Pineridge Apartments - Swimming Pool
2207 118 Street NW Edmonton AB T6J 5L3 · Aquatic Facility
10 inspections
- Risk Management Inspection
0 infractions
- Demand Inspection
1 infraction
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- The microbiological water sample submitted on 07/08/2025 was unsatisfactory: HPC 520 CFU/mL. Take all necessary action to ensure microbiologically safe water. Submit a new microbiological water sample at your earliest convenience once the water chemistry is balanced.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Risk Management Inspection
0 infractions
- Demand Inspection
1 infraction
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- The microbiological water sample result collected on 26/06/2025 [ID: 25EN-177E00718] was unsatisfactory: HPC 250 CFU/mL. Take all necessary action to ensure microbiologically safe water. Submit a new microbiological water sample at your earliest convenience once the water chemistry is balanced.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Risk Management Inspection
0 infractions
- Monitoring Inspection
3 infractions
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- The rate of filtration was 17.52 gpm/sq. ft, which exceeds the required maximum rate of filtration 15 gpm/ sq. ft (flow rate 110 gpm and filter area 6.2 ft sq.).
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- There was a discrepancy between the manual pH reading 7.32 (sampled from the automated controller) and the automated controller reading pH 7.16.
- 12. Are the general safety devices and physical conditions in this pool providing a safe environment (Critical)?
- The pool light was in disrepair: the glass was broken, and the light was removed from the pool basin (observed on the pool deck). Please replace the pool light.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Risk Management Inspection
0 infractions
- Demand Inspection
1 infraction
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- the sample 24EN-186E00471 submitted on July 4, 2024, was unsatisfactory: HPC 120
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Monitoring Inspection
1 infraction
- 18. Have plans for construction, renovations or alteration for the pool been submitted for written approval?
- The disinfection system was changed - Pulsar dry feeder was installed. Please provide information for the new disinfecting system.
- 18. Have plans for construction, renovations or alteration for the pool been submitted for written approval?
- Risk Management Inspection
0 infractions