Chartwell Wescott Retirement Residence - Swimming Pool
3841 Allan Drive SW Edmonton AB T6W 4B8 · Aquatic Facility
44 inspections
- Risk Management Inspection
1 infraction
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Unsatisfactory Lab Test Result:Collection Date: June 24, 2026 Location: Pool **HPC 120cfu/mL
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Demand Inspection
1 infraction
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Unsatisfactory Lab Test Result:Collection Date: June 24, 2026 Location: Pool **HPC 120cfu/mL
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Risk Management Inspection
0 infractions
- Demand Inspection
1 infraction
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Unsatisfactory Lab Test Result:Collection Date: June 10, 2026 Location: Pool **HPC 360cfu/mL
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Risk Management Inspection
0 infractions
- Demand Inspection
3 infractions
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Unsatisfactory Lab Test Result:Collection Date: May 26, 2026Location: Pool **HPC 120cfu/mL
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Collection Date: April 29/26Location: Pool **HPC 350 cfu/mL
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Collection Date: May 13, 2026Location: Pool **HPC 120cfu/mL
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Demand Inspection
2 infractions
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Collection Date: May 13, 2026Location: Pool **HPC 120cfu/mL
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Collection Date: April 29/26Location: Pool **HPC 350 cfu/mL
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Risk Management Inspection
1 infraction
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Collection Date: April 29/26Location: Pool **HPC 350 cfu/mL
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Demand Inspection
1 infraction
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Unsatisfactory Lab Test Result:Collection Date: April 29/26Location: Pool **HPC 350 cfu/mL
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Risk Management Inspection
0 infractions
- Demand Inspection
1 infraction
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Unsatisfactory Lab Test Result:Collection Date: March 17/26Location: Pool **HPC 120 cfu/mL
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Risk Management Inspection
0 infractions
- Monitoring Inspection
1 infraction
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- **Filtration rate was 15.3gpm/sq ft based on filtration area of 6.5sq ft and flow rate of 100gpm. Required to be less than 15gpm/sq ft. Please reduce flow rate to 98gpm max to ensure filtration rate is less than 15gpm/sq ft. This limit is to achieve the proper filtration rate and ensure the filter operates at optimal capacity without the risk of damage.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Risk Management Inspection
0 infractions
- Demand Inspection
2 infractions
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- October 10/25(12:50) Sample tested presence of HPC 300cfu/mL
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- *Total alkalinity (50ppm, 47ppm and 40ppm) tested on deck was out of regulatory range of 60-180ppm. Troubleshoot and ensure alkalinity is within regulatory range.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Monitoring Inspection
1 infraction
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- *Total alkalinity (50ppm, 47ppm and 40ppm) tested on deck was out of regulatory range of 60-180ppm. Troubleshoot and ensure alkalinity is within regulatory range.
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- Risk Management Inspection
6 infractions
- 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
- *Free chlorine tested on deck was out of range (high value measured). Troubleshoot and ensure free chlorine is within regulatory range.*pH(6.67) tested on deck was out of regulatory range of 6.8-7.6 Troubleshoot and ensure pH is within regulatory range.
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- *Total alkalinity(14ppm) tested on deck was out of regulatory range of 60-180ppm. Troubleshoot and ensure alkalinity is within regulatory range.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- *Flow rate(120GPM) was too high causing filtration rate to exceed 15 GPM/sq ft. based on a filtration area of 7.06sq ft. Filtration rate was 16.99GPM/sq ft. Reduce flow rate to ensure adequate turnover without exceeding filtration rate.
- 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
- *Sand like material was observed in the bottom of the pool and stairs. Remove sand like material and ensure no debris is in the pool. Ensure sand filter is in good working condition. *Lots of debris and bugs noted in skimmer baskets. Site indicated they are checked every month. Increase monitoring/cleaning of skimmer baskets.
- 16. Are proper testing, monitoring, and other records being properly maintained?
- Pool is not being tested and/or recorded for pH, free chlorine, and total chlorine and recorded for automated controller readings and set points are not being recorded.Record indicate missing information on various dates including: April16, 19, 20, 23, 25, 26.Testing had not been completed on day of inspection when the pool was in operation.Ensure that pool parameters are tested and recorded at least once per day. Ensure staff responsible for recording of basin parameters receive education of how to sample pool parameters.
- 16. Are proper testing, monitoring, and other records being properly maintained?
- *Gaps were observed in the manual chemistry testing records. Multiple days especially weekends were blank. Manny indicated no one site completes the chemistry when he is not working. Ensure manual chemical testing occurs every day. Ensure actions taken for high/low values are also recorded as needed
- 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
- Risk Management Inspection
6 infractions
- 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
- *Free chlorine tested on deck was out of range (high value measured). Troubleshoot and ensure free chlorine is within regulatory range.*pH(6.67) tested on deck was out of regulatory range of 6.8-7.6 Troubleshoot and ensure pH is within regulatory range.
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- *Total alkalinity(14ppm) tested on deck was out of regulatory range of 60-180ppm. Troubleshoot and ensure alkalinity is within regulatory range.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- *Flow rate(120GPM) was too high causing filtration rate to exceed 15 GPM/sq ft. based on a filtration area of 7.06sq ft. Filtration rate was 16.99GPM/sq ft. Reduce flow rate to ensure adequate turnover without exceeding filtration rate.
- 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
- *Sand like material was observed in the bottom of the pool and stairs. Remove sand like material and ensure no debris is in the pool. Ensure sand filter is in good working condition. *Lots of debris and bugs noted in skimmer baskets. Site indicated they are checked every month. Increase monitoring/cleaning of skimmer baskets.
- 16. Are proper testing, monitoring, and other records being properly maintained?
- Pool is not being tested and/or recorded for pH, free chlorine, and total chlorine and recorded for automated controller readings and set points are not being recorded.Record indicate missing information on various dates including: April16, 19, 20, 23, 25, 26.Testing had not been completed on day of inspection when the pool was in operation.Ensure that pool parameters are tested and recorded at least once per day. Ensure staff responsible for recording of basin parameters receive education of how to sample pool parameters.
- 16. Are proper testing, monitoring, and other records being properly maintained?
- *Gaps were observed in the manual chemistry testing records. Multiple days especially weekends were blank. Manny indicated no one site completes the chemistry when he is not working. Ensure manual chemical testing occurs every day. Ensure actions taken for high/low values are also recorded as needed
- 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
- Monitoring Inspection
6 infractions
- 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
- *Free chlorine tested on deck was out of range (high value measured). Troubleshoot and ensure free chlorine is within regulatory range.*pH(6.67) tested on deck was out of regulatory range of 6.8-7.6 Troubleshoot and ensure pH is within regulatory range.
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- *Total alkalinity(14ppm) tested on deck was out of regulatory range of 60-180ppm. Troubleshoot and ensure alkalinity is within regulatory range.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- *Flow rate(120GPM) was too high causing filtration rate to exceed 15 GPM/sq ft. based on a filtration area of 7.06sq ft. Filtration rate was 16.99GPM/sq ft. Reduce flow rate to ensure adequate turnover without exceeding filtration rate.
- 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
- *Sand like material was observed in the bottom of the pool and stairs. Remove sand like material and ensure no debris is in the pool. Ensure sand filter is in good working condition. *Lots of debris and bugs noted in skimmer baskets. Site indicated they are checked every month. Increase monitoring/cleaning of skimmer baskets.
- 16. Are proper testing, monitoring, and other records being properly maintained?
- Pool is not being tested and/or recorded for pH, free chlorine, and total chlorine and recorded for automated controller readings and set points are not being recorded.Record indicate missing information on various dates including: April16, 19, 20, 23, 25, 26.Testing had not been completed on day of inspection when the pool was in operation.Ensure that pool parameters are tested and recorded at least once per day. Ensure staff responsible for recording of basin parameters receive education of how to sample pool parameters.
- 16. Are proper testing, monitoring, and other records being properly maintained?
- *Gaps were observed in the manual chemistry testing records. Multiple days especially weekends were blank. Manny indicated no one site completes the chemistry when he is not working. Ensure manual chemical testing occurs every day. Ensure actions taken for high/low values are also recorded as needed
- 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
- Risk Management Inspection
7 infractions
- 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
- Free chlorine is low. Pools with a ORP of 700mV must be maintained at 0.5 ppm free chlorine or higher. Free chlorine is >10 ppm
- 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
- pH at basin tested as "OR" and 8.19. pH is high. Adjust to safe operating level.
- 06. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Critical)?
- Flow Meter: high flow meter not operational, low (salt cell) flow meter 20GPM. Flow meter is not operational.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Flow 10,500 US Gal. / 37 GMP = 4.73 hours. Turnover rate is not being achieved. Adjust flow to ensure adequate turnover rate without exceeding filtration rate. April 26 - Flow meter indicates 30 GPM. 10,500 US Gal. / 30 GMP = 5.8 hours. Turnover rate is not being achieved. Adjust flow to ensure adequate turnover rate without exceeding filtration rate.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Automated controller does not appear to be accurate with manual testing completed at the basin. Ensure automated controller is able to accurately reflect pool basin chemistry.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- *Salt debris build up and/or leak observed at 2 flow meters, automated controller probe box, and valve at sand filter. Repair.
- 16. Are proper testing, monitoring, and other records being properly maintained?
- Pool is not being tested and/or recorded for pH, free chlorine, and total chlorine and recorded for automated controller readings and set points are not being recorded.Record indicate missing information on various dates including: April16, 19, 20, 23, 25, 26.Testing had not been completed on day of inspection when the pool was in operation.Ensure that pool parameters are tested and recorded at least once per day. Ensure staff responsible for recording of basin parameters receive education of how to sample pool parameters.
- 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
- Demand Inspection
8 infractions
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Unsatisfactory Lab Test Result:Collection Date: Sept 17/2024 Location: Pool** HPC: 430cfu/100mL of water.
- 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
- Free chlorine is low. Pools with a ORP of 700mV must be maintained at 0.5 ppm free chlorine or higher. Free chlorine is >10 ppm
- 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
- pH at basin tested as "OR" and 8.19. pH is high. Adjust to safe operating level.
- 06. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Critical)?
- Flow Meter: high flow meter not operational, low (salt cell) flow meter 20GPM. Flow meter is not operational.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Flow 10,500 US Gal. / 37 GMP = 4.73 hours. Turnover rate is not being achieved. Adjust flow to ensure adequate turnover rate without exceeding filtration rate. April 26 - Flow meter indicates 30 GPM. 10,500 US Gal. / 30 GMP = 5.8 hours. Turnover rate is not being achieved. Adjust flow to ensure adequate turnover rate without exceeding filtration rate.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Automated controller does not appear to be accurate with manual testing completed at the basin. Ensure automated controller is able to accurately reflect pool basin chemistry.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- *Salt debris build up and/or leak observed at 2 flow meters, automated controller probe box, and valve at sand filter. Repair.
- 16. Are proper testing, monitoring, and other records being properly maintained?
- Pool is not being tested and/or recorded for pH, free chlorine, and total chlorine and recorded for automated controller readings and set points are not being recorded.Record indicate missing information on various dates including: April16, 19, 20, 23, 25, 26.Testing had not been completed on day of inspection when the pool was in operation.Ensure that pool parameters are tested and recorded at least once per day. Ensure staff responsible for recording of basin parameters receive education of how to sample pool parameters.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Demand Inspection
8 infractions
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Unsatisfactory Lab Test Result:Collection Date: August 29, 2024 Location: Pool on Deck** HPC: >57, 000 CFU/100mL of water.
- 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
- Free chlorine is low. Pools with a ORP of 700mV must be maintained at 0.5 ppm free chlorine or higher. Free chlorine is >10 ppm
- 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
- pH at basin tested as "OR" and 8.19. pH is high. Adjust to safe operating level.
- 06. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Critical)?
- Flow Meter: high flow meter not operational, low (salt cell) flow meter 20GPM. Flow meter is not operational.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Flow 10,500 US Gal. / 37 GMP = 4.73 hours. Turnover rate is not being achieved. Adjust flow to ensure adequate turnover rate without exceeding filtration rate. April 26 - Flow meter indicates 30 GPM. 10,500 US Gal. / 30 GMP = 5.8 hours. Turnover rate is not being achieved. Adjust flow to ensure adequate turnover rate without exceeding filtration rate.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Automated controller does not appear to be accurate with manual testing completed at the basin. Ensure automated controller is able to accurately reflect pool basin chemistry.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- *Salt debris build up and/or leak observed at 2 flow meters, automated controller probe box, and valve at sand filter. Repair.
- 16. Are proper testing, monitoring, and other records being properly maintained?
- Pool is not being tested and/or recorded for pH, free chlorine, and total chlorine and recorded for automated controller readings and set points are not being recorded.Record indicate missing information on various dates including: April16, 19, 20, 23, 25, 26.Testing had not been completed on day of inspection when the pool was in operation.Ensure that pool parameters are tested and recorded at least once per day. Ensure staff responsible for recording of basin parameters receive education of how to sample pool parameters.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Demand Inspection
9 infractions
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- *Sample collected on July 16/24 HPC: >57, 000/100mL of water
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- *Sample collected on July 30/24 HPC: >57, 000/100mL of water
- 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
- Free chlorine is low. Pools with a ORP of 700mV must be maintained at 0.5 ppm free chlorine or higher. Free chlorine is >10 ppm
- 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
- pH at basin tested as "OR" and 8.19. pH is high. Adjust to safe operating level.
- 06. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Critical)?
- Flow Meter: high flow meter not operational, low (salt cell) flow meter 20GPM. Flow meter is not operational.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Flow 10,500 US Gal. / 37 GMP = 4.73 hours. Turnover rate is not being achieved. Adjust flow to ensure adequate turnover rate without exceeding filtration rate. April 26 - Flow meter indicates 30 GPM. 10,500 US Gal. / 30 GMP = 5.8 hours. Turnover rate is not being achieved. Adjust flow to ensure adequate turnover rate without exceeding filtration rate.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Automated controller does not appear to be accurate with manual testing completed at the basin. Ensure automated controller is able to accurately reflect pool basin chemistry.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- *Salt debris build up and/or leak observed at 2 flow meters, automated controller probe box, and valve at sand filter. Repair.
- 16. Are proper testing, monitoring, and other records being properly maintained?
- Pool is not being tested and/or recorded for pH, free chlorine, and total chlorine and recorded for automated controller readings and set points are not being recorded.Record indicate missing information on various dates including: April16, 19, 20, 23, 25, 26.Testing had not been completed on day of inspection when the pool was in operation.Ensure that pool parameters are tested and recorded at least once per day. Ensure staff responsible for recording of basin parameters receive education of how to sample pool parameters.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Demand Inspection
8 infractions
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- *Sample collected on July 16/24 HPC: >57, 000/100mL of water
- 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
- Free chlorine is low. Pools with a ORP of 700mV must be maintained at 0.5 ppm free chlorine or higher. Free chlorine is >10 ppm
- 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
- pH at basin tested as "OR" and 8.19. pH is high. Adjust to safe operating level.
- 06. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Critical)?
- Flow Meter: high flow meter not operational, low (salt cell) flow meter 20GPM. Flow meter is not operational.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Flow 10,500 US Gal. / 37 GMP = 4.73 hours. Turnover rate is not being achieved. Adjust flow to ensure adequate turnover rate without exceeding filtration rate. April 26 - Flow meter indicates 30 GPM. 10,500 US Gal. / 30 GMP = 5.8 hours. Turnover rate is not being achieved. Adjust flow to ensure adequate turnover rate without exceeding filtration rate.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Automated controller does not appear to be accurate with manual testing completed at the basin. Ensure automated controller is able to accurately reflect pool basin chemistry.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- *Salt debris build up and/or leak observed at 2 flow meters, automated controller probe box, and valve at sand filter. Repair.
- 16. Are proper testing, monitoring, and other records being properly maintained?
- Pool is not being tested and/or recorded for pH, free chlorine, and total chlorine and recorded for automated controller readings and set points are not being recorded.Record indicate missing information on various dates including: April16, 19, 20, 23, 25, 26.Testing had not been completed on day of inspection when the pool was in operation.Ensure that pool parameters are tested and recorded at least once per day. Ensure staff responsible for recording of basin parameters receive education of how to sample pool parameters.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Risk Management Inspection
7 infractions
- 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
- pH at basin tested as "OR" and 8.19. pH is high. Adjust to safe operating level.
- 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
- Free chlorine is low. Pools with a ORP of 700mV must be maintained at 0.5 ppm free chlorine or higher. Free chlorine is >10 ppm
- 06. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Critical)?
- Flow Meter: high flow meter not operational, low (salt cell) flow meter 20GPM. Flow meter is not operational.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Automated controller does not appear to be accurate with manual testing completed at the basin. Ensure automated controller is able to accurately reflect pool basin chemistry.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- *Salt debris build up and/or leak observed at 2 flow meters, automated controller probe box, and valve at sand filter. Repair.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Flow 10,500 US Gal. / 37 GMP = 4.73 hours. Turnover rate is not being achieved. Adjust flow to ensure adequate turnover rate without exceeding filtration rate. April 26 - Flow meter indicates 30 GPM. 10,500 US Gal. / 30 GMP = 5.8 hours. Turnover rate is not being achieved. Adjust flow to ensure adequate turnover rate without exceeding filtration rate.
- 16. Are proper testing, monitoring, and other records being properly maintained?
- Pool is not being tested and/or recorded for pH, free chlorine, and total chlorine and recorded for automated controller readings and set points are not being recorded.Record indicate missing information on various dates including: April16, 19, 20, 23, 25, 26.Testing had not been completed on day of inspection when the pool was in operation.Ensure that pool parameters are tested and recorded at least once per day. Ensure staff responsible for recording of basin parameters receive education of how to sample pool parameters.
- 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
- Risk Management Inspection
3 infractions
- 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
- Free chlorine is low. Pools with a ORP of 700mV must be maintained at 0.5 ppm free chlorine or higher.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Flow 10,500 US Gal. / 37 GMP = 4.73 hours. Turnover rate is not being achieved. Adjust flow to ensure adequate turnover rate without exceeding filtration rate. April 26 - Flow meter indicates 30 GPM. 10,500 US Gal. / 30 GMP = 5.8 hours. Turnover rate is not being achieved. Adjust flow to ensure adequate turnover rate without exceeding filtration rate.
- 16. Are proper testing, monitoring, and other records being properly maintained?
- Pool is not being tested and/or recorded for pH, free chlorine, and total chlorine and recorded for automated controller readings and set points are not being recorded.Record indicate missing information on various dates including: April16, 19, 20, 23, 25, 26.Testing had not been completed on day of inspection when the pool was in operation.Ensure that pool parameters are tested and recorded at least once per day. Ensure staff responsible for recording of basin parameters receive education of how to sample pool parameters.
- 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
- Demand Inspection
4 infractions
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Bacteriological water sample collected 04/06/2024 was not processed. The sample was received more than 24 hours after collection. Resubmit a new water sample.
- 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
- Free chlorine is low. Pools with a ORP of 700mV must be maintained at 0.5 ppm free chlorine or higher.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Flow 10,500 US Gal. / 37 GMP = 4.73 hours. Turnover rate is not being achieved. Adjust flow to ensure adequate turnover rate without exceeding filtration rate. April 26 - Flow meter indicates 30 GPM. 10,500 US Gal. / 30 GMP = 5.8 hours. Turnover rate is not being achieved. Adjust flow to ensure adequate turnover rate without exceeding filtration rate.
- 16. Are proper testing, monitoring, and other records being properly maintained?
- Pool is not being tested and/or recorded for pH, free chlorine, and total chlorine and recorded for automated controller readings and set points are not being recorded.Record indicate missing information on various dates including: April16, 19, 20, 23, 25, 26.Testing had not been completed on day of inspection when the pool was in operation.Ensure that pool parameters are tested and recorded at least once per day. Ensure staff responsible for recording of basin parameters receive education of how to sample pool parameters.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Risk Management Inspection
4 infractions
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- April 24, 2024 bacteriological water sample was unsatisfactory. HPC: 180 CFU/mL
- 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
- Free chlorine is low. Pools with a ORP of 700mV must be maintained at 0.5 ppm free chlorine or higher.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Flow 10,500 US Gal. / 37 GMP = 4.73 hours. Turnover rate is not being achieved. Adjust flow to ensure adequate turnover rate without exceeding filtration rate. April 26 - Flow meter indicates 30 GPM. 10,500 US Gal. / 30 GMP = 5.8 hours. Turnover rate is not being achieved. Adjust flow to ensure adequate turnover rate without exceeding filtration rate.
- 16. Are proper testing, monitoring, and other records being properly maintained?
- Pool is not being tested and/or recorded for pH, free chlorine, and total chlorine and recorded for automated controller readings and set points are not being recorded.Record indicate missing information on various dates including: April16, 19, 20, 23, 25, 26.Testing had not been completed on day of inspection when the pool was in operation.Ensure that pool parameters are tested and recorded at least once per day. Ensure staff responsible for recording of basin parameters receive education of how to sample pool parameters.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Risk Management Inspection
3 infractions
- 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
- Free chlorine is low. Pools with a ORP of 700mV must be maintained at 0.5 ppm free chlorine or higher.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Flow 10,500 US Gal. / 37 GMP = 4.73 hours. Turnover rate is not being achieved. Adjust flow to ensure adequate turnover rate without exceeding filtration rate. April 26 - Flow meter indicates 30 GPM. 10,500 US Gal. / 30 GMP = 5.8 hours. Turnover rate is not being achieved. Adjust flow to ensure adequate turnover rate without exceeding filtration rate.
- 16. Are proper testing, monitoring, and other records being properly maintained?
- Pool is not being tested and/or recorded for pH, free chlorine, and total chlorine and recorded for automated controller readings and set points are not being recorded.Record indicate missing information on various dates including: April16, 19, 20, 23, 25, 26.Testing had not been completed on day of inspection when the pool was in operation.Ensure that pool parameters are tested and recorded at least once per day. Ensure staff responsible for recording of basin parameters receive education of how to sample pool parameters.
- 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
- Monitoring Inspection
3 infractions
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Flow 10,500 US Gal. / 37 GMP = 4.73 hours. Turnover rate is not being achieved. Adjust flow to ensure adequate turnover rate without exceeding filtration rate.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Automated controller does not appear to be accurate with manual testing completed at the basin. Ensure automated controller is able to accurately reflect pool basin chemistry.
- 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
- Observed debris (sand or grout) in the bottom of the pool especially around stairs and scum line around the exterior of the pool. Clean. April 13 2024- *Debris noted in pool. Pool vacuum observed in basin*Water level of pool is to the top of the skimmer. Ensure water level is lowered so water is middle of the skimmer to ensure sufficient removal of surface contaminants.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Demand Inspection
3 infractions
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- X Bacteriological water sample collected on February 13, 2024 was unsatisfactory.- HPC >57000 CFU/mL
- 10. Are general nuisance conditions, other than those noted in other violations, being prevented at this pool (Non-Critical)?
- Outstanding: Light at the bottom of the stairs leading into the pool was observed to be burnt out. Ensure light is replaced/fixed as soon as possible. Ensure repair work is booked and completed promptly. Rust stains were observed in the stairs area. It appears that the operator has a plan in place for fixing the stains. Ensure repair work is booked and completed promptly.
- 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
- Observed debris (sand or grout) in the bottom of the pool especially around stairs and scum line around the exterior of the pool. Clean.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Demand Inspection
4 infractions
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- X Water sample collected on January 25, 2024 was not received by the lab until January 27, 2024 and was not processed.Non-urgent sample received during weekend/holiday without approval. The sample was received more than 24 hours after collection.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Bacteriological water sample submitted January 29, 2024 was not tested. Sample not tested due to missing label on bottle.
- 10. Are general nuisance conditions, other than those noted in other violations, being prevented at this pool (Non-Critical)?
- Outstanding: Light at the bottom of the stairs leading into the pool was observed to be burnt out. Ensure light is replaced/fixed as soon as possible. Ensure repair work is booked and completed promptly. Rust stains were observed in the stairs area. It appears that the operator has a plan in place for fixing the stains. Ensure repair work is booked and completed promptly.
- 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
- Observed debris (sand or grout) in the bottom of the pool especially around stairs and scum line around the exterior of the pool. Clean.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Demand Inspection
4 infractions
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- X Water sample collected on January 25, 2024 was not received by the lab until January 27, 2024 and was not processed.Non-urgent sample received during weekend/holiday without approval. The sample was received more than 24 hours after collection.
- 09. Are general nuisance conditions, other than those noted in other violations, being prevented at this pool (Critical)?
- * Free chlorine is out of range (high value measured). Troubleshoot ensure free chlorine is within regulatory range.
- 10. Are general nuisance conditions, other than those noted in other violations, being prevented at this pool (Non-Critical)?
- Outstanding: Light at the bottom of the stairs leading into the pool was observed to be burnt out. Ensure light is replaced/fixed as soon as possible. Ensure repair work is booked and completed promptly. Rust stains were observed in the stairs area. It appears that the operator has a plan in place for fixing the stains. Ensure repair work is booked and completed promptly.
- 15. Has an owner or owner's agent, if any, been identified and is the pool operated and maintained by a qualified pool operator?
- Licensed pool operator not available onsite. Ensure pool operator is available onsite for chemical testing and pool maintenance as needed. Operator is looking to put in place a temporary plan.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Demand Inspection
4 infractions
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- HPC >57,000 cfu/ml was found in the Dec 28, 2023 water sample. Please treat the basin and resample.
- 09. Are general nuisance conditions, other than those noted in other violations, being prevented at this pool (Critical)?
- * Free chlorine is out of range (high value measured). Troubleshoot ensure free chlorine is within regulatory range.
- 10. Are general nuisance conditions, other than those noted in other violations, being prevented at this pool (Non-Critical)?
- Outstanding: Light at the bottom of the stairs leading into the pool was observed to be burnt out. Ensure light is replaced/fixed as soon as possible. Ensure repair work is booked and completed promptly. Rust stains were observed in the stairs area. It appears that the operator has a plan in place for fixing the stains. Ensure repair work is booked and completed promptly.
- 15. Has an owner or owner's agent, if any, been identified and is the pool operated and maintained by a qualified pool operator?
- Licensed pool operator not available onsite. Ensure pool operator is available onsite for chemical testing and pool maintenance as needed. Operator is looking to put in place a temporary plan.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Risk Management Inspection
4 infractions
- 10. Are general nuisance conditions, other than those noted in other violations, being prevented at this pool (Non-Critical)?
- Outstanding: Light at the bottom of the stairs leading into the pool was observed to be burnt out. Ensure light is replaced/fixed as soon as possible. Ensure repair work is booked and completed promptly. Rust stains were observed in the stairs area. It appears that the operator has a plan in place for fixing the stains. Ensure repair work is booked and completed promptly.
- 10. Are general nuisance conditions, other than those noted in other violations, being prevented at this pool (Non-Critical)?
- *** Pool was observed to be needing vacuuming. Debris were observed at the bottom of the pool.
- 15. Has an owner or owner's agent, if any, been identified and is the pool operated and maintained by a qualified pool operator?
- Licensed pool operator not available onsite. As per the operator the pool service provider is providing weekly consultation. New maintenance manager is registered to obtain certification in January. Please send a copy of the certification.
- 16. Are proper testing, monitoring, and other records being properly maintained?
- ***Gaps in record keeping were observed. Ensure manual sampling is done consistently and records are kept (including weekends). Ensure actions taken for high/low values are also recorded as needed.
- 10. Are general nuisance conditions, other than those noted in other violations, being prevented at this pool (Non-Critical)?
- Risk Management Inspection
4 infractions
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Unsatisfactory water sample was received for sample taken on December 6 : WE-23-0131171 High HPC count (160).
- 09. Are general nuisance conditions, other than those noted in other violations, being prevented at this pool (Critical)?
- * Free chlorine is out of range (high value measured). Troubleshoot ensure free chlorine is within regulatory range.
- 10. Are general nuisance conditions, other than those noted in other violations, being prevented at this pool (Non-Critical)?
- Outstanding: Light at the bottom of the stairs leading into the pool was observed to be burnt out. Ensure light is replaced/fixed as soon as possible. Ensure repair work is booked and completed promptly. Rust stains were observed in the stairs area. It appears that the operator has a plan in place for fixing the stains. Ensure repair work is booked and completed promptly.
- 15. Has an owner or owner's agent, if any, been identified and is the pool operated and maintained by a qualified pool operator?
- Licensed pool operator not available onsite. Ensure pool operator is available onsite for chemical testing and pool maintenance as needed. Operator is looking to put in place a temporary plan.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Monitoring Inspection
3 infractions
- 09. Are general nuisance conditions, other than those noted in other violations, being prevented at this pool (Critical)?
- * Free chlorine is out of range (high value measured). Troubleshoot ensure free chlorine is within regulatory range.
- 10. Are general nuisance conditions, other than those noted in other violations, being prevented at this pool (Non-Critical)?
- Outstanding: Light at the bottom of the stairs leading into the pool was observed to be burnt out. Ensure light is replaced/fixed as soon as possible. Ensure repair work is booked and completed promptly. Rust stains were observed in the stairs area. It appears that the operator has a plan in place for fixing the stains. Ensure repair work is booked and completed promptly.
- 15. Has an owner or owner's agent, if any, been identified and is the pool operated and maintained by a qualified pool operator?
- Licensed pool operator not available onsite. Ensure pool operator is available onsite for chemical testing and pool maintenance as needed. Operator is looking to put in place a temporary plan.
- 09. Are general nuisance conditions, other than those noted in other violations, being prevented at this pool (Critical)?
- Risk Management Inspection
2 infractions
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Unsatisfactory water sample was received for sample taken on October 31. This is the second failed water sample result (back-to-back).
- 10. Are general nuisance conditions, other than those noted in other violations, being prevented at this pool (Non-Critical)?
- Light at the bottom of the stairs leading into the pool was observed to be burnt out. Ensure light is replaced/fixed as soon as possible. Operator has confirmed that they are currently seeking out quotes. Ensure repair work is booked and completed promptly. Rust stains were observed in the stairs area. It appears that the operator has a plan in place for fixing the stains. Ensure repair work is booked and completed promptly.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Risk Management Inspection
2 infractions
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Unsatisfactory water sample was received for sample taken on October 24 : WE:23-015108- High HPC count (>57000).
- 10. Are general nuisance conditions, other than those noted in other violations, being prevented at this pool (Non-Critical)?
- Light at the bottom of the stairs leading into the pool was observed to be burnt out. Ensure light is replaced/fixed as soon as possible. Operator has confirmed that they are currently seeking out quotes. Ensure repair work is booked and completed promptly. Rust stains were observed in the stairs area. It appears that the operator has a plan in place for fixing the stains. Ensure repair work is booked and completed promptly.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Risk Management Inspection
2 infractions
- 10. Are general nuisance conditions, other than those noted in other violations, being prevented at this pool (Non-Critical)?
- Light at the bottom of the stairs leading into the pool was observed to be burnt out. Ensure light is replaced/fixed as soon as possible. Operator has confirmed that they are currently seeking out quotes. Ensure repair work is booked and completed promptly. Rust stains were observed in the stairs area. It appears that the operator has a plan in place for fixing the stains. Ensure repair work is booked and completed promptly.
- 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
- *Anti-entrapment plan review was not booked at this time with the pool service provider. Ensure anti-entrapment plan is booked asap as previously discussed. At the time of inspection pool is being assessed for compliance by the pool maintenance operator.
- 10. Are general nuisance conditions, other than those noted in other violations, being prevented at this pool (Non-Critical)?
- Risk Management Inspection
3 infractions
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Sample taken on September 20- High HPC count (1600). Operator was advised on the next steps.
- 10. Are general nuisance conditions, other than those noted in other violations, being prevented at this pool (Non-Critical)?
- Light at the bottom of the stairs leading into the pool was observed to be burnt out. Ensure light is replaced/fixed as soon as possible. Operator has confirmed that they are currently seeking out quotes. Ensure repair work is booked and completed promptly. Rust stains were observed in the stairs area. It appears that the operator has a plan in place for fixing the stains. Ensure repair work is booked and completed promptly.
- 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
- *Anti-entrapment plan review was not booked at this time with the pool service provider. Ensure anti-entrapment plan is booked asap as previously discussed.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Risk Management Inspection
2 infractions
- 10. Are general nuisance conditions, other than those noted in other violations, being prevented at this pool (Non-Critical)?
- Light at the bottom of the stairs leading into the pool was observed to be burnt out. Ensure light is replaced/fixed as soon as possible. Operator has confirmed that they are currently seeking out quotes. Ensure repair work is booked and completed promptly. Rust stains were observed in the stairs area. It appears that the operator has a plan in place for fixing the stains. Ensure repair work is booked and completed promptly.
- 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
- *Anti-entrapment plan review was not booked at this time with the pool service provider. Ensure anti-entrapment plan is booked asap as previously discussed.
- 10. Are general nuisance conditions, other than those noted in other violations, being prevented at this pool (Non-Critical)?
- Risk Management Inspection
3 infractions
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Flow rate(120gpm) of pool water was too high. This caused the rate of filtration (16.99gpm/sq ft) to be greater than 15gpm/ sq ft as required for swimming pools with a high rate sand filter. From the specification of the pool equipment/plans submitted to this office the designed flow rate should be between 43.75gpm to 105.9gpm. Please troubleshoot. Reduce flow rate to ensure the filtration rate does not exceed 15gpm/sq ft and turnover period of pool does not exceed 4 hours.
- 10. Are general nuisance conditions, other than those noted in other violations, being prevented at this pool (Non-Critical)?
- Light at the bottom of the stairs leading into the pool was observed to be burnt out. Ensure light is replaced/fixed as soon as possible. Operator has confirmed that they are currently seeking out quotes. Ensure repair work is booked and completed promptly. Rust stains were observed in the stairs area. It appears that the operator has a plan in place for fixing the stains. Ensure repair work is booked and completed promptly.
- 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
- Facility does not have a complete anti-entrapment plan onsite. Ensure anti-entrapment a completed plan is summitted within next 30 days.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Risk Management Inspection
5 infractions
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Flow rate(120gpm) of pool water was too high. This caused the rate of filtration (16.99gpm/sq ft) to be greater than 15gpm/ sq ft as required for swimming pools with a high rate sand filter. From the specification of the pool equipment/plans submitted to this office the designed flow rate should be between 43.75gpm to 105.9gpm. Please troubleshoot. Reduce flow rate to ensure the filtration rate does not exceed 15gpm/sq ft and turnover period of pool does not exceed 4 hours.
- 09. Are general nuisance conditions, other than those noted in other violations, being prevented at this pool (Critical)?
- Free chlorine was measured with Pool 1.0 Kit to be high. Immediately correct the free chlorine to ensure safe water for patrons.
- 10. Are general nuisance conditions, other than those noted in other violations, being prevented at this pool (Non-Critical)?
- Light at the bottom of the stairs leading into the pool was observed to be burnt out. Ensure light is replaced/fixed as soon as possible. Operator has confirmed that they are currently seeking out quotes.
- 16. Are proper testing, monitoring, and other records being properly maintained?
- Manual testing of the basin is not being conducted as required or records have not been maintained. Written pool records show records show no testing for the following days in June (30,16,2) and July (24,25,27)
- 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
- Facility does not have anti-entrapment plan onsite or anti-entrapment plan could not be located. Ensure anti-entrapment plan is summitted within next 30 days.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?