NOBLE ST CHTR-CRIMSON(CORLISS HS)
821 E 103rd St (10300S), CHICAGO, IL 60628 · School
15 inspections
- Canvass
1 infraction
- 55. PHYSICAL FACILITIES INSTALLED, MAINTAINED & CLEAN
- 6-501.12 OBSERVED MINOR DEBRIS UNDER THE SHELVES IN THE DRY STORAGE AREA. INSTRUCTED TO CLEAN. OBSERVED STANDING WATER BY THE CONDENSER. INSTRUCTED TO REMOVE.
- 55. PHYSICAL FACILITIES INSTALLED, MAINTAINED & CLEAN
- Canvass
3 infractions
- 55. PHYSICAL FACILITIES INSTALLED, MAINTAINED & CLEAN
- MISSING/LOOSE CEILING TILES IN THE BASEMENT REAR STORAGE AND PREP AREA. INSTRUCTED TO PROVIDE/REPLACE MISSING/LOOSE CEILING TILES AND MAINTAIN.
- 55. PHYSICAL FACILITIES INSTALLED, MAINTAINED & CLEAN
- MOPS NOT PROPERLY STORED WHEN NOT IN USE. INSTRUCTED TO STORE HANGING UP FOR PROPER AIR DRYING. MAINTAIN SAME.
- 56. ADEQUATE VENTILATION & LIGHTING; DESIGNATED AREAS USED
- BLOWN LIGHTS IN THE BASEMENT REAR STORAGE AND FOOD PREP AREA. INSTRUCTED TO REPLACE BLOWN LIGHT BULBS AND MAINTAIN ADEQUATE LIGHTING.
- 55. PHYSICAL FACILITIES INSTALLED, MAINTAINED & CLEAN
- Canvass
4 infractions
- 40. PERSONAL CLEANLINESS
- FOUND A MALE SERVER SERVING FOOD AND NOT WEARING A HAIR OR BEARD RESTRAINT. INSTRUCTED MANAGER TO HAVE ALL FOOD HANDLERS TO WEAR A HAIR AND/OR BEARD RESTRAINT. MAINTAIN SAME.
- 51. PLUMBING INSTALLED; PROPER BACKFLOW DEVICES
- FOUND THE HOT WATER KNOB/HANDLE ON THE FAUCET ABOVE THE SANITIZING COMPARTMENT OF THE 3-COMPARTMENT SINK STRIPPED. INSTRUCTED MANAGER TO FIX OR REPLACE KNOB/HANDLE AND MAINTAIN.
- 55. PHYSICAL FACILITIES INSTALLED, MAINTAINED & CLEAN
- FOUND THE FAN COVER IN THE STAFF'S WOMEN'S TOILET ROOM WITH DIRT/DUST BUILD UP. INSTRUCTED MANAGER TO CLEAN AND MAINTAIN FAN COVER.
- 55. PHYSICAL FACILITIES INSTALLED, MAINTAINED & CLEAN
- FOUND THE BUTLER STORAGE AREA OUTSIDE THE KITCHEN AREA CLUTTERED. INSTRUCTED MANAGER TO ELIMINATE CLUTTER AND ORGANIZE AREA. MAINTAIN SAME.
- 40. PERSONAL CLEANLINESS
- Canvass Re-Inspection
2 infractions
- 10. ADEQUATE HANDWASHING SINKS PROPERLY SUPPLIED AND ACCESSIBLE
- OBSERVED NO HOT WATER IN GIRLS AND BOYS WEST WASHROOMS(74.2F). INSTRUCTED MANAGER TO PROVIDE AT 100F-120F WATER AT ALL HAND WASHING SINKS. PRIORITY 7-38-030(C)
- 59. PREVIOUS PRIORITY FOUNDATION VIOLATION CORRECTED
- PREVIOUS PRIORITY FOUNDATION VIOLATION NOT CORRECTED FROM REPORT #2564768 ON 10-4-22:OBSERVED NO HAND WASHING SINK INSIDE SERVING AREA. INSTRUCTED MANAGER TO INSTALL HAND WASHING SINK WITH HOT AND COLD RUNNING WATER, SOAP AND PAPER TOWELS IN SERVING LINE. PRIORITY 7-42-090
- 10. ADEQUATE HANDWASHING SINKS PROPERLY SUPPLIED AND ACCESSIBLE
- Canvass Re-Inspection
4 infractions
- 10. ADEQUATE HANDWASHING SINKS PROPERLY SUPPLIED AND ACCESSIBLE
- OBSERVED NO HOT WATER IN GIRLS AND BOYS WEST WASHROOMS(74.2F). INSTRUCTED MANAGER TO PROVIDE AT LEAST 100F WATER AT ALL HAND WASHING SINKS. PRIORITY 7-38-030(C)
- 10. ADEQUATE HANDWASHING SINKS PROPERLY SUPPLIED AND ACCESSIBLE
- OBSERVED NO HAND WASHING SINK INSIDE SERVING AREA. INSTRUCTED MANAGER TO INSTALL HAND WASHING SINK WITH HOT AND COLD RUNNING WATER, SOAP AND PAPER TOWELS IN SERVING LINE. PRIORITY FOUNDATION 7-38-030(C)
- 51. PLUMBING INSTALLED; PROPER BACKFLOW DEVICES
- OBSERVED LEAKING COLD WATER HANDLE ON HAND WASHING SINK IN MAIN KITCHEN. INSTRUCTED MANAGER TO REPAIR.
- 56. ADEQUATE VENTILATION & LIGHTING; DESIGNATED AREAS USED
- OBSERVED LOOSE LIGHT SHIELD IN REAR PREP AREA. INSTRUCTED MANAGER TO REPAIR.
- 10. ADEQUATE HANDWASHING SINKS PROPERLY SUPPLIED AND ACCESSIBLE
- Canvass Re-Inspection
6 infractions
- 10. ADEQUATE HANDWASHING SINKS PROPERLY SUPPLIED AND ACCESSIBLE
- OBSERVED NO HOT WATER IN GIRLS AND BOYS WEST WASHROOMS(74.2F). INSTRUCTED MANAGER TO PROVIDE AT LEAST 100F WATER AT ALL HAND WASHING SINKS. PRIORITY 7-38-030(C)
- 10. ADEQUATE HANDWASHING SINKS PROPERLY SUPPLIED AND ACCESSIBLE
- OBSERVED NO HAND WASHING SINK INSIDE SERVING AREA. INSTRUCTED MANAGER TO INSTALL HAND WASHING SINK WITH HOT AND COLD RUNNING WATER, SOAP AND PAPER TOWELS IN SERVING LINE. PRIORITY FOUNDATION 7-38-030(C)
- 49. NON-FOOD/FOOD CONTACT SURFACES CLEAN
- OBSERVED RESIDUE DEBRIS ON INTERIOR AND EXTERIOR SURFACES OF SHELVING UNITS, HOLDING UNITS, CABINETS. INSTRUCTED MANAGER TO CLEAN AND MAINTAIN.
- 51. PLUMBING INSTALLED; PROPER BACKFLOW DEVICES
- OBSERVED LEAKING COLD WATER HANDLE ON HAND WASHING SINK IN MAIN KITCHEN. INSTRUCTED MANAGER TO REPAIR.
- 56. ADEQUATE VENTILATION & LIGHTING; DESIGNATED AREAS USED
- OBSERVED LOOSE LIGHT SHIELD IN REAR PREP AREA. INSTRUCTED MANAGER TO REPAIR.
- 59. PREVIOUS PRIORITY FOUNDATION VIOLATION CORRECTED
- PREVIOUS PRIORITY FOUNDATION VIOLATION NOT CORRECTED FROM REPORT #2563792 ON 9-16-22:38- OBSERVED OVER 20 MICE DROPPINGS SCATTERED INSIDE FAN AND ON FLOOR ALONG WALLS UNDER SERVING LINE. INSTRUCTED MANAGER TO CALL AN EXTERMINATOR FOR SERVICE, CLEAN AND SANITIZE ALL AREAS. PRIORITY 7-42-090
- 10. ADEQUATE HANDWASHING SINKS PROPERLY SUPPLIED AND ACCESSIBLE
- Canvass Re-Inspection
8 infractions
- 10. ADEQUATE HANDWASHING SINKS PROPERLY SUPPLIED AND ACCESSIBLE
- OBSERVED NO HAND WASHING SINK INSIDE SERVING AREA. INSTRUCTED MANAGER TO INSTALL HAND WASHING SINK WITH HOT AND COLD RUNNING WATER, SOAP AND PAPER TOWELS IN SERVING LINE. PRIORITY FOUNDATION 7-38-030(C)
- 10. ADEQUATE HANDWASHING SINKS PROPERLY SUPPLIED AND ACCESSIBLE
- OBSERVED NO HOT WATER IN GIRLS AND BOYS WEST WASHROOMS(74.2F). INSTRUCTED MANAGER TO PROVIDE AT LEAST 100F WATER AT ALL HAND WASHING SINKS. PRIORITY 7-38-030(C)
- 49. NON-FOOD/FOOD CONTACT SURFACES CLEAN
- OBSERVED RESIDUE ON INTERIOR OF ICE MACHINE, DEBRIS ON INTERIOR AND EXTERIOR SURFACES OF SHELVING UNITS, HOLDING UNITS, CABINETS. INSTRUCTED MANAGER TO CLEAN AND MAINTAIN.
- 51. PLUMBING INSTALLED; PROPER BACKFLOW DEVICES
- OBSERVED LEAKING COLD WATER HANDLE ON HAND WASHING SINK IN MAIN KITCHEN. INSTRUCTED MANAGER TO REPAIR.
- 54. GARBAGE & REFUSE PROPERLY DISPOSED; FACILITIES MAINTAINED
- OBSERVED NO WASTE RECEPTACLE AT HAND WASHING SINK NEAR SERVERY. INSTRUCTED MANAGER TO PROVIDE.
- 55. PHYSICAL FACILITIES INSTALLED, MAINTAINED & CLEAN
- OBSERVED CEILING TILES NOT SECURE IN REAR STORAGE AREA. INSTRUCTED MANAGER TO REPAIR.
- 56. ADEQUATE VENTILATION & LIGHTING; DESIGNATED AREAS USED
- OBSERVED LOOSE LIGHT SHIELD IN REAR PREP AREA. INSTRUCTED MANAGER TO REPAIR.
- 59. PREVIOUS PRIORITY FOUNDATION VIOLATION CORRECTED
- PREVIOUS PRIORITY FOUNDATION VIOLATION NOT CORRECTED FROM REPORT #2563792 ON 9-16-22:38- OBSERVED OVER 20 MICE DROPPINGS ON FLOOR IN DRY STORAGE AREA, 10 MICE DROPPINGS ON FLOOR BEHIND AND BETWEEN COOKING EQUIPMENT, 10 MICE DROPPINGS ON FLOOR IN REAR STEAM TABLE STORAGE AREA, 10 MICE DROPPINGS AROUND COMPRESSOR UNIT UNDER UNUSED COOLERS IN SERVERY, 20 MICE DROPPINGS ON FLOOR AND WINDOW LEDGES NEAR VENDING MACHINES IN DINING AREA. INSTRUCTED MANAGER TO CALL AN EXTERMINATOR FOR SERVICE, CLEAN AND SANITIZE ALL AREAS. PRIORITY 7-42-090
- 10. ADEQUATE HANDWASHING SINKS PROPERLY SUPPLIED AND ACCESSIBLE
- Canvass
9 infractions
- 10. ADEQUATE HANDWASHING SINKS PROPERLY SUPPLIED AND ACCESSIBLE
- OBSERVED NO HAND WASHING SINK INSIDE SERVING AREA. INSTRUCTED MANAGER TO INSTALL HAND WASHING SINK WITH HOT AND COLD RUNNING WATER, SOAP AND PAPER TOWELS IN SERVING LINE. PRIORITY FOUNDATION 7-38-030(C)
- 10. ADEQUATE HANDWASHING SINKS PROPERLY SUPPLIED AND ACCESSIBLE
- OBSERVED NO HOT WATER IN GIRLS AND BOYS WEST WASHROOMS(74.2F). INSTRUCTED MANAGER TO PROVIDE AT LEAST 100F WATER AT ALL HAND WASHING SINKS. PRIORITY 7-38-030(C)
- 33. PROPER COOLING METHODS USED; ADEQUATE EQUIPMENT FOR TEMPERATURE CONTROL
- OBSERVED WALK-IN COOLERS NOT OPERABLE AND MAINTAINING IMPROPER TEMPERATURE 54.7F. INSTRUCTED MANAGER TO REPAIR. ALL COOLERS MUST MAINTAIN 41F OR BELOW. COOLERS ARE TAGGED HELD FOR INSPECTION AND MUST NOT BE USED UNTIL REINSPECTED BY CHICAGO DEPARTMENT OF HEALTH. PRIORITY 7-38-005
- 38. INSECTS, RODENTS, & ANIMALS NOT PRESENT
- OBSERVED OVER 30 MICE DROPPINGS ON FLOOR IN PAPER STORAGE AREA, 30 MICE DROPPINGS ON FLOOR IN DRY STORAGE AREA, 20 MICE DROPPINGS ON FLOOR BEHIND AND BETWEEN COOKING EQUIPMENT, 10 MICE DROPPINGS ON FLOOR BETWEEN UTENSIL STORAGE SHELVING, 10 MICE DROPPINGS ON FLOOR IN REAR UTILITY DRAINAGE AREA, 5 MICE DROPPINGS ON BASE OF HOT HOLDING UNIT IN REAR STORAGE AREA, 20 MICE DROPPINGS INSIDE CABINET UNDER HAND SINK IN SERVERY, 20 MICE DROPPINGS AROUND COMPRESSOR UNIT UNDER UNUSED COOLERS IN SERVERY, 20 MICE DROPPINGS ON FLOOR AND WINDOW LEDGES NEAR VENDING MACHINES IN DINING AREA. INSTRUCTED MANAGER TO CALL AN EXTERMINATOR FOR SERVICE, CLEAN AND SANITIZE ALL AREAS. PRIORITY FOUNDATION 7-38-020(A)
- 49. NON-FOOD/FOOD CONTACT SURFACES CLEAN
- OBSERVED RESIDUE ON INTERIOR OF ICE MACHINE, DEBRIS ON INTERIOR AND EXTERIOR SURFACES OF SHELVING UNITS, HOLDING UNITS, CABINETS. INSTRUCTED MANAGER TO CLEAN AND MAINTAIN.
- 51. PLUMBING INSTALLED; PROPER BACKFLOW DEVICES
- OBSERVED LEAKING COLD WATER HANDLE ON HAND WASHING SINK IN MAIN KITCHEN. INSTRUCTED MANAGER TO REPAIR.
- 54. GARBAGE & REFUSE PROPERLY DISPOSED; FACILITIES MAINTAINED
- OBSERVED NO WASTE RECEPTACLE AT HAND WASHING SINK NEAR SERVERY. INSTRUCTED MANAGER TO PROVIDE.
- 55. PHYSICAL FACILITIES INSTALLED, MAINTAINED & CLEAN
- OBSERVED CEILING TILES NOT SECURE IN REAR STORAGE AREA. INSTRUCTED MANAGER TO REPAIR.
- 56. ADEQUATE VENTILATION & LIGHTING; DESIGNATED AREAS USED
- OBSERVED LOOSE LIGHT SHIELD IN REAR PREP AREA. INSTRUCTED MANAGER TO REPAIR.
- 10. ADEQUATE HANDWASHING SINKS PROPERLY SUPPLIED AND ACCESSIBLE
- Canvass
2 infractions
- 47. FOOD & NON-FOOD CONTACT SURFACES CLEANABLE, PROPERLY DESIGNED, CONSTRUCTED & USED
- OBSERVED INTERIOR OF WALK IN COOLER CEILINGS AND FLOORS WITH FOAM SEALANT PROTRUDING FROM SEAMS. INSTRUCTED MANAGER THAT SURFACES NEED TO BE SMOOTH AND EASILY CLEANABLE.
- 53. TOILET FACILITIES: PROPERLY CONSTRUCTED, SUPPLIED, & CLEANED
- OBSERVED NO COVERED WASTE RECEPTACLE IN STAFF TOILET ROOM. INSTRUCTED MANAGER TO PROVIDE AND MAINTAIN.
- 47. FOOD & NON-FOOD CONTACT SURFACES CLEANABLE, PROPERLY DESIGNED, CONSTRUCTED & USED
- Canvass
3 infractions
- 49. NON-FOOD/FOOD CONTACT SURFACES CLEAN
- MUST CLEAN THE INTERIOR OF THE ICE MACHINE.
- 51. PLUMBING INSTALLED; PROPER BACKFLOW DEVICES
- OBSERVED LEAKS AT THE FRONT HAND WASH SINK AND 1 COMP SINK WITH LEAKS AT THE BASE OF THE FIXTURES. MUST REPAIR AND MAINTAIN.
- 55. PHYSICAL FACILITIES INSTALLED, MAINTAINED & CLEAN
- FLOORS INSIDE THE REAR WALK IN FREEZER NEEDS CLEANING TO REMOVE DEBRIS.
- 49. NON-FOOD/FOOD CONTACT SURFACES CLEAN
- Canvass
2 infractions
- 2. CITY OF CHICAGO FOOD SERVICE SANITATION CERTIFICATE
- NO VALID CITY OF CHICAGO FOOD SANITATION CERTIFICATE POSTED FOR (PIC) PRIORITY FOUNDATION 7-38-012
- 5. PROCEDURES FOR RESPONDING TO VOMITING AND DIARRHEAL EVENTS
- OBSERVED PROCEDURE IN PLACE FOR VOMITING AND DIARRHEAL EVENTS. HOWEVER MUST PROVIDE ALL NECESSARY ITEMS IN POLICY INCLUDING DISPOSABLE GLOVES,FACE MASK, DISPOSABLE MOP AND APPROPRIATE SANITIZER TO KILL THE NOROVIRUS. PRIORITY FOUNDATION.
- 2. CITY OF CHICAGO FOOD SERVICE SANITATION CERTIFICATE
- Canvass
1 infraction
- 55. PHYSICAL FACILITIES INSTALLED, MAINTAINED & CLEAN
- OBSERVED A LEAK AT THE BASE OF THE COLD WATER KNOB ON THE HAND WASHING SINK IN THE FOOD PREPARATION AREA. INSTRUCTED TO FIX AND MAINTAIN. 6-501.13 FLOORS IN THE CORNERS AND THE INTERIOR OF THE FLOOR DRAINS IN THE STORAGE AND FOOD PREP AREA NEEDS TO BE CLEANED. INSTRUCTED TO REMOVE DIRT/DEBRIS FROM CORNERS AND FLOOR DRAINS. MAINTAIN SAME.
- 55. PHYSICAL FACILITIES INSTALLED, MAINTAINED & CLEAN
- Canvass
3 infractions
- 32. FOOD AND NON-FOOD CONTACT SURFACES PROPERLY DESIGNED, CONSTRUCTED AND MAINTAINED
- OBSERVED DAMAGED INSIDE OF DOOR FRAME AT #2 WALK-IN COOLER IN BASEMENT FOOD PREP AREA. INSTRUCTED TO REPAIR AND MAINTAIN.
- 34. FLOORS: CONSTRUCTED PER CODE, CLEANED, GOOD REPAIR, COVING INSTALLED, DUST-LESS CLEANING METHODS USED
- OBSERVED FLOOR INSIDE #2 WALK-IN COOLER IN NEED OF CLEANING. INSTRUCTED TO CLEAN AND MAINTAIN. OBSERVED LESS THAN 3 DEAD INSECTS ON FLOOR BEHIND REFRIGERATORS IN FOOD PREP AREA. INSTRUCTED TO CLEAN AND MAINTAIN.
- 38. VENTILATION: ROOMS AND EQUIPMENT VENTED AS REQUIRED: PLUMBING: INSTALLED AND MAINTAINED
- OBSERVED LOW WATER PRESSURE AT THE EXPOSED HAND SINK LOCATED IN ROOM 181- FOOD SERVING AREA/DINING AREA. FACILITY PROVIDED THE WORK ORDER INVOICE. INSTRUCTED TO REPAIR AND MAINTAIN.
- 32. FOOD AND NON-FOOD CONTACT SURFACES PROPERLY DESIGNED, CONSTRUCTED AND MAINTAINED
- Canvass Re-Inspection
0 infractions
- Canvass
3 infractions
- 18. NO EVIDENCE OF RODENT OR INSECT OUTER OPENINGS PROTECTED/RODENT PROOFED, A WRITTEN LOG SHALL BE MAINTAINED AVAILABLE TO THE INSPECTORS
- OBSERVED LIVE ROACH CRAWLING IN KITCHEN OFFICE AND LIVE ROACH CRAWLING ON FLOOR IN HALLWAY NEAR KITCHEN ENTRANCE. INSTRUCTED MANAGER TO CALL AN EXTERMINATOR FOR SERVICE, CLEAN AND SANITIZE ALL AREAS. SERIOUS VIOLATION 7-38-020
- 33. FOOD AND NON-FOOD CONTACT EQUIPMENT UTENSILS CLEAN, FREE OF ABRASIVE DETERGENTS
- CLEAN INTERIOR OF UTILITY SINK IN CLOSET NEAR ROOM 279.
- 34. FLOORS: CONSTRUCTED PER CODE, CLEANED, GOOD REPAIR, COVING INSTALLED, DUST-LESS CLEANING METHODS USED
- CLEAN FLOORS IN ALL SECOND FLOOR ELECTRICAL ROOMS.
- 18. NO EVIDENCE OF RODENT OR INSECT OUTER OPENINGS PROTECTED/RODENT PROOFED, A WRITTEN LOG SHALL BE MAINTAINED AVAILABLE TO THE INSPECTORS