Thorhild Pool
402 6 Avenue Thorhild AB T0A 3J0 · Aquatic Facility
10 inspections
- Monitoring Inspection
0 infractions
- Monitoring Inspection
0 infractions
- Risk Management Inspection
0 infractions
- Demand Inspection
1 infraction
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- The sample 24EN-178E00860 has total coliform bacteria present. This could indicate a problem with the disinfection of the pool water. Ensure the pool water free chlorine is raised to 10 ppm for 1 turnover (5 hours) and that another sample is submitted on Tuesday July 2.
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Demand Inspection
1 infraction
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- The sample 24EN-178E00860 has total coliform bacteria present. This could indicate a problem with the disinfection of the pool water. Ensure the pool water free chlorine is raised to 10 ppm for 1 turnover (5 hours) and that another sample is submitted on Tuesday July 2.
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Demand Inspection
1 infraction
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- The HPC for sample 24EN-171E00901 is 280 CFU/ml. This could indicate a problem with the disinfection of the pool water. Ensure the pool water free chlorine is raised to 10 ppm for 1 turnover (5 hours) and that another sample is submitted on Tuesday June 25.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Demand Inspection
1 infraction
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- The HPC for sample 24En-164E00640 is 420 CFU/ml. This could indicate a problem with the disinfection of the pool water. Ensure all the pool chemical parameters are acceptable and that another sample is submitted on Tuesday June 18.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Monitoring Inspection
0 infractions
- Risk Management Inspection
0 infractions
- Demand Inspection
1 infraction
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- The HPC count of sample WE-23-0078126 is 2710 CFU/mL. This could indicate a failure of the disinfection system. Ensure all of the chemical parameters are satisfactory and that another pool water sample is submitted.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?