Sierras Of Inglewood - Whirlpool

45 Inglewood Drive St. Albert AB T8N 0B8 · Aquatic Facility

Inspection summary

Sierras Of Inglewood - Whirlpool has been inspected 12 times by Alberta Health Services (Environmental Public Health) since April 4, 2024. The most recent inspection, on July 6, 2026, recorded 1 infraction.

None of the 12 inspections on record were free of infractions. In the past 12 months there were 8 inspections with 15 infractions recorded. The higher-risk findings here relate to: Pool and spa water quality and Chemicals and toxic substances.

The number of infractions per inspection has stayed roughly the same over time.

What these findings mean

Health authorities word their findings differently, so we group them by what they mean for the people using the facility. Higher-risk findings are the ones that could directly cause illness or injury, such as water that is not properly treated.

  • Pool and spa water qualityHigher risk

    For pools, spas and splash pads, inspectors test disinfectant levels, pH and water clarity, and check safety equipment. Water that is not properly treated can spread skin, ear and stomach infections.

    Recorded 17 times across 12 separate inspections, most recently on July 6, 2026. For example: Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?

  • Chemicals and toxic substancesHigher risk

    Pool chemicals such as chlorine and acid must be labelled, stored apart from each other and handled safely. Mixing them by mistake can release toxic gas, so storage and handling problems are treated seriously.

    Recorded 5 times across 3 separate inspections, most recently on June 30, 2026. For example: Is the chemical quality of the water in this pool satisfactory (Critical)?

About this data

These results come from Alberta Health Services (Environmental Public Health), which inspects food premises and other public facilities in this area. We republish the authority's public disclosure data and refresh it regularly; the official record is the final word.

12 inspections

  1. Risk Management Inspection

    1 infraction

    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • June 30, 2026: Turnover rate is not meeting the required 20 minutes. Increase flow rate to 124 gpm to meet requirement. January 15, 2025: Turnover rate is still just slightly over the required 20 minutes at 20.6 minutes. Please increase the total flow rate slightly. April 4 2024: The turnover rate is too slow. Please increase the total flow rate to ensure a 20 minute or less turnover.(Pool volume: 2470 gal, total flow rate: 112 GPM 2470 gal/112 gpm/60 = Turnover period: 37 minutes.)
  2. Monitoring Inspection

    4 infractions

    • 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
      • The free available chlorine was less than 2.0 ppm in a basin above 30 degrees C.
    • 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
      • pH was 6.66, please increase to a minimum of 6.8.
    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • Alkalinity was 57 ppm, please increase to a minimum of 60 ppm.
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • June 30, 2026: Turnover rate is not meeting the required 20 minutes. Increase flow rate to 124 gpm to meet requirement. January 15, 2025: Turnover rate is still just slightly over the required 20 minutes at 20.6 minutes. Please increase the total flow rate slightly. April 4 2024: The turnover rate is too slow. Please increase the total flow rate to ensure a 20 minute or less turnover.(Pool volume: 2470 gal, total flow rate: 112 GPM 2470 gal/112 gpm/60 = Turnover period: 37 minutes.)
  3. Risk Management Inspection

    2 infractions

    • 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
      • The free available chlorine was less than 2.0 ppm in a basin above 30 degrees C.
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • June 30, 2026: Turnover rate is not meeting the required 20 minutes. Increase flow rate to 124 gpm to meet requirement. January 15, 2025: Turnover rate is still just slightly over the required 20 minutes at 20.6 minutes. Please increase the total flow rate slightly. April 4 2024: The turnover rate is too slow. Please increase the total flow rate to ensure a 20 minute or less turnover.(Pool volume: 2470 gal, total flow rate: 112 GPM 2470 gal/112 gpm/60 = Turnover period: 37 minutes.)
  4. Risk Management Inspection

    1 infraction

    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • January 15, 2025: Turnover rate is still just slightly over the required 20 minutes at 20.6 minutes. Please increase the total flow rate slightly. April 4 2024: The turnover rate is too slow. Please increase the total flow rate to ensure a 20 minute or less turnover.(Pool volume: 2470 gal, total flow rate: 112 GPM 2470 gal/112 gpm/60 = Turnover period: 37 minutes.)
  5. Demand Inspection

    3 infractions

    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • Alkalinity was only 35 ppm.
    • 06. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Critical)?
      • The filter circulation pump was non-operational at time of inspection.
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • January 15, 2025: Turnover rate is still just slightly over the required 20 minutes at 20.6 minutes. Please increase the total flow rate slightly. April 4 2024: The turnover rate is too slow. Please increase the total flow rate to ensure a 20 minute or less turnover.(Pool volume: 2470 gal, total flow rate: 112 GPM 2470 gal/112 gpm/60 = Turnover period: 37 minutes.)
  6. Risk Management Inspection

    1 infraction

    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • January 15, 2025: Turnover rate is still just slightly over the required 20 minutes at 20.6 minutes. Please increase the total flow rate slightly. April 4 2024: The turnover rate is too slow. Please increase the total flow rate to ensure a 20 minute or less turnover.(Pool volume: 2470 gal, total flow rate: 112 GPM 2470 gal/112 gpm/60 = Turnover period: 37 minutes.)
  7. Demand Inspection

    2 infractions

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • HPC was 180 cfu/100 ml.
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • January 15, 2025: Turnover rate is still just slightly over the required 20 minutes at 20.6 minutes. Please increase the total flow rate slightly. April 4 2024: The turnover rate is too slow. Please increase the total flow rate to ensure a 20 minute or less turnover.(Pool volume: 2470 gal, total flow rate: 112 GPM 2470 gal/112 gpm/60 = Turnover period: 37 minutes.)
  8. Risk Management Inspection

    1 infraction

    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • January 15, 2025: Turnover rate is still just slightly over the required 20 minutes at 20.6 minutes. Please increase the total flow rate slightly. April 4 2024: The turnover rate is too slow. Please increase the total flow rate to ensure a 20 minute or less turnover.(Pool volume: 2470 gal, total flow rate: 112 GPM 2470 gal/112 gpm/60 = Turnover period: 37 minutes.)
  9. Demand Inspection

    2 infractions

    • 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
      • TC was isolated.
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • January 15, 2025: Turnover rate is still just slightly over the required 20 minutes at 20.6 minutes. Please increase the total flow rate slightly. April 4 2024: The turnover rate is too slow. Please increase the total flow rate to ensure a 20 minute or less turnover.(Pool volume: 2470 gal, total flow rate: 112 GPM 2470 gal/112 gpm/60 = Turnover period: 37 minutes.)
  10. Demand Inspection

    2 infractions

    • 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
      • TC was isolated in the preliminary sample.
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • January 15, 2025: Turnover rate is still just slightly over the required 20 minutes at 20.6 minutes. Please increase the total flow rate slightly. April 4 2024: The turnover rate is too slow. Please increase the total flow rate to ensure a 20 minute or less turnover.(Pool volume: 2470 gal, total flow rate: 112 GPM 2470 gal/112 gpm/60 = Turnover period: 37 minutes.)
  11. Monitoring Inspection

    1 infraction

    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • January 15, 2025: Turnover rate is still just slightly over the required 20 minutes at 20.6 minutes. Please increase the total flow rate slightly. April 4 2024: The turnover rate is too slow. Please increase the total flow rate to ensure a 20 minute or less turnover.(Pool volume: 2470 gal, total flow rate: 112 GPM 2470 gal/112 gpm/60 = Turnover period: 37 minutes.)
  12. Monitoring Inspection

    2 infractions

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • A bacteriological sample was not submitted for the whirlpool for the last two weeks. Please take and submit one for testing as soon as possible.
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • The turnover rate is too slow. Please increase the total flow rate to ensure a 20 minute or less turnover.(Pool volume: 2470 gal, total flow rate: 112 GPM 2470 gal/112 gpm/60 = Turnover period: 37 minutes.)