Aquatic Wellness Multiplex - 25m Teach Pool
10 Knowledge Way Grande Prairie AB T8W 2V9 · Aquatic Facility
19 inspections
- Demand Inspection
0 infractions
- Demand Inspection
1 infraction
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Unsatisfactory laboratory result received, collection date November 12, 2025- HPC 110 CFU/ml. Resample the pool.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Demand Inspection
0 infractions
- Risk Management Inspection
0 infractions
- Demand Inspection
1 infraction
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Unsatisfactory water result received, collection date August 6 2025: HPC - 190 CFU/ml. Ensure HPC count is less 100 CFU/mL.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Demand Inspection
1 infraction
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Unsatisfactory water result received, collection date June 17, 2025: HPC - 810 CFU/ml. Resample the pool.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Monitoring Inspection
0 infractions
- Monitoring Inspection
1 infraction
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Turnover rate is calculated at 4.41 hours.Turnover= Basin volume/Flowrate/60 mins = 116102 gallons/438.5 gallons per minute/ 60 mins = 4.41 hours.Increase the flow rate and ensure the turnover rate for a pool built after 2006 is 4 hours.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Risk Management Inspection
0 infractions
- Demand Inspection
2 infractions
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Unsatisfactory result received, collection date August 19, 2024; Total Coliforms present.Please super chlorinate the pool and resample.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Unsatisfactory laboratory result received; HPC >57000 CFU/ml. Please super chlorinate the pool and resample.
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Monitoring Inspection
0 infractions
- Demand Inspection
1 infraction
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Unsatisfactory lab results received, collected July 15, 2024, HPC 110 CFU/ml.Unsatisfactory Laboratory result received for water sample collected on July 22, 2024, HPC 57000 CFU/ml.Please super chlorinate and resample.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Demand Inspection
1 infraction
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Unsatisfactory lab results received, collected July 15, 2024, HPC 110 CFU/ml.Please submit a resample.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Risk Management Inspection
0 infractions
- Demand Inspection
1 infraction
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Unsatisfactory laboratory result received June 13, 2024: HPC 180 CFU/ml.Please submit a resample.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Risk Management Inspection
0 infractions
- Demand Inspection
1 infraction
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- HPC is 180 CFU/ml on the laboratory report. Please resample the pool.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Monitoring Inspection
0 infractions
- Demand Inspection
2 infractions
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Laboratory results indicated Pseudomonas isolated and Total Coliforms. Please close, scrub, super chlorinate the pool.The Pseudomonas information sheet will be sent in an email with the report and laboratory results. **A satisfactory laboratory results must be received before the pool can reopened.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- HPC of 190 CFU/ ml is noted on the Laboratory report. Please super chlorinate the pool.
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?