Bob Bahan Pool & Fitness Centre - Whirlpool

4812 14 Avenue SE Calgary AB T2A 0K9 · Aquatic Facility

8 inspections

  1. Risk Management Inspection

    4 infractions

    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • **OUTSTANDING**1. The combined chlorine measured 3.40ppm. The water is scheduled to be replaced tomorrow. **April 21, 2026: Combined chlorine measured 2.02ppm. COMPLETE THE FOLLOWING:1. Keep the combined chlorine as low as possible. The maximum recommended amount is 1.00ppm.
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • 1. The recirculation flow metre read 115.81 GPM, and the calculated turnover rate was 24 minutes. COMPLETE THE FOLLOWING:1. Please ensure the whirlpool is achieving a turnover rate of 20 minutes, and the flow rate does not exceed 141 GPM.
    • 13. Are the general safety devices and physical conditions in this pool providing a safe environment (Non-Critical)?
      • **OUTSTANDING**1. The clock to monitor patron length of stay was located outside the whirlpool area and was not easily visible to all patrons from the whirlpool.**April 21, 2026: a second clock was ordered and scheduled to be installed the week of March 16th. COMPLETE THE FOLLOWING:1. Please ensure the second clock is installed in an area where it is easily visible to all whirlpool patrons.
    • 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
      • 1. No anti-entrapment plans were completed for the new drain covers. Only the certificates of compliance were available.COMPLETE THE FOLLOWING:1. Please complete new anti-entrapment plans for the drain covers.
  2. Demand Inspection

    5 infractions

    • 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
      • 1. The bacteriological water sample collected on April 8, 2026 was present for pseudomonas.
    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • 1. The bacteriological water sample collected on April 8, 2026 had a heterotrophic plate count of 260 colony forming units/ mL.
    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • 1. The combined chlorine measured 3.40ppm. The water is scheduled to be replaced tomorrow. COMPLETE THE FOLLOWING:1. Keep the combined chlorine as low as possible. The maximum recommended amount is 1.00ppm.
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • 1. The flow metre was not operational and was not providing a reading.COMPLETE THE FOLLOWING:1. Repair or replace the flow metre.
    • 13. Are the general safety devices and physical conditions in this pool providing a safe environment (Non-Critical)?
      • 1. The clock to monitor patron length of stay was located outside the whirlpool area and was not easily visible to all patrons from the whirlpool.COMPLETE THE FOLLOWING:1. Please relocate the clock to an area where it is easily visible to all whirlpool patrons.
  3. Monitoring Inspection

    3 infractions

    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • 1. The combined chlorine measured 3.40ppm. The water is scheduled to be replaced tomorrow. COMPLETE THE FOLLOWING:1. Keep the combined chlorine as low as possible. The maximum recommended amount is 1.00ppm.
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • 1. The flow metre was not operational and was not providing a reading.COMPLETE THE FOLLOWING:1. Repair or replace the flow metre.
    • 13. Are the general safety devices and physical conditions in this pool providing a safe environment (Non-Critical)?
      • 1. The clock to monitor patron length of stay was located outside the whirlpool area and was not easily visible to all patrons from the whirlpool.COMPLETE THE FOLLOWING:1. Please relocate the clock to an area where it is easily visible to all whirlpool patrons.
  4. Demand Inspection

    2 infractions

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • 1. The sample collected on December 10, 2025 was not tested due to no identification number on the bottle.
    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • The whirlpool combined chlorine was measured at 8.77 milligrams per litre.-Please reduce and maintain combined chlorine as low as possible to ensure patrons' comfort.
  5. Demand Inspection

    2 infractions

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • Water sample collected on September 17, 2025, was tested as there was no identification number on the bottle.**Please re-sample.
    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • The whirlpool combined chlorine was measured at 8.77 milligrams per litre.-Please reduce and maintain combined chlorine as low as possible to ensure patrons' comfort.
  6. Risk Management Inspection

    1 infraction

    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • The whirlpool combined chlorine was measured at 8.77 milligrams per litre.-Please reduce and maintain combined chlorine as low as possible to ensure patrons' comfort.
  7. Demand Inspection

    2 infractions

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • The samples were not tested due to date and time of collection were not provided on the requisition form.- The operator was advised to submit resample.
    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • The whirlpool combined chlorine was measured at 8.77 milligrams per litre.-Please reduce and maintain combined chlorine as low as possible to ensure patrons' comfort.
  8. Monitoring Inspection

    1 infraction

    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • The whirlpool combined chlorine was measured at 8.77 milligrams per litre.-Please reduce and maintain combined chlorine as low as possible to ensure patrons' comfort.