Fairmont Banff Springs - Indoor Pool

405 Spray Avenue Banff AB T1L 1J4 · Aquatic Facility

4 inspections

  1. Monitoring Inspection

    2 infractions

    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • Alkalinity measured at 20ppm with AHS test kit and 40ppm with facility manual test. Raise alkalinity to at least 60ppm; preferrably between 80-120ppm. Discussed with operator and is in progress.
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • Automated controller values are not the same as manual readings/AHS test results, (pH lower than controller). As discussed, calibration is in progress.
  2. Demand Inspection

    1 infraction

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • Dec.19/24; HPC 120cfu/ml. Treat and resample.
  3. Monitoring Inspection

    0 infractions

  4. Monitoring Inspection

    3 infractions

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • Mar.18/24; HPC 130cfu/ml. Check systems and resample.
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • pH measured close to 7.5, setpoint on controller is 7.2. Check and calibrate controller to ensure manual tests and controller settings are consistent.
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • Skimmers closer to window seem to be pulling more water than skimmers close to wading pool. Ensure skimmers are balanced and provide adequate surface filtration.