Holiday Inn Express & Suites Airdrie - Whirlpool
64 East Lake Avenue NE Airdrie AB T4A 2G8 · Aquatic Facility
Inspection summary
Holiday Inn Express & Suites Airdrie - Whirlpool has been inspected 21 times by Alberta Health Services (Environmental Public Health) since June 27, 2024. The most recent inspection, on October 7, 2026, recorded 1 infraction.
3 of 21 inspections on record found no infractions at all. In the past 12 months there were 15 inspections with 16 infractions recorded. The higher-risk findings here relate to: Chemicals and toxic substances and Pool and spa water quality.
The number of infractions per inspection has stayed roughly the same over time.
What these findings mean
Health authorities word their findings differently, so we group them by what they mean for the people using the facility. Higher-risk findings are the ones that could directly cause illness or injury, such as water that is not properly treated.
Chemicals and toxic substancesHigher risk
Pool chemicals such as chlorine and acid must be labelled, stored apart from each other and handled safely. Mixing them by mistake can release toxic gas, so storage and handling problems are treated seriously.
Recorded 15 times across 15 separate inspections, most recently on June 2, 2026. For example:
Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
Pool and spa water qualityHigher risk
For pools, spas and splash pads, inspectors test disinfectant levels, pH and water clarity, and check safety equipment. Water that is not properly treated can spread skin, ear and stomach infections.
Recorded 9 times across 9 separate inspections, most recently on October 7, 2026. For example:
Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
About this data
These results come from Alberta Health Services (Environmental Public Health), which inspects food premises and other public facilities in this area. We republish the authority's public disclosure data and refresh it regularly; the official record is the final word.
21 inspections
- Demand Inspection
1 infraction
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Water sample submitted to the lab on October 6, 2026 was dated Sept 29th, 2026, which is more than 24 hours since collection. Water sample was not processed. **Resubmit sample
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Risk Management Inspection
0 infractions
- Demand Inspection
1 infraction
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Water sample submitted to the lab on Sept 22, 2026, was dated Sept 15th, 2026, which is more than 24 hours since collection. Water sample was not processed.**Resubmit sample
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Risk Management Inspection
0 infractions
- Demand Inspection
1 infraction
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Water sample submitted on July 7th returned positive for Pseudomonas.**Complete a treatment of the pool and resubmit sample to the lab.
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Monitoring Inspection
0 infractions
- Demand Inspection
1 infraction
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- The Combined chlorine for the hot tub was measured at 3.75ppm**Please maintain CC value as low as possible**It is recommended to maintain combined chlorine value below 1.0ppm.**Investigate reason for the constant high CC value and rectify concerns
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- Risk Management Inspection
1 infraction
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- The Combined chlorine for the hot tub was measured at 3.75ppm**Please maintain CC value as low as possible**It is recommended to maintain combined chlorine value below 1.0ppm.**Investigate reason for the constant high CC value and rectify concerns
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- Demand Inspection
2 infractions
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Water sample submitted on March 31 was not processed due to missing ID number.**Please resubmit sample
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- The Combined chlorine for the hot tub was measured at 3.75ppm**Please maintain CC value as low as possible**It is recommended to maintain combined chlorine value below 1.0ppm.**Investigate reason for the constant high CC value and rectify concerns
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Risk Management Inspection
1 infraction
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- The Combined chlorine for the hot tub was measured at 3.75ppm**Please maintain CC value as low as possible**It is recommended to maintain combined chlorine value below 1.0ppm.**Investigate reason for the constant high CC value and rectify concerns
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- Demand Inspection
2 infractions
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- There was no time of collection indicated on sample submitted on March 10**Resubmit sample
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- The Combined chlorine for the hot tub was measured at 3.75ppm**Please maintain CC value as low as possible**It is recommended to maintain combined chlorine value below 1.0ppm.**Investigate reason for the constant high CC value and rectify concerns
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Risk Management Inspection
1 infraction
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- The Combined chlorine for the hot tub was measured at 3.75ppm**Please maintain CC value as low as possible**It is recommended to maintain combined chlorine value below 1.0ppm.**Investigate reason for the constant high CC value and rectify concerns
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- Demand Inspection
2 infractions
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- The most recent bacteriological water sample indicated a heterotrophic plate count of 500 CFU/mL.
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- The Combined chlorine for the hot tub was measured at 3.75ppm**Please maintain CC value as low as possible**It is recommended to maintain combined chlorine value below 1.0ppm.**Investigate reason for the constant high CC value and rectify concerns
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Monitoring Inspection
1 infraction
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- The Combined chlorine for the hot tub was measured at 3.75ppm**Please maintain CC value as low as possible**It is recommended to maintain combined chlorine value below 1.0ppm.**Investigate reason for the constant high CC value and rectify concerns
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- Risk Management Inspection
2 infractions
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Water sample submitted on Nov 25 was not processed because there was no ID label on the sample bottle.**Resubmit sample.
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- The Combined chlorine for the hot tub was measured at 2.28ppm**Please maintain CC value as low as possible**It is recommended to maintain combined chlorine value below 1.0ppm.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Risk Management Inspection
1 infraction
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- The Combined chlorine for the hot tub was measured at 2.28ppm**Please maintain CC value as low as possible**It is recommended to maintain combined chlorine value below 1.0ppm.
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- Demand Inspection
2 infractions
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- HPC value for water sample submitted on June 17, 2025, was 57000CFU/ml. Please treat water and resubmit sample.
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- The Combined chlorine for the hot tub was measured at 2.28ppm**Please maintain CC value as low as possible**It is recommended to maintain combined chlorine value below 1.0ppm.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Demand Inspection
2 infractions
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- HPC value for water sample submitted on June 10, 2025, was 120CFU/ml. Please resubmit sample.
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- The Combined chlorine for the hot tub was measured at 2.28ppm**Please maintain CC value as low as possible**It is recommended to maintain combined chlorine value below 1.0ppm.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Monitoring Inspection
1 infraction
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- The Combined chlorine for the hot tub was measured at 2.28ppm**Please maintain CC value as low as possible**It is recommended to maintain combined chlorine value below 1.0ppm.
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- Monitoring Inspection
1 infraction
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- The Combined chlorine for the hot tub was measured at 3.35ppm**Please maintain CC value as low as possible**It is recommended to maintain combined chlorine value below 1.0ppm.
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- Initial Inspection
1 infraction
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- The Combined chlorine for the hot tub was measured at 3.45ppm**Please maintain CC value as low as possible**It is recommended to maintain combined chlorine value below 1.0ppm.
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
Nearby inspected facilities
- Holiday Inn Express & Suites Airdrie - Common
64 East Lake Avenue NE Airdrie AB T4A 2G8
8 inspections
- Holiday Inn Express & Suites Airdrie - Swimming Pool
64 East Lake Avenue NE Airdrie AB T4A 2G8
19 inspections
- Holiday Inn Express & Suites Airdrie - Food
64 East Lake Avenue NE Airdrie AB T4A 2G8
5 inspections
- Abrio Place - Food
52 East Lake Avenue NE Airdrie AB T4A 2G8
8 inspections
- Airdrie Backyard & Leisure
107 - 51 East Lake Avenue NE Airdrie AB T4A 2H1
1 inspection
- Old Town Pizza House Bar & Grill
216 Edmonton Trail NE Airdrie AB T4B 1R9
6 inspections
- Egg & Us
521 3 Avenue NE Airdrie AB T4B 1R8
8 inspections
- Petro Canada - Store
217 Edmonton Trail NE Airdrie AB T4B 1S1
2 inspections