Skip to content
Loading map…

Shouldice Aquatic Centre - Dive Pool

5303 Bowness Road NW Calgary AB T3B 0C3 · Aquatic Facility

Inspection summary

Shouldice Aquatic Centre - Dive Pool has been inspected 9 times by Alberta Health Services (Environmental Public Health) since December 8, 2023. The most recent inspection, on October 20, 2025, recorded 4 infractions.

None of the 9 inspections on record were free of infractions. No inspections are on record from the past 12 months. The higher-risk findings here relate to: Pool and spa water quality and Food temperature control.

The number of infractions per inspection has stayed roughly the same over time.

What these findings mean

Health authorities word their findings differently, so we group them by what they mean for the people using the facility. Higher-risk findings are the ones that could directly cause illness or injury, such as water that is not properly treated.

  • Pool and spa water qualityHigher risk

    For pools, spas and splash pads, inspectors test disinfectant levels, pH and water clarity, and check safety equipment. Water that is not properly treated can spread skin, ear and stomach infections.

    Recorded 22 times across 9 separate inspections, most recently on October 20, 2025. For example: Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?

  • Food temperature controlHigher risk

    Inspectors check that anything that has to be kept at a set temperature, such as chilled or hot food, or equipment like sterilizers, stays in its safe range and that accurate thermometers are on hand. With food, temperature problems are one of the most common causes of food poisoning.

    Recorded 7 times across 7 separate inspections, most recently on October 20, 2025. For example: Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?

  • Permits, records and postingLower risk

    Operating permits, water-test logs, posted bather rules and emergency procedures. Daily test logs are how operators show the water was checked and treated between inspections.

    Recorded 7 times across 7 separate inspections, most recently on October 20, 2025. For example: Are proper testing, monitoring, and other records being properly maintained?

About this data

These results come from Alberta Health Services (Environmental Public Health), which inspects food premises and other public facilities in this area. We republish the authority's public disclosure data and refresh it regularly; the official record is the final word.

9 inspections

  1. Risk Management Inspection

    4 infractions

    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • 1. The two filters' information/dimensions could not be accessed thus filtration rate could be calculated. Violation from Nov 2022.2. The pool has too much water and is submerging the filters. Reduce water level so that the skimmers can skim the water. Violation as of Dec 22 20231. Please clean the indicated area and ensure water level is high enough and flowing above the overflow drain to ensure complete removal of surface water and avoiding scum build up.2. Please provide filter information (filter area, maximum filtration rate etc.) to ensure that pool meets optimum filtration rate.
    • 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
      • There is a significant leak on the supply line behind the filters. Ensure this is repaired.
    • 15. Has an owner or owner's agent, if any, been identified and is the pool operated and maintained by a qualified pool operator?
      • Staff was not aware how to read the flow rate and the automated system. "Previous violation"Staff onsite and management in charge did not know how to find or convert flow rate read on the computer output. -All staff should know how to read flow rates so that adequate turnover and filtration rates can be determined.
    • 16. Are proper testing, monitoring, and other records being properly maintained?
      • The following reagents in the taylor test kits were expired:Small and large bottle of phenol redDPD 1 and 2ThiosulfateReplace reagents. Ensure expiry of reagents are checked often.
  2. Demand Inspection

    5 infractions

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • Oct 8 2025 Water sample results: 250 CFU/mL HPC. Please treat and resample
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • 1. The two filters' information/dimensions could not be accessed thus filtration rate could be calculated. Violation from Nov 2022.2. The pool has too much water and is submerging the filters. Reduce water level so that the skimmers can skim the water. Violation as of Dec 22 20231. Please clean the indicated area and ensure water level is high enough and flowing above the overflow drain to ensure complete removal of surface water and avoiding scum build up.2. Please provide filter information (filter area, maximum filtration rate etc.) to ensure that pool meets optimum filtration rate.
    • 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
      • There is a significant leak on the supply line behind the filters. Ensure this is repaired.
    • 15. Has an owner or owner's agent, if any, been identified and is the pool operated and maintained by a qualified pool operator?
      • Staff was not aware how to read the flow rate and the automated system. "Previous violation"Staff onsite and management in charge did not know how to find or convert flow rate read on the computer output. -All staff should know how to read flow rates so that adequate turnover and filtration rates can be determined.
    • 16. Are proper testing, monitoring, and other records being properly maintained?
      • The following reagents in the taylor test kits were expired:Small and large bottle of phenol redDPD 1 and 2ThiosulfateReplace reagents. Ensure expiry of reagents are checked often.
  3. Monitoring Inspection

    4 infractions

    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • 1. The two filters' information/dimensions could not be accessed thus filtration rate could be calculated. Violation from Nov 2022.2. The pool has too much water and is submerging the filters. Reduce water level so that the skimmers can skim the water. Violation as of Dec 22 20231. Please clean the indicated area and ensure water level is high enough and flowing above the overflow drain to ensure complete removal of surface water and avoiding scum build up.2. Please provide filter information (filter area, maximum filtration rate etc.) to ensure that pool meets optimum filtration rate.
    • 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
      • There is a significant leak on the supply line behind the filters. Ensure this is repaired.
    • 15. Has an owner or owner's agent, if any, been identified and is the pool operated and maintained by a qualified pool operator?
      • Staff was not aware how to read the flow rate and the automated system. "Previous violation"Staff onsite and management in charge did not know how to find or convert flow rate read on the computer output. -All staff should know how to read flow rates so that adequate turnover and filtration rates can be determined.
    • 16. Are proper testing, monitoring, and other records being properly maintained?
      • The following reagents in the taylor test kits were expired:Small and large bottle of phenol redDPD 1 and 2ThiosulfateReplace reagents. Ensure expiry of reagents are checked often.
  4. Demand Inspection

    4 infractions

    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • 1. The two filters' information/dimensions could not be accessed thus filtration rate could be calculated. Violation from Nov 2022.2. The pool has too much water and is submerging the filters. Reduce water level so that the skimmers can skim the water. Violation as of Dec 22 20231. Please clean the indicated area and ensure water level is high enough and flowing above the overflow drain to ensure complete removal of surface water and avoiding scum build up.2. Please provide filter information (filter area, maximum filtration rate etc.) to ensure that pool meets optimum filtration rate.
    • 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
      • There is a significant leak on the supply line behind the filters. Ensure this is repaired.
    • 15. Has an owner or owner's agent, if any, been identified and is the pool operated and maintained by a qualified pool operator?
      • Staff onsite and management in charge did not know how to find or convert flow rate read on the computer output. All staff should know how to read flow rates so that adequate turnover and filtration rates can be determined.
    • 16. Are proper testing, monitoring, and other records being properly maintained?
      • The following reagents in the taylor test kits were expired:Small and large bottle of phenol redDPD 1 and 2ThiosulfateReplace reagents. Ensure expiry of reagents are checked often.
  5. Demand Inspection

    5 infractions

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • Sample not processed as missing time and date of collection. Submit a resample on Oct 17/24.Spoke to Alana
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • 1. The two filters' information/dimensions could not be accessed thus filtration rate could be calculated. Violation from Nov 2022.2. The pool has too much water and is submerging the filters. Reduce water level so that the skimmers can skim the water. Violation as of Dec 22 20231. Please clean the indicated area and ensure water level is high enough and flowing above the overflow drain to ensure complete removal of surface water and avoiding scum build up.2. Please provide filter information (filter area, maximum filtration rate etc.) to ensure that pool meets optimum filtration rate.
    • 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
      • There is a significant leak on the supply line behind the filters. Ensure this is repaired.
    • 15. Has an owner or owner's agent, if any, been identified and is the pool operated and maintained by a qualified pool operator?
      • Staff onsite and management in charge did not know how to find or convert flow rate read on the computer output. All staff should know how to read flow rates so that adequate turnover and filtration rates can be determined.
    • 16. Are proper testing, monitoring, and other records being properly maintained?
      • The following reagents in the taylor test kits were expired:Small and large bottle of phenol redDPD 1 and 2ThiosulfateReplace reagents. Ensure expiry of reagents are checked often.
  6. Risk Management Inspection

    4 infractions

    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • 1. The two filters' information/dimensions could not be accessed thus filtration rate could be calculated. Violation from Nov 2022.2. The pool has too much water and is submerging the filters. Reduce water level so that the skimmers can skim the water. Violation as of Dec 22 20231. Please clean the indicated area and ensure water level is high enough and flowing above the overflow drain to ensure complete removal of surface water and avoiding scum build up.2. Please provide filter information (filter area, maximum filtration rate etc.) to ensure that pool meets optimum filtration rate.
    • 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
      • There is a significant leak on the supply line behind the filters. Ensure this is repaired.
    • 15. Has an owner or owner's agent, if any, been identified and is the pool operated and maintained by a qualified pool operator?
      • Staff onsite and management in charge did not know how to find or convert flow rate read on the computer output. All staff should know how to read flow rates so that adequate turnover and filtration rates can be determined.
    • 16. Are proper testing, monitoring, and other records being properly maintained?
      • The following reagents in the taylor test kits were expired:Small and large bottle of phenol redDPD 1 and 2ThiosulfateReplace reagents. Ensure expiry of reagents are checked often.
  7. Monitoring Inspection

    4 infractions

    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • 1. The two filters' information/dimensions could not be accessed thus filtration rate could be calculated. Violation from Nov 2022.2. The pool has too much water and is submerging the filters. Reduce water level so that the skimmers can skim the water. Violation as of Dec 22 20231. Please clean the indicated area and ensure water level is high enough and flowing above the overflow drain to ensure complete removal of surface water and avoiding scum build up.2. Please provide filter information (filter area, maximum filtration rate etc.) to ensure that pool meets optimum filtration rate.
    • 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
      • There is a significant leak on the supply line behind the filters. Ensure this is repaired.
    • 15. Has an owner or owner's agent, if any, been identified and is the pool operated and maintained by a qualified pool operator?
      • Staff onsite and management in charge did not know how to find or convert flow rate read on the computer output. All staff should know how to read flow rates so that adequate turnover and filtration rates can be determined.
    • 16. Are proper testing, monitoring, and other records being properly maintained?
      • The following reagents in the taylor test kits were expired:Small and large bottle of phenol redDPD 1 and 2ThiosulfateReplace reagents. Ensure expiry of reagents are checked often.
  8. Demand Inspection

    3 infractions

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • Sample received on December 21, 2023 not processed, received more than 24 hours after collection. Resample.
    • 06. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Critical)?
      • The flow meter for the dive pool was not working at the time of inspection, unable to assess flow rate.Please repair flow meter.
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • 1. Scum build-up was noticed in the overflow drain in the front of the dive pool near the marking "Deep Point"2. The two filters' information/dimensions could not be accessed thus filtration rate could be calculated.1. Please clean the indicated area and ensure water level is high enough and flowing above the overflow drain to ensure complete removal of surface water and avoiding scum build up.2. Please provide filter information (filter area, maximum filtration rate etc.) to ensure that pool meets optimum filtration rate.
  9. Demand Inspection

    3 infractions

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • WC-23-0077619 HPC 180 CFU/mLTreat and resample
    • 06. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Critical)?
      • The flow meter for the dive pool was not working at the time of inspection, unable to assess flow rate.Please repair flow meter.
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • 1. Scum build-up was noticed in the overflow drain in the front of the dive pool near the marking "Deep Point"2. The two filters' information/dimensions could not be accessed thus filtration rate could be calculated.1. Please clean the indicated area and ensure water level is high enough and flowing above the overflow drain to ensure complete removal of surface water and avoiding scum build up.2. Please provide filter information (filter area, maximum filtration rate etc.) to ensure that pool meets optimum filtration rate.

Nearby inspected facilities