YMCA Pool - Indoor Pool

235 McNabb Street Sault Ste. Marie ON P6B 1Y3 · Indoor Pool

Inspection summary

YMCA Pool - Indoor Pool has been inspected 9 times by Algoma Public Health since June 11, 2024. The most recent inspection, on August 25, 2026, recorded 1 infraction.

4 of 9 inspections on record found no infractions at all. In the past 12 months there were 4 inspections with 4 infractions recorded. The higher-risk findings here relate to: Pool and spa water quality.

The number of infractions per inspection has stayed roughly the same over time.

What these findings mean

Health authorities word their findings differently, so we group them by what they mean for the people using the facility. Higher-risk findings are the ones that could directly cause illness or injury, such as water that is not properly treated.

  • Pool and spa water qualityHigher risk

    For pools, spas and splash pads, inspectors test disinfectant levels, pH and water clarity, and check safety equipment. Water that is not properly treated can spread skin, ear and stomach infections.

    Recorded 3 times across 3 separate inspections, most recently on June 9, 2026. For example: Daily pool tests and records completed

  • Permits, records and postingLower risk

    Operating permits, water-test logs, posted bather rules and emergency procedures. Daily test logs are how operators show the water was checked and treated between inspections.

    Recorded 3 times across 3 separate inspections, most recently on August 25, 2026. For example: Weekly and monthly tests and records completed

  • Other findingsLower risk

    Findings that do not fit the categories above, such as follow-ups that confirm an earlier violation was corrected, or requirements specific to this type of facility.

    Recorded once on November 21, 2024. For example: An emergency stop button must be accessible in the event of emergency [Sec. 26]

About this data

These results come from Algoma Public Health, which inspects food premises and other public facilities in this area. We republish the authority's public disclosure data and refresh it regularly; the official record is the final word.

9 inspections

  1. Required

    1 infraction

    • Weekly and monthly tests and records completed
      • Water, gravity, and suction outlet covers must be inspected at least once within each period of 30 operating days [Sec. 16.1(a)]
      • Emergency stop button must bed labelled and must be tested and recorded at least once within each period of 30 operating days [Sec. 16.1(d)]
      • Pool records must be signed by the person who performed the inspection [Sec. 16.1(g)]
      • Pool records are to be retained for a period of one year from the date of making the record, and are to be available for viewing by a public health inspector at any time [Sec. 16.1(h)]
  2. Required

    1 infraction

    • Daily pool tests and records completed
      • The reading of the make-up water meter must be recorded [Sec. 8(b)]
      • For a pool with an automatic sensing device, total alkalinity, pH value, free available chlorine and total chlorine or bromine residual, and water clarity checked and recorded every four hours until the daily use period has ended [Sec. 7(12)]
      • The land line emergency telephone is tested to confirm that it is in operating condition and is directly connected to an emergency service or local telephone utility before the pool is opened for use each day [Sec. 8(g)]
  3. Required

    2 infractions

    • Daily pool tests and records completed
      • The time at which each pool test is completed is to be recorded [Sec. 8]
      • Estimated number of bather uses during the operating day must be recorded [Sec. 8(a)]
      • The reading of the make-up water meter must be recorded [Sec. 8(b)]
      • For a pool with an automatic sensing device, total alkalinity, pH value, free available chlorine and total chlorine or bromine residual, and water clarity checked and recorded every four hours until the daily use period has ended [Sec. 7(12)]
      • The land line emergency telephone is tested to confirm that it is in operating condition and is directly connected to an emergency service or local telephone utility before the pool is opened for use each day [Sec. 8(g)]
    • Weekly and monthly tests and records completed
      • Water, gravity, and suction outlet covers must be inspected at least once within each period of 30 operating days [Sec. 16.1(a)]
      • The test-buttons associated with the ground current leakage detecting and de-energizing devices are activated during the daily use period and must be tested either monthly, or according to the manufacturer’s instructions, whichever is more frequent [Sec. 16.1(c)]
      • Emergency stop button must bed labelled and must be tested and recorded at least once within each period of 30 operating days [Sec. 16.1(d)]
  4. Required

    0 infractions

  5. Required

    1 infraction

    • Pool circulation is acceptable [Sec. 6(3)(c)]
  6. Required

    0 infractions

  7. Required

    0 infractions

  8. Required

    2 infractions

    • Weekly and monthly tests and records completed
    • An emergency stop button must be accessible in the event of emergency [Sec. 26]
      • An emergency stop button must be provided and capable of deactivating all pumps used in the operation of the pool [Sec. 26(1)]
      • The emergency stop button must be located within the vicinity of the pool and activate an audible and visual signal when used [Sec. 26(1)(b-c)]
  9. Required

    0 infractions