Fairmont Banff Springs - Indoor Pool
405 Spray Avenue Banff AB T1L 1J4 · Aquatic Facility
4 inspections
- Monitoring Inspection
2 infractions
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- Alkalinity measured at 20ppm with AHS test kit and 40ppm with facility manual test. Raise alkalinity to at least 60ppm; preferrably between 80-120ppm. Discussed with operator and is in progress.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Automated controller values are not the same as manual readings/AHS test results, (pH lower than controller). As discussed, calibration is in progress.
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- Demand Inspection
1 infraction
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Dec.19/24; HPC 120cfu/ml. Treat and resample.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Monitoring Inspection
0 infractions
- Monitoring Inspection
3 infractions
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Mar.18/24; HPC 130cfu/ml. Check systems and resample.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- pH measured close to 7.5, setpoint on controller is 7.2. Check and calibrate controller to ensure manual tests and controller settings are consistent.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Skimmers closer to window seem to be pulling more water than skimmers close to wading pool. Ensure skimmers are balanced and provide adequate surface filtration.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?