Holiday Inn Conference Centre Edmonton South - Whirlpool
4485 Gateway Boulevard NW Edmonton AB T6H 5C3 · Aquatic Facility
24 inspections
- Demand Inspection
1 infraction
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- the microbiological water sample 26EN-188E01036 submitted on July 7, 2026, was unsatisfactory: Pseudomonas aeruginosa was isolated.
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Risk Management Inspection
0 infractions
- Demand Inspection
1 infraction
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- The microbiological water sample submitted on 16 June 2026 was unsatisfactory: HPC 570 CFU/mL. Take all necessary action to ensure microbiologically safe water. Submit a new microbiological water sample at your earliest convenience once the water chemistry is balanced.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Risk Management Inspection
0 infractions
- Demand Inspection
1 infraction
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- The microbiological water sample submitted on 13 April 2026 was unsatisfactory: HPC 1750 CFU/mL. Take all necessary action to ensure microbiologically safe water. Submit a new microbiological water sample at your earliest convenience once the water chemistry is balanced.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Demand Inspection
1 infraction
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- The microbiological water sample submitted on 23 March 2026was unsatisfactory: Pseudomonas aeruginosa isolated take all necessary action to ensure microbiologically safe water. Submit a new microbiological water sample at your earliest convenience once the water chemistry is balanced.
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Monitoring Inspection
0 infractions
- Risk Management Inspection
0 infractions
- Demand Inspection
1 infraction
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- The microbiological water sample submitted on 6 Jan 2026 was unsatisfactory: Total Coliform present. Take all necessary action to ensure microbiologically safe water. Submit a new microbiological water sample at your earliest convenience once the water chemistry is balanced.
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Risk Management Inspection
0 infractions
- Demand Inspection
1 infraction
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- The microbiological water sample submitted on 2/9/2025 was unsatisfactory: HPC 190 CFU/mL. Take all necessary action to ensure microbiologically safe water. Submit a new microbiological water sample at your earliest convenience once the water chemistry is balanced.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Risk Management Inspection
0 infractions
- Demand Inspection
2 infractions
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- The microbiological water sample result collected on 05/08/2025 [25EN-217E00085] was unsatisfactory: Pseudomonas aeruginosa isolated. Take all necessary action to ensure microbiologically safe water. Submit a new microbiological water sample at your earliest convenience once the water chemistry is balanced.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- An alarm was noted on the chemical controller for the pH however the set point and readings were consistent. The operator attempted to clear the alarm but the controller went back into alarm. Contact a service provider to address concerns with the controller to ensure the pH feed system is working correctly.
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Demand Inspection
1 infraction
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- An alarm was noted on the chemical controller for the pH however the set point and readings were consistent. The operator attempted to clear the alarm but the controller went back into alarm. Contact a service provider to address concerns with the controller to ensure the pH feed system is working correctly.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Risk Management Inspection
0 infractions
- Demand Inspection
2 infractions
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- The microbiological water sample submitted on March 26, 2025, was unsatisfactory: HPC >57000 CFU/mL. Take all necessary action to ensure microbiologically safe water. Submit a new microbiological water sample at your earliest convenience once the water chemistry is balanced.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- The manual pH measured was 6.91 and the controller was reading 7.2. The manual and controller pH was not consistent. Check controller and recalibrate as necessary.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Risk Management Inspection
1 infraction
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- The manual pH measured was 6.91 and the controller was reading 7.2. The manual and controller pH was not consistent. Check controller and recalibrate as necessary.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Demand Inspection
2 infractions
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- The microbiological water sample submitted on December 30, 2024 and January 6, 2025, was unsatisfactory: Pseudomonas aeruginosa isolated. Take all necessary action to ensure microbiologically safe water. Submit a new microbiological water sample at your earliest convenience once the water chemistry is balanced. Operator instructed to close whirlpool and treat. A satisfactory microbiological result is required before the basin can be opened to the public.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- The manual pH measured was 6.91 and the controller was reading 7.2. The manual and controller pH was not consistent. Check controller and recalibrate as necessary.
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Demand Inspection
2 infractions
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- The microbiological water sample submitted on December 30, 2024, was unsatisfactory: Pseudomonas aeruginosa isolated. Take all necessary action to ensure microbiologically safe water. Submit a new microbiological water sample at your earliest convenience once the water chemistry is balanced.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- The manual pH measured was 6.91 and the controller was reading 7.2. The manual and controller pH was not consistent. Check controller and recalibrate as necessary.
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Risk Management Inspection
1 infraction
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- The manual pH measured was 6.91 and the controller was reading 7.2. The manual and controller pH was not consistent. Check controller and recalibrate as necessary.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Risk Management Inspection
2 infractions
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- The manual pH measured was 6.91 and the controller was reading 7.2. The manual and controller pH was not consistent. Check controller and recalibrate as necessary.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Flow rate appeared to be 25 GPM however due to worn scale on the flow meter flow may be slightly higher. Flow must be at least 35 GPM in order to maintain a turnover period of 15 minutes. Replace the flow meter and confirm flow rate.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Monitoring Inspection
4 infractions
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- The manual pH measured was 6.91 and the controller was reading 7.2. The manual and controller pH was not consistent. Check controller and recalibrate as necessary.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Flow rate appeared to be 25 GPM however due to worn scale on the flow meter flow may be slightly higher. Flow must be at least 35 GPM in order to maintain a turnover period of 15 minutes. Replace the flow meter and confirm flow rate.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Leak was noted at the plumbing going to the heat exchanger. Repair or replace plumbing to address the leak.
- 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
- Scum buildup was noted in the upper inside of the skimmer pot. Clean and remove the scum build up.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Risk Management Inspection
0 infractions
- Monitoring Inspection
1 infraction
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Flow meter for the circulation system is not working. The float appears to be stuck with debris. Clean out the flow meter and ensure that it is working.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?