Edgecliffe Estates - Whirlpool
OFFICE - 3400 Edenwold Heights NW Calgary AB T3A 3Y8 · Aquatic Facility
12 inspections
- Demand Inspection
3 infractions
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Water sample collected on 11/05/2026 was rejected due to time of collection not indicated on the form.Resample
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- The Filtration rate was recorded at 18.5 USG ft2.The filtration rate must be less than 12.5 USG/M/FT2 for whirlpools
- 12. Are the general safety devices and physical conditions in this pool providing a safe environment (Critical)?
- The anti-entrapment plan installed expired in March 2022.Install and submit an updated anti-entrapment plan.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Monitoring Inspection
3 infractions
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Water sample collected on 19/08/2025 tested positive for pseudomonas aeruginosa.Treat and resample
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- The Filtration rate was recorded at 18.5 USG ft2.The filtration rate must be less than 12.5 USG/M/FT2 for whirlpools
- 12. Are the general safety devices and physical conditions in this pool providing a safe environment (Critical)?
- The anti-entrapment plan installed expired in March 2022.Install and submit an updated anti-entrapment plan.
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Risk Management Inspection
0 infractions
- Demand Inspection
1 infraction
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Repeat violation:Water sample collected on 22/07/2025 tested positive for Pseudomonas aeruginosa.Recurring violation:The water sample collected on 18/07/2025, tested positive for pseudomonas aeruginosa.Close the hot tub.Repeat violation:The water sample collected on 14/07/2025, tested positive for Pseudomonas aeruginosa.Treat and resample.Previous violation:The water sample collected on 30/06/2025, tested positive for Pseudomonas aeruginosa.Treat and resample.
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Demand Inspection
1 infraction
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Recurring violation:The water sample collected on 18/07/2025, tested positive for pseudomonas aeruginosa.Close the hot tub.Repeat violation:The water sample collected on 14/07/2025, tested positive for Pseudomonas aeruginosa.Treat and resample.Previous violation:The water sample collected on 30/06/2025, tested positive for Pseudomonas aeruginosa.Treat and resample.
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Demand Inspection
2 infractions
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- The water sample collected on 14/07/2025, tested positive for Pseudomonas aeruginosa.Treat and resample.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- The water sample collected on 14/07/2025, had a HPC of 1230 CFC/mL.Treat and resample.
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Risk Management Inspection
0 infractions
- Risk Management Inspection
1 infraction
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Water sample result rejected. The sample was received more than 24 hours after collection.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Risk Management Inspection
0 infractions
- Monitoring Inspection
1 infraction
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Flow meter after the filter was not functional. Hence turnover rate and filtration rate could not be determined. Replace the dysfunctional flow meter.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Risk Management Inspection
0 infractions
- Demand Inspection
1 infraction
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Pseudomonas aeruginosa was isolated per 100mL.-Please treat the hot tub following AHS unsatisfactory water sample for Pseudomonas aeruginosa.
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?