Canyon Meadows Pool - Whirlpool

89 Canova Road SW Calgary AB T2W 6G3 · Aquatic Facility

17 inspections

  1. Demand Inspection

    1 infraction

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • Water sample submitted was rejected by the lab as the sample bottle leaked.Submit another sample.
  2. Monitoring Inspection

    1 infraction

    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • Flow rate at time of inspection was 6.167 LPS.Minimum calculated flow rate based on pool volume of 11356L is 9.46 LPS.Verify the accuracy of the flow meter.Calculated turnover rate based on the flow rate is 30 minutes.Ensure the turnover period is no more than 20 minutes.
  3. Demand Inspection

    1 infraction

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • Water sample submitted August 13, 2025 had 160 CFU/mL Resample
  4. Risk Management Inspection

    0 infractions

  5. Demand Inspection

    1 infraction

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • Water sample collected on Aug 6/25 had HPC of 160 cfu/ml. - Submit a resample.
  6. Risk Management Inspection

    0 infractions

  7. Risk Management Inspection

    1 infraction

    • 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
      • 1. Could not determine flow rate of the recirculation system.- Install a flow meter that would provide accurate reading.2. Water temperature measured at 41.4C. - Maintain water temperature at 40C or lower.
  8. Demand Inspection

    2 infractions

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • Water sample submitted on July 1 was not processed because it was received after 24 hrs of collection.
    • 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
      • 1. Could not determine flow rate of the recirculation system.- Install a flow meter that would provide accurate reading.2. Water temperature measured at 41.4C. - Maintain water temperature at 40C or lower.
  9. Monitoring Inspection

    1 infraction

    • 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
      • 1. Could not determine flow rate of the recirculation system.- Install a flow meter that would provide accurate reading.2. Water temperature measured at 41.4C. - Maintain water temperature at 40C or lower.
  10. Risk Management Inspection

    1 infraction

    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • Combined chlorine level tested at 2.23 ppm.- Maintain combined chlorine at the lowest possible level.- Recommend adding fresh water more often to keep combined chlorine at a low level.
  11. Risk Management Inspection

    2 infractions

    • 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
      • Water sample collected on Feb 19/25 had Pseudomonas isolated.- Treat the pool water, clean the basin and submit a resample.
    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • Combined chlorine level tested at 2.23 ppm.- Maintain combined chlorine at the lowest possible level.- Recommend adding fresh water more often to keep combined chlorine at a low level.
  12. Risk Management Inspection

    1 infraction

    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • Combined chlorine level tested at 2.23 ppm.- Maintain combined chlorine at the lowest possible level.- Recommend adding fresh water more often to keep combined chlorine at a low level.
  13. Demand Inspection

    2 infractions

    • 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
      • Water sample collected on May 29/24 had Pseudomonas isolated and HPC was 930 cfu/ml. - Treat the whirlpool water and submit a resample.
    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • Combined chlorine level tested at 2.23 ppm.- Maintain combined chlorine at the lowest possible level.- Recommend adding fresh water more often to keep combined chlorine at a low level.
  14. Monitoring Inspection

    1 infraction

    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • Combined chlorine level tested at 2.23 ppm.- Maintain combined chlorine at the lowest possible level.- Recommend adding fresh water more often to keep combined chlorine at a low level.
  15. Demand Inspection

    1 infraction

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • Water sample collected on Dec 21/23 was not processed because sample was delivered to the Provincial Laboratory more than 24 hrs after collection. - resample
  16. Demand Inspection

    1 infraction

    • 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
      • Water sample collected on Oct 18/23 had Pseudomonas present. - Treat the whirlpool water, drain, refill, chemically balance water and submit a resample.
  17. Risk Management Inspection

    0 infractions