pulling through 2 drains, the drain covers would be adequate (65gpm).2. Secondary anti-entrapment system (VacAlert) not working. Repair and replace.
- 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
- Update anti-entrapment plan with both jet and recirculation flow.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?