Super 8 Shawnessy - Whirlpool
60 Shawville Road SE Calgary AB T2Y 3S6 · Aquatic Facility
Inspection summary
Super 8 Shawnessy - Whirlpool has been inspected 16 times by Alberta Health Services (Environmental Public Health) since January 15, 2024. The most recent inspection, on July 24, 2026, found no infractions.
3 of 16 inspections on record found no infractions at all. In the past 12 months there were 4 inspections with 5 infractions recorded. The higher-risk findings here relate to: Pool and spa water quality, Chemicals and toxic substances and Food temperature control.
Recent inspections have recorded fewer infractions than earlier ones, so the record is improving.
What these findings mean
Health authorities word their findings differently, so we group them by what they mean for the people using the facility. Higher-risk findings are the ones that could directly cause illness or injury, such as water that is not properly treated.
Pool and spa water qualityHigher risk
For pools, spas and splash pads, inspectors test disinfectant levels, pH and water clarity, and check safety equipment. Water that is not properly treated can spread skin, ear and stomach infections.
Recorded 17 times across 12 separate inspections, most recently on May 31, 2026. For example:
Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
Chemicals and toxic substancesHigher risk
Pool chemicals such as chlorine and acid must be labelled, stored apart from each other and handled safely. Mixing them by mistake can release toxic gas, so storage and handling problems are treated seriously.
Recorded 4 times across 3 separate inspections, most recently on July 14, 2026. For example:
Is the chemical quality of the water in this pool satisfactory (Critical)?
Food temperature controlHigher risk
Inspectors check that anything that has to be kept at a set temperature, such as chilled or hot food, or equipment like sterilizers, stays in its safe range and that accurate thermometers are on hand. With food, temperature problems are one of the most common causes of food poisoning.
Recorded 4 times across 4 separate inspections, most recently on July 14, 2026. For example:
Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
Food safety training and certificationLower risk
Many jurisdictions require trained pool operators and certified lifeguards. These findings mean required training, certification or staffing records were missing at the time of inspection.
Recorded 6 times across 6 separate inspections, most recently on October 4, 2024. For example:
Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
About this data
These results come from Alberta Health Services (Environmental Public Health), which inspects food premises and other public facilities in this area. We republish the authority's public disclosure data and refresh it regularly; the official record is the final word.
16 inspections
- Risk Management Inspection
0 infractions
- Monitoring Inspection
3 infractions
- 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
- The pH of the whirlpool was measured at 8.18. **Adjust and check the whirlpool's water chemistry more frequently. Whirlpools must be maintained at a pH between 6.8-7.6.
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- Combined chlorine was at 2.9ppm when measured.***Ensure that combined chlorine is kept at the lowest level possible.
- 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
- A whirlpool skimmer was observed to be upturned and not operating properly,**Check skimmers more often to ensure the pool remains in a clean and sanitary condition.
- 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
- Demand Inspection
1 infraction
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Water sample was not processed because the time of collection was not recorded.Please submit a new sample and ensure all information is completed accurately on the requisition form.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Demand Inspection
1 infraction
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Recent water sample submitted was not processed - sample was received more than 24 hours after collection.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Demand Inspection
1 infraction
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- The water sample collected on Sep 26, 2025 was cancelled by the Prov Lab as there was no identification number on the bottle. -resample
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Demand Inspection
1 infraction
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- July 4th water sample information was not legible so the test was cancelled by the lab. Pool operator had already left when PHI called. Left message through reception for pool operator to ensure information is legible on the sample next week.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Risk Management Inspection
0 infractions
- Risk Management Inspection
3 infractions
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- 1. Automated system was not adequately calibrated. Chlorine manual reading was not consistent with automated readings.- Calibrate the automated system.
- 09. Are general nuisance conditions, other than those noted in other violations, being prevented at this pool (Critical)?
- 1. Weirs were getting stuck in skimmers and were not freely floating, therefore not providing adequate skimming.- Adequate skimming through the skimmers is required. 2. Flow meter for Sch 40 was installed on Sch 80 pipe. Therefore, the operational flow could not be verified.- Verify if the manufacturer's installation requirements were followed.- Flow must be password protected.
- 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
- 1. Some tiles on the pool deck were cracked and grout was missing creating sharp edges. -Repair2. Watter was pooling on the north side of the whirlpool. - Repair the pool deck3. Some cement/ grout around floor drains was still soft.- Pool deck must be impervious to moisture and easy to clean.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Initial Inspection
2 infractions
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- 1. Automated system was not calibrated.
- 09. Are general nuisance conditions, other than those noted in other violations, being prevented at this pool (Critical)?
- 1. Door to the chemical room was not installed.2. Construction equipment was still present on the deck.3. Cemented deck area was not sealed to make it impervious to moisture.4. Skimmers were missing weirs.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Risk Management Inspection
0 infractions
- Demand Inspection
5 infractions
- 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
- Free chlorine level measure 0 ppm. - Free chlorine residual in water must be maintained at 2 ppm or higher.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- According to the daily pool records, chlorine has been added manually instead of being added by the automated system. The automated system is not providing adequate chemical levels. Automated monitoring system is not consistent with manual chemical readings. Manual chlorine levels were reading 0 ppm and pH 7.26. Automated system readings were reading chlorine 0.87 ppm and pH 8.64.- Calibrate/ repair the system so the automated system is providing adequate chemical levels and is consistent with manual readings.
- 12. Are the general safety devices and physical conditions in this pool providing a safe environment (Critical)?
- Whirlpool water was cloudy and main drains were not visible- Resolve cloudiness of the water. Ensure that water is adequately clear at all times.
- 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
- Whirlpool basin is losing water. Staff has been adding fresh water several times a day to maintain a required water level. - Repair the basin. Maintain adequate water level at all times.
- 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
- Anti-entrapment assessment for jet system is incorrect. - Update the assessment form.
- 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
- Monitoring Inspection
5 infractions
- 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
- Free chlorine level measure 0 ppm. - Free chlorine residual in water must be maintained at 2 ppm or higher.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- According to the daily pool records, chlorine has been added manually instead of being added by the automated system. The automated system is not providing adequate chemical levels. Automated monitoring system is not consistent with manual chemical readings. Manual chlorine levels were reading 0 ppm and pH 7.26. Automated system readings were reading chlorine 0.87 ppm and pH 8.64.- Calibrate/ repair the system so the automated system is providing adequate chemical levels and is consistent with manual readings.
- 12. Are the general safety devices and physical conditions in this pool providing a safe environment (Critical)?
- Whirlpool water was cloudy and main drains were not visible- Resolve cloudiness of the water. Ensure that water is adequately clear at all times.
- 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
- Whirlpool basin is losing water. Staff has been adding fresh water several times a day to maintain a required water level. - Repair the basin. Maintain adequate water level at all times.
- 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
- Anti-entrapment assessment for jet system is incorrect. - Update the assessment form.
- 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
- Risk Management Inspection
2 infractions
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Automated monitoring system is not consistent with manual chemical readings and it's not providing adequate chemicals levels. - Calibrate/ repair the system so the automated system is providing consistent readings with manual readings.
- 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
- Anti-entrapment assessment for jet system is incorrect. - Update the assessment form.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Monitoring Inspection
2 infractions
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Automated monitoring system is not consistent with manual chemical readings and it's not providing adequate chemicals levels. Free chlorine tested at 1.91 ppm.- Calibrate/ repair the system so the automated system is providing consistent readings with manual readings. - Maintain free chlorine level at 2 ppm minimum.
- 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
- Anti-entrapment assessment for jet system is incorrect. - Update the assessment form.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Risk Management Inspection
2 infractions
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Automated monitoring system is not consistent with manual chemical readings and it's not providing adequate chemicals levels. pH tested at 8.- Calibrate/ repair the system so the automated system is providing consistent readings with manual readings. - Maintain pH level between 6.8-7.6
- 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
- Anti-entrapment assessment for jet system is incorrect. - Update the assessment form.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Demand Inspection
3 infractions
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Bacteriological water sample submitted on January 12/24 had Pseudomonas isolated, Total Coliforms present and HPC of 510 cfu/ml. - Treat the whirlpool water, drain, thoroughly clean the basin, refill, chemical balance the water and submit a resample.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Automated monitoring system is not consistent with manual chemical readings. Manual free chlorine testing was 0.75 ppm and automated system was reading 5 ppm. After calibration, the manual reading was 3.96 ppm and automated system's reading 1.16 ppm. Adjust/ repair the system so the automated system is providing consistent readings with manual readings.
- 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
- Anti-entrapment assessment was incomplete. - Complete the assessment and provide all the necessary supporting documentation.
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
Nearby inspected facilities
- Super 8 Shawnessy - Swimming Pool
60 Shawville Road SE Calgary AB T2Y 3S6
8 inspections
- Super 8 Shawnessy - Common
60 Shawville Road SE Calgary AB T2Y 3S6
4 inspections
- Fresh Path
100 - 250 Shawville Boulevard SE Calgary AB T2Y 2Z7
1 inspection
- Bronze Baxx Tanning
101 - 250 Shawville Boulevard SE Calgary AB T2Y 2Z7
1 inspection
- Calgary Co-op 14 - Food Store
100 - 250 Shawville Boulevard SE Calgary AB T2Y 2Z7
6 inspections
- OPA! of Greece 120
118 - 250 Shawville Boulevard SE Calgary AB T2Y 2Z7
7 inspections
- BeU
120 - 250 Shawville Boulevard SE Calgary AB T2Y 2Z7
3 inspections
- Happy Cup 4
128 - 250 Shawville Boulevard SE Calgary AB T2Y 2Z7
1 inspection