Sierras Of Inglewood - Whirlpool

45 Inglewood Drive St. Albert AB T8N 0B8 · Aquatic Facility

11 inspections

  1. Monitoring Inspection

    4 infractions

    • 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
      • The free available chlorine was less than 2.0 ppm in a basin above 30 degrees C.
    • 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
      • pH was 6.66, please increase to a minimum of 6.8.
    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • Alkalinity was 57 ppm, please increase to a minimum of 60 ppm.
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • June 30, 2026: Turnover rate is not meeting the required 20 minutes. Increase flow rate to 124 gpm to meet requirement. January 15, 2025: Turnover rate is still just slightly over the required 20 minutes at 20.6 minutes. Please increase the total flow rate slightly. April 4 2024: The turnover rate is too slow. Please increase the total flow rate to ensure a 20 minute or less turnover.(Pool volume: 2470 gal, total flow rate: 112 GPM 2470 gal/112 gpm/60 = Turnover period: 37 minutes.)
  2. Risk Management Inspection

    2 infractions

    • 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
      • The free available chlorine was less than 2.0 ppm in a basin above 30 degrees C.
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • June 30, 2026: Turnover rate is not meeting the required 20 minutes. Increase flow rate to 124 gpm to meet requirement. January 15, 2025: Turnover rate is still just slightly over the required 20 minutes at 20.6 minutes. Please increase the total flow rate slightly. April 4 2024: The turnover rate is too slow. Please increase the total flow rate to ensure a 20 minute or less turnover.(Pool volume: 2470 gal, total flow rate: 112 GPM 2470 gal/112 gpm/60 = Turnover period: 37 minutes.)
  3. Risk Management Inspection

    1 infraction

    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • January 15, 2025: Turnover rate is still just slightly over the required 20 minutes at 20.6 minutes. Please increase the total flow rate slightly. April 4 2024: The turnover rate is too slow. Please increase the total flow rate to ensure a 20 minute or less turnover.(Pool volume: 2470 gal, total flow rate: 112 GPM 2470 gal/112 gpm/60 = Turnover period: 37 minutes.)
  4. Demand Inspection

    3 infractions

    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • Alkalinity was only 35 ppm.
    • 06. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Critical)?
      • The filter circulation pump was non-operational at time of inspection.
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • January 15, 2025: Turnover rate is still just slightly over the required 20 minutes at 20.6 minutes. Please increase the total flow rate slightly. April 4 2024: The turnover rate is too slow. Please increase the total flow rate to ensure a 20 minute or less turnover.(Pool volume: 2470 gal, total flow rate: 112 GPM 2470 gal/112 gpm/60 = Turnover period: 37 minutes.)
  5. Risk Management Inspection

    1 infraction

    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • January 15, 2025: Turnover rate is still just slightly over the required 20 minutes at 20.6 minutes. Please increase the total flow rate slightly. April 4 2024: The turnover rate is too slow. Please increase the total flow rate to ensure a 20 minute or less turnover.(Pool volume: 2470 gal, total flow rate: 112 GPM 2470 gal/112 gpm/60 = Turnover period: 37 minutes.)
  6. Demand Inspection

    2 infractions

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • HPC was 180 cfu/100 ml.
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • January 15, 2025: Turnover rate is still just slightly over the required 20 minutes at 20.6 minutes. Please increase the total flow rate slightly. April 4 2024: The turnover rate is too slow. Please increase the total flow rate to ensure a 20 minute or less turnover.(Pool volume: 2470 gal, total flow rate: 112 GPM 2470 gal/112 gpm/60 = Turnover period: 37 minutes.)
  7. Risk Management Inspection

    1 infraction

    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • January 15, 2025: Turnover rate is still just slightly over the required 20 minutes at 20.6 minutes. Please increase the total flow rate slightly. April 4 2024: The turnover rate is too slow. Please increase the total flow rate to ensure a 20 minute or less turnover.(Pool volume: 2470 gal, total flow rate: 112 GPM 2470 gal/112 gpm/60 = Turnover period: 37 minutes.)
  8. Demand Inspection

    2 infractions

    • 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
      • TC was isolated.
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • January 15, 2025: Turnover rate is still just slightly over the required 20 minutes at 20.6 minutes. Please increase the total flow rate slightly. April 4 2024: The turnover rate is too slow. Please increase the total flow rate to ensure a 20 minute or less turnover.(Pool volume: 2470 gal, total flow rate: 112 GPM 2470 gal/112 gpm/60 = Turnover period: 37 minutes.)
  9. Demand Inspection

    2 infractions

    • 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
      • TC was isolated in the preliminary sample.
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • January 15, 2025: Turnover rate is still just slightly over the required 20 minutes at 20.6 minutes. Please increase the total flow rate slightly. April 4 2024: The turnover rate is too slow. Please increase the total flow rate to ensure a 20 minute or less turnover.(Pool volume: 2470 gal, total flow rate: 112 GPM 2470 gal/112 gpm/60 = Turnover period: 37 minutes.)
  10. Monitoring Inspection

    1 infraction

    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • January 15, 2025: Turnover rate is still just slightly over the required 20 minutes at 20.6 minutes. Please increase the total flow rate slightly. April 4 2024: The turnover rate is too slow. Please increase the total flow rate to ensure a 20 minute or less turnover.(Pool volume: 2470 gal, total flow rate: 112 GPM 2470 gal/112 gpm/60 = Turnover period: 37 minutes.)
  11. Monitoring Inspection

    2 infractions

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • A bacteriological sample was not submitted for the whirlpool for the last two weeks. Please take and submit one for testing as soon as possible.
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • The turnover rate is too slow. Please increase the total flow rate to ensure a 20 minute or less turnover.(Pool volume: 2470 gal, total flow rate: 112 GPM 2470 gal/112 gpm/60 = Turnover period: 37 minutes.)