Edgecliffe Estates - Pool
OFFICE - 3400 Edenwold Heights NW Calgary AB T3A 3Y8 · Aquatic Facility
11 inspections
- Monitoring Inspection
2 infractions
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- The flow meter was not functional; hence, the turnover rate and filtration rate could not be determined. Replace the flow meter.Previous violation:Filtration rate of the swimming pool was too fast calculated at 20 GPM/ ft^2.- Filtration rate for high-rate sand filters must be maintained below 15 GPM/ft2 for pools or provide filter specification sheet that confirm that the calculated filtration rate does not exceed manufactures specs.
- 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
- The pool ladders were wobbling and appeared unstable.Properly secure the ladders in the pool.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Demand Inspection
2 infractions
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Water sample collected on 18/07/2025, had a HPC of 3640 CFU/mL.Treat and resample.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Filtration rate of the swimming pool was too fast calculated at 20 GPM/ ft^2.- Filtration rate for high-rate sand filters must be maintained below 15 GPM/ft2 for pools or provide filter specification sheet that confirm that the calculated filtration rate does not exceed manufactures specs.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Risk Management Inspection
1 infraction
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Filtration rate of the swimming pool was too fast calculated at 20 GPM/ ft^2.- Filtration rate for high-rate sand filters must be maintained below 15 GPM/ft2 for pools or provide filter specification sheet that confirm that the calculated filtration rate does not exceed manufactures specs.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Monitoring Inspection
3 infractions
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- **Repeated violation: The filtration area information of the high rate sand filter was not available for the filter. The maximum filtration rate could not be calculated.*Find the filtration area information for the high rate sand filter.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- The filtration area information of the high-rate sand filter was not available for the filter. Thus, the maximum filtration rate could not be calculated.*Find the filtration area information for the high-rate sand filter.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- The flow meter after the filter was not functional. Hence turnover rate and filtration rate could not be determined. Replace the dysfunctional flow meter.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Demand Inspection
2 infractions
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- **Repeated violation: The filtration area information of the high rate sand filter was not available for the filter. The maximum filtration rate could not be calculated.*Find the filtration area information for the high rate sand filter.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- The filtration area information of the high-rate sand filter was not available for the filter. Thus, the maximum filtration rate could not be calculated.*Find the filtration area information for the high-rate sand filter.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Demand Inspection
3 infractions
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Water sample collected on 16th December 2024 was positive for Heterotrophic plate count at a value of #7060. Treat and resample
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- **Repeated violation: The filtration area information of the high rate sand filter was not available for the filter. The maximum filtration rate could not be calculated.*Find the filtration area information for the high rate sand filter.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- The filtration area information of the high-rate sand filter was not available for the filter. Thus, the maximum filtration rate could not be calculated.*Find the filtration area information for the high-rate sand filter.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Demand Inspection
3 infractions
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- May 27/24 Sample - HPC- 170CFU/ MLTreat and resample - spoke to ArlenJune 05/ 24 Sample - HPC 350 cfu/mlSpoke to Arlen - Pool closing for maintenance and as result of water main break incompliance with city of calgary. Nonetheless treat pool.June 13/24 HPC 1160 CFU/ML Spoke to ArlenGoing to further investigate - water bottles contaminated in strorage area was going to investiigate as POOL is closed - incompliance with City of Calgary requirements.Treat and resample with different water bottles
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- **Repeated violation: The filtration area information of the high rate sand filter was not available for the filter. The maximum filtration rate could not be calculated.*Find the filtration area information for the high rate sand filter.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- The filtration area information of the high-rate sand filter was not available for the filter. Thus, the maximum filtration rate could not be calculated.*Find the filtration area information for the high-rate sand filter.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Demand Inspection
3 infractions
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- May 27/24 Sample - HPC- 170CFU/ MLTreat and resample - spoke to ArlenJune 05/ 24 Sample - HPC 350 cfu/mlSpoke to Arlen - Pool closing for maintenance and as result of water main break incompliance with city of calgary. Nonetheless treat pool.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- **Repeated violation: The filtration area information of the high rate sand filter was not available for the filter. The maximum filtration rate could not be calculated.*Find the filtration area information for the high rate sand filter.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- The filtration area information of the high-rate sand filter was not available for the filter. Thus, the maximum filtration rate could not be calculated.*Find the filtration area information for the high-rate sand filter.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Demand Inspection
3 infractions
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- May 27/24 Sample - HPC- 170CFU/ MLTreat and resample - spoke to Arlen
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- **Repeated violation: The filtration area information of the high rate sand filter was not available for the filter. The maximum filtration rate could not be calculated.*Find the filtration area information for the high rate sand filter.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- The filtration area information of the high-rate sand filter was not available for the filter. Thus, the maximum filtration rate could not be calculated.*Find the filtration area information for the high-rate sand filter.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Risk Management Inspection
2 infractions
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- **Repeated violation: The filtration area information of the high rate sand filter was not available for the filter. The maximum filtration rate could not be calculated.*Find the filtration area information for the high rate sand filter.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- The filtration area information of the high-rate sand filter was not available for the filter. Thus, the maximum filtration rate could not be calculated.*Find the filtration area information for the high-rate sand filter.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Demand Inspection
3 infractions
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- HPC of 170 CFU/mL. Limit of 100CFU/mL. Treat pool and submit a resample.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- **Repeated violation: The filtration area information of the high rate sand filter was not available for the filter. The maximum filtration rate could not be calculated.*Find the filtration area information for the high rate sand filter.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- The filtration area information of the high-rate sand filter was not available for the filter. Thus, the maximum filtration rate could not be calculated.*Find the filtration area information for the high-rate sand filter.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?