Chateau Renoir - Whirlpool
9229 16 Street SW Calgary AB T2V 5H3 · Aquatic Facility
10 inspections
- Risk Management Inspection
0 infractions
- Risk Management Inspection
1 infraction
- 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
- The flow meter was not accurate.-Please repair the flow meter.Note: Whirlpool volume is 2400 Gal, minimum flow rate should be 120 GPM to achieve a turnover period of 20 minutes.
- 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
- Risk Management Inspection
1 infraction
- 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
- 1. There was some mildew/debris in the whirlpool skimmers and on the whirlpool basin.-Please clean the whirlpool basin and skimmers to remove any mildew/debris.2. The flow meter was not operational.-Please repair the flow meter.
- 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
- Monitoring Inspection
1 infraction
- 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
- 1. There was some mildew/debris in the whirlpool skimmers and on the whirlpool basin.-Please clean the whirlpool basin and skimmers to remove any mildew/debris.2. The flow meter was not operational.-Please repair the flow meter.
- 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
- Risk Management Inspection
0 infractions
- Demand Inspection
2 infractions
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- The water sample collected on February 12, 2025 had total coliforms present.-Treat and resample.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- The water sample collected on February 5, 2025 had a HPC count of 120 cfu/ml.-Submit a resample.
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Demand Inspection
1 infraction
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- The water sample collected on February 5, 2025 had a HPC count of 120 cfu/ml.-Submit a resample.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Risk Management Inspection
0 infractions
- Monitoring Inspection
1 infraction
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- Total alkalinity measured low at 48 gpm.- Maintain total alkalinity between 60 and 180gpm.
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- Initial Inspection
0 infractions