Delta Hotels By Marriott Edmonton South - Whirlpool

4404 Gateway Boulevard NW Edmonton AB T6H 5C2 · Aquatic Facility

8 inspections

  1. Risk Management Inspection

    2 infractions

    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • The free chlorine measurement on the controller is not consistent with the manual readings. Check and recalibrate controller as required.Service call was placed with ECOLAB to check controller.
    • 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
      • Grout between the tile on the floor of the basin is wearing and missing in some areas. Regrout areas where missing. Regrouting has been booked.
  2. Monitoring Inspection

    2 infractions

    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • The free chlorine measurement on the controller is not consistent with the manual readings. Check and recalibrate controller as required.
    • 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
      • 1. Grout between the tile on the floor of the basin is wearing and missing in some areas. Regrout areas where missing.2. Whirlpool water temperature in the basin was measured to be 40.5C. Adjust the thermostat so that the temperature of the water in the basin is maintained at 40C or less.
  3. Risk Management Inspection

    0 infractions

  4. Demand Inspection

    2 infractions

    • 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
      • The microbiological water sample submitted on 20 May 2025 was unsatisfactory: Pseudomonas aeruginosa isolated, Take all necessary action to ensure microbiologically safe water. Submit a new microbiological water sample at your earliest convenience once the water chemistry is balanced.
    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • The microbiological water sample submitted on 20 May 2025 was unsatisfactory: HPC 3030 CFU/mL. Take all necessary action to ensure microbiologically safe water. Submit a new microbiological water sample at your earliest convenience once the water chemistry is balanced.
  5. Risk Management Inspection

    0 infractions

  6. Monitoring Inspection

    1 infraction

    • 13. Are the general safety devices and physical conditions in this pool providing a safe environment (Non-Critical)?
      • The secondary anti-entrapment device (SVRS) has not been tested since shut down in May 2025. Test the pump devices and confirm compliance.
  7. Demand Inspection

    2 infractions

    • 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
      • The microbiological water sample submitted on 7 May 2024 was unsatisfactory: Pseudomonas aeruginosa isolated, Take all necessary action to ensure microbiologically safe water. Submit a new microbiological water sample at your earliest convenience once the water chemistry is balanced.
    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • The microbiological water sample submitted on 7 May 2024 was unsatisfactory: HPC >57000 CFU/mL. Take all necessary action to ensure microbiologically safe water. Submit a new microbiological water sample at your earliest convenience once the water chemistry is balanced.
  8. Risk Management Inspection

    0 infractions