Shouldice Aquatic Centre - Main Pool

5303 Bowness Road NW Calgary AB T3B 0C3 · Aquatic Facility

13 inspections

  1. Risk Management Inspection

    6 infractions

    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • The Total alkalinity was measured at 188 ppm.-Ensure that the total alkalinity is not less than 60milligrams/liter and greater than 180 milligrams per liter.
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • The pool has too much water and is submerging the filters. Reduce water level so that the skimmers can skim the water.
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • The turnover period of the main pool was 12.22 hours.-Ensure that 100 percentage volume of the water is recirculated within 4 hours.
    • 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
      • There is a water leak coming from the filters. Ensure this is repaired.
    • 15. Has an owner or owner's agent, if any, been identified and is the pool operated and maintained by a qualified pool operator?
      • Staff onsite and management in charge did not know how to find or convert flow rate read on the computer output. All staff should know how to read flow rates so that adequate turnover and filtration rates can be determined.
    • 16. Are proper testing, monitoring, and other records being properly maintained?
      • The following reagents in the taylor test kits were expired:Small and large bottle of phenol redDPD 1 and 2ThiosulfateReplace reagents. Ensure expiry of reagents are checked often.
  2. Demand Inspection

    7 infractions

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • Water sample dated April 1, 2026 could not be processed- no identification number on the bottle
    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • The Total alkalinity was measured at 188 ppm.-Ensure that the total alkalinity is not less than 60milligrams/liter and greater than 180 milligrams per liter.
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • The pool has too much water and is submerging the filters. Reduce water level so that the skimmers can skim the water.
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • The turnover period of the main pool was 12.22 hours.-Ensure that 100 percentage volume of the water is recirculated within 4 hours.
    • 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
      • There is a water leak coming from the filters. Ensure this is repaired.
    • 15. Has an owner or owner's agent, if any, been identified and is the pool operated and maintained by a qualified pool operator?
      • Staff onsite and management in charge did not know how to find or convert flow rate read on the computer output. All staff should know how to read flow rates so that adequate turnover and filtration rates can be determined.
    • 16. Are proper testing, monitoring, and other records being properly maintained?
      • The following reagents in the taylor test kits were expired:Small and large bottle of phenol redDPD 1 and 2ThiosulfateReplace reagents. Ensure expiry of reagents are checked often.
  3. Demand Inspection

    7 infractions

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • Water sample cancelled due to no time or date indicated on form. - please sample and submit for testing.
    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • The Total alkalinity was measured at 188 ppm.-Ensure that the total alkalinity is not less than 60milligrams/liter and greater than 180 milligrams per liter.
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • The pool has too much water and is submerging the filters. Reduce water level so that the skimmers can skim the water.
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • The turnover period of the main pool was 12.22 hours.-Ensure that 100 percentage volume of the water is recirculated within 4 hours.
    • 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
      • There is a water leak coming from the filters. Ensure this is repaired.
    • 15. Has an owner or owner's agent, if any, been identified and is the pool operated and maintained by a qualified pool operator?
      • Staff onsite and management in charge did not know how to find or convert flow rate read on the computer output. All staff should know how to read flow rates so that adequate turnover and filtration rates can be determined.
    • 16. Are proper testing, monitoring, and other records being properly maintained?
      • The following reagents in the taylor test kits were expired:Small and large bottle of phenol redDPD 1 and 2ThiosulfateReplace reagents. Ensure expiry of reagents are checked often.
  4. Monitoring Inspection

    6 infractions

    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • The Total alkalinity was measured at 188 ppm.-Ensure that the total alkalinity is not less than 60milligrams/liter and greater than 180 milligrams per liter.
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • The pool has too much water and is submerging the filters. Reduce water level so that the skimmers can skim the water.
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • The turnover period of the main pool was 12.22 hours.-Ensure that 100 percentage volume of the water is recirculated within 4 hours.
    • 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
      • There is a water leak coming from the filters. Ensure this is repaired.
    • 15. Has an owner or owner's agent, if any, been identified and is the pool operated and maintained by a qualified pool operator?
      • Staff onsite and management in charge did not know how to find or convert flow rate read on the computer output. All staff should know how to read flow rates so that adequate turnover and filtration rates can be determined.
    • 16. Are proper testing, monitoring, and other records being properly maintained?
      • The following reagents in the taylor test kits were expired:Small and large bottle of phenol redDPD 1 and 2ThiosulfateReplace reagents. Ensure expiry of reagents are checked often.
  5. Demand Inspection

    5 infractions

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • HPC count: 160 CFUSample taken by Cassidy -Treat and Resample
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • The pool has too much water and is submerging the filters. Reduce water level so that the skimmers can skim the water.
    • 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
      • There is a water leak coming from the filters. Ensure this is repaired.
    • 15. Has an owner or owner's agent, if any, been identified and is the pool operated and maintained by a qualified pool operator?
      • Staff onsite and management in charge did not know how to find or convert flow rate read on the computer output. All staff should know how to read flow rates so that adequate turnover and filtration rates can be determined.
    • 16. Are proper testing, monitoring, and other records being properly maintained?
      • The following reagents in the taylor test kits were expired:Small and large bottle of phenol redDPD 1 and 2ThiosulfateReplace reagents. Ensure expiry of reagents are checked often.
  6. Demand Inspection

    4 infractions

    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • The pool has too much water and is submerging the filters. Reduce water level so that the skimmers can skim the water.
    • 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
      • There is a water leak coming from the filters. Ensure this is repaired.
    • 15. Has an owner or owner's agent, if any, been identified and is the pool operated and maintained by a qualified pool operator?
      • Staff onsite and management in charge did not know how to find or convert flow rate read on the computer output. All staff should know how to read flow rates so that adequate turnover and filtration rates can be determined.
    • 16. Are proper testing, monitoring, and other records being properly maintained?
      • The following reagents in the taylor test kits were expired:Small and large bottle of phenol redDPD 1 and 2ThiosulfateReplace reagents. Ensure expiry of reagents are checked often.
  7. Demand Inspection

    5 infractions

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • Sample not processed as missing time and date of collection. Submit a resample on Oct 17/24.Spoke to Alana
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • The pool has too much water and is submerging the filters. Reduce water level so that the skimmers can skim the water.
    • 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
      • There is a water leak coming from the filters. Ensure this is repaired.
    • 15. Has an owner or owner's agent, if any, been identified and is the pool operated and maintained by a qualified pool operator?
      • Staff onsite and management in charge did not know how to find or convert flow rate read on the computer output. All staff should know how to read flow rates so that adequate turnover and filtration rates can be determined.
    • 16. Are proper testing, monitoring, and other records being properly maintained?
      • The following reagents in the taylor test kits were expired:Small and large bottle of phenol redDPD 1 and 2ThiosulfateReplace reagents. Ensure expiry of reagents are checked often.
  8. Demand Inspection

    5 infractions

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • HPC 1880 Treat and resample
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • The pool has too much water and is submerging the filters. Reduce water level so that the skimmers can skim the water.
    • 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
      • There is a water leak coming from the filters. Ensure this is repaired.
    • 15. Has an owner or owner's agent, if any, been identified and is the pool operated and maintained by a qualified pool operator?
      • Staff onsite and management in charge did not know how to find or convert flow rate read on the computer output. All staff should know how to read flow rates so that adequate turnover and filtration rates can be determined.
    • 16. Are proper testing, monitoring, and other records being properly maintained?
      • The following reagents in the taylor test kits were expired:Small and large bottle of phenol redDPD 1 and 2ThiosulfateReplace reagents. Ensure expiry of reagents are checked often.
  9. Demand Inspection

    5 infractions

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • HPC 1880 Treat and resample
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • The pool has too much water and is submerging the filters. Reduce water level so that the skimmers can skim the water.
    • 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
      • There is a water leak coming from the filters. Ensure this is repaired.
    • 15. Has an owner or owner's agent, if any, been identified and is the pool operated and maintained by a qualified pool operator?
      • Staff onsite and management in charge did not know how to find or convert flow rate read on the computer output. All staff should know how to read flow rates so that adequate turnover and filtration rates can be determined.
    • 16. Are proper testing, monitoring, and other records being properly maintained?
      • The following reagents in the taylor test kits were expired:Small and large bottle of phenol redDPD 1 and 2ThiosulfateReplace reagents. Ensure expiry of reagents are checked often.
  10. Risk Management Inspection

    4 infractions

    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • The pool has too much water and is submerging the filters. Reduce water level so that the skimmers can skim the water.
    • 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
      • There is a water leak coming from the filters. Ensure this is repaired.
    • 15. Has an owner or owner's agent, if any, been identified and is the pool operated and maintained by a qualified pool operator?
      • Staff onsite and management in charge did not know how to find or convert flow rate read on the computer output. All staff should know how to read flow rates so that adequate turnover and filtration rates can be determined.
    • 16. Are proper testing, monitoring, and other records being properly maintained?
      • The following reagents in the taylor test kits were expired:Small and large bottle of phenol redDPD 1 and 2ThiosulfateReplace reagents. Ensure expiry of reagents are checked often.
  11. Monitoring Inspection

    4 infractions

    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • The pool has too much water and is submerging the filters. Reduce water level so that the skimmers can skim the water.
    • 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
      • There is a water leak coming from the filters. Ensure this is repaired.
    • 15. Has an owner or owner's agent, if any, been identified and is the pool operated and maintained by a qualified pool operator?
      • Staff onsite and management in charge did not know how to find or convert flow rate read on the computer output. All staff should know how to read flow rates so that adequate turnover and filtration rates can be determined.
    • 16. Are proper testing, monitoring, and other records being properly maintained?
      • The following reagents in the taylor test kits were expired:Small and large bottle of phenol redDPD 1 and 2ThiosulfateReplace reagents. Ensure expiry of reagents are checked often.
  12. Demand Inspection

    3 infractions

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • Sample received on December 21, 2023 not processed, received more than 24 hours after collection. Resample.
    • 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
      • The Free Available Chlorine residual was measured at 0.91 ppm which is below the minimum requirement of 1.0ppm.Please raise chlorine level to at least 1.0ppm and maintain minimum requirement daily.
    • 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
      • The rails on the left and right side of the pool close to the markings 1.4m were loose and not properly securedPlease Tighten/Secure all rails
  13. Demand Inspection

    3 infractions

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • WC-23-0077602 HPC 180 cfu/ml Treat and Resample
    • 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
      • The Free Available Chlorine residual was measured at 0.91 ppm which is below the minimum requirement of 1.0ppm.Please raise chlorine level to at least 1.0ppm and maintain minimum requirement daily.
    • 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
      • The rails on the left and right side of the pool close to the markings 1.4m were loose and not properly securedPlease Tighten/Secure all rails