Roland Michener Aquatic Centre - Teach/Warm Pool
3820 51A Street Red Deer AB T4N 5Y5 · Aquatic Facility
9 inspections
- Monitoring Inspection
0 infractions
- Monitoring Inspection
0 infractions
- Monitoring Inspection
1 infraction
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- CC – 1.15Alkalinity – 62 Please ensure that alkalinity level is maintained between 80-120 ppm. Too low of alkalinity in a swimming pool may affect the stability of pH and cause corrosive water negatively impacting pool basin, deck surfaces and equipment.
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- Monitoring Inspection
1 infraction
- 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
- Basin is being maintained.Pool temperature measured 44.4ºC
- 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
- Monitoring Inspection
0 infractions
- Monitoring Inspection
0 infractions
- Demand Inspection
0 infractions
- Demand Inspection
1 infraction
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- High HPC results 410 CFU's.Operator was taking the water samples from a spigot in the mechanical room.High HPC likely from this dead end line.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Risk Management Inspection
1 infraction
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- High HPC resultsOperator notified of this issue.Teach pool drained, cleaned, shocked chlorinated and the filter media was back washed.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?