Lake Louise Inn - Lower Whirlpool
210 Village Road Lake Louise AB · Aquatic Facility
7 inspections
- Demand Inspection
4 infractions
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- May 5/26; Sample not tested no id label on bottle.
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- Alkalinity was slightly high, measured at 193ppm; should be between 60 and 180ppm.
- 10. Are general nuisance conditions, other than those noted in other violations, being prevented at this pool (Non-Critical)?
- Water was somewhat cloudy in whirlpool at time of inspection although main drains were still clearly visible. Alkalinity was slightly over acceptable range- this may need to be maintained at lower level of maintain adequate clarity. Ensure pool is closed if clarity deteriorates further.
- 13. Are the general safety devices and physical conditions in this pool providing a safe environment (Non-Critical)?
- Jet pump flow meter is not working. Repair flow meter for jets.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Demand Inspection
4 infractions
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Oct.29/25 Sample not tested. No date on requisition.
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- Alkalinity was slightly high, measured at 193ppm; should be between 60 and 180ppm.
- 10. Are general nuisance conditions, other than those noted in other violations, being prevented at this pool (Non-Critical)?
- Water was somewhat cloudy in whirlpool at time of inspection although main drains were still clearly visible. Alkalinity was slightly over acceptable range- this may need to be maintained at lower level of maintain adequate clarity. Ensure pool is closed if clarity deteriorates further.
- 13. Are the general safety devices and physical conditions in this pool providing a safe environment (Non-Critical)?
- Jet pump flow meter is not working. Repair flow meter for jets.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Monitoring Inspection
3 infractions
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- Alkalinity was slightly high, measured at 193ppm; should be between 60 and 180ppm.
- 10. Are general nuisance conditions, other than those noted in other violations, being prevented at this pool (Non-Critical)?
- Water was somewhat cloudy in whirlpool at time of inspection although main drains were still clearly visible. Alkalinity was slightly over acceptable range- this may need to be maintained at lower level of maintain adequate clarity. Ensure pool is closed if clarity deteriorates further.
- 13. Are the general safety devices and physical conditions in this pool providing a safe environment (Non-Critical)?
- Jet pump flow meter is not working. Repair flow meter for jets.
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- Demand Inspection
1 infraction
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Nov.12/24; Sample positive for TC. Treat and resample.
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Monitoring Inspection
0 infractions
- Demand Inspection
2 infractions
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- June 3/24; Coliform positive. Treat and resample.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Flow rate is just slightly high for the filtration capacity (63gpm, maximum should be 61gpm, minimum is 53). If possible, throttle back flow rate slightly.
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Monitoring Inspection
2 infractions
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Flow rate is just slightly high for the filtration capacity (63gpm, maximum should be 61gpm, minimum is 53). If possible, throttle back flow rate slightly.
- 12. Are the general safety devices and physical conditions in this pool providing a safe environment (Critical)?
- Water temperature was measured at 41C. Ensure water temperature remains at or below 40C.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?