Foremost Civic Centre Swimming Pool - Spray Park
301 Main Street Foremost AB T0K 0X0 · Aquatic Facility
12 inspections
- Monitoring Inspection
0 infractions
- Demand Inspection
0 infractions
- Monitoring Inspection
1 infraction
- 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
- The pH measured 7.82. Operator manually added chemical to decrease pH.
- 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
- Risk Management Inspection
3 infractions
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- The operator is not monitoring total alkalinity, which should be done weekly.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- There is no flow meter installed in the mechanical room to monitor water flow within the recirculation system. A flow meter should be installed to measure the flow of the water in the recirculation line.
- 16. Are proper testing, monitoring, and other records being properly maintained?
- Daily water chemistry testing is not currently being performed. Discussed testing the water daily for its chemical parameters.Discussed keeping record of tested chemical parameters.
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- Demand Inspection
4 infractions
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- June 16, 2025 sample had HPC count of 150 and TC present.
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- The operator is not monitoring total alkalinity, which should be done weekly.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- There is no flow meter installed in the mechanical room to monitor water flow within the recirculation system. A flow meter should be installed to measure the flow of the water in the recirculation line.
- 16. Are proper testing, monitoring, and other records being properly maintained?
- Daily water chemistry testing is not currently being performed. Discussed testing the water daily for its chemical parameters.Discussed keeping record of tested chemical parameters.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Demand Inspection
4 infractions
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- The bacteriological sample collected on June 10/25 came back unsatisfactory (4000 HPC). Operator noted the only concern was recent rain. Discussed submitting a re-sample next week.
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- The operator is not monitoring total alkalinity, which should be done weekly.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- There is no flow meter installed in the mechanical room to monitor water flow within the recirculation system. A flow meter should be installed to measure the flow of the water in the recirculation line.
- 16. Are proper testing, monitoring, and other records being properly maintained?
- Daily water chemistry testing is not currently being performed. Discussed testing the water daily for its chemical parameters.Discussed keeping record of tested chemical parameters.
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Demand Inspection
2 infractions
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- 4000 HPC in bact. water sample.
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- The total alkalinity of the spray park water is not being measured. The alkalinity should measure between 60 and 180 ppm.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Risk Management Inspection
1 infraction
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- The total alkalinity of the spray park water was measured at 48 ppm. The alkalinity should measure between 60 and 180 ppm.
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- Demand Inspection
2 infractions
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- An elevated level of HPC (850 CFU/mL) was present in the water sample submitted to the Provincial Lab on 17/07/2024.
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- The total alkalinity of the spray park water was measured at 48 ppm. The alkalinity should measure between 60 and 180 ppm.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Risk Management Inspection
1 infraction
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- The total alkalinity of the spray park water was measured at 48 ppm. The alkalinity should measure between 60 and 180 ppm.
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- Monitoring Inspection
3 infractions
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- ProvLab results for water sample collected on July 24, 2023 indicated that HPC was >57000 CFU/mL. Please ensure that no visible contamination is present in the spray park and that water chemical requirements are maintained. Please also submit a resample.
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- The total alkalinity of the spray park water was measured at 48 ppm. The alkalinity should measure between 60 and 180 ppm.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- A functional flow meter is not present on the spray park's recirculation line.Please ensure a flow meter is installed so that the flow and turnover rates can be verified.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Demand Inspection
1 infraction
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- ProvLab results for water sample collected on July 24, 2023 indicated that HPC was >57000 CFU/mL. Please ensure that no visible contamination is present in the spray park and that water chemical requirements are maintained. Please also submit a resample.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?