Fairmont Banff Springs - Willow Stream Centre/Cascade Waterfall

405 Spray Avenue Banff AB T1L 1J4 · Aquatic Facility

Inspection summary

Fairmont Banff Springs - Willow Stream Centre/Cascade Waterfall has been inspected 10 times by Alberta Health Services (Environmental Public Health) since October 19, 2023. The most recent inspection, on April 28, 2026, recorded 3 infractions.

None of the 10 inspections on record were free of infractions. In the past 12 months there were 2 inspections with 4 infractions recorded. The higher-risk findings here relate to: Pool and spa water quality and Chemicals and toxic substances.

The number of infractions per inspection has stayed roughly the same over time.

What these findings mean

Health authorities word their findings differently, so we group them by what they mean for the people using the facility. Higher-risk findings are the ones that could directly cause illness or injury, such as water that is not properly treated.

  • Pool and spa water qualityHigher risk

    For pools, spas and splash pads, inspectors test disinfectant levels, pH and water clarity, and check safety equipment. Water that is not properly treated can spread skin, ear and stomach infections.

    Recorded 19 times across 10 separate inspections, most recently on April 28, 2026. For example: Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Critical)?

  • Chemicals and toxic substancesHigher risk

    Pool chemicals such as chlorine and acid must be labelled, stored apart from each other and handled safely. Mixing them by mistake can release toxic gas, so storage and handling problems are treated seriously.

    Recorded 4 times across 3 separate inspections, most recently on April 28, 2026. For example: Is the chemical quality of the water in this pool satisfactory (Non-Critical)?

About this data

These results come from Alberta Health Services (Environmental Public Health), which inspects food premises and other public facilities in this area. We republish the authority's public disclosure data and refresh it regularly; the official record is the final word.

10 inspections

  1. Monitoring Inspection

    3 infractions

    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • Alkalinity measured at 23ppm. Ensure alkalinity is adjusted often enough to remain in acceptable range.
    • 06. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Critical)?
      • 1. One of two Triton filters not in use to meet minimum filtration area for required flow rate. Additional filtration will be required if water quality can not be maintained.2. Flow rate is not meeting minimum turnover (65gpm, just over 1/2 of required) due to plumbing issues. If water quality can not be maintained, additional recirculation may be required.
    • 12. Are the general safety devices and physical conditions in this pool providing a safe environment (Critical)?
      • Automatic pump shut-off is not currently installed on recirculation pump as per anti-entrapment plan. Discussed and equipment is on-site and will be installed.
  2. Demand Inspection

    1 infraction

    • 06. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Critical)?
      • One of two Triton filters not in use. Due to leaks main drain has been closed and not achieving adequate turnover or filtration. Only achieving approximately 63gpm of flow rate which is half of what is required (112gpm). Unsatisfactory water samples noted in December.**Please provide our office with a written plan within 7 days on how circulation and disinfection will be corrected for this basin (alternatively, whirlpool could be closed until repairs are completed)**
  3. Demand Inspection

    2 infractions

    • 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
      • May 20/25; Sample positive for coliforms. Treat and resample.
    • 06. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Critical)?
      • One of two Triton filters not in use. Due to leaks main drain has been closed and not achieving adequate turnover or filtration. Only achieving approximately 63gpm of flow rate which is half of what is required (112gpm). Unsatisfactory water samples noted in December.**Please provide our office with a written plan within 7 days on how circulation and disinfection will be corrected for this basin (alternatively, whirlpool could be closed until repairs are completed)**
  4. Monitoring Inspection

    2 infractions

    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • Alkalinity measured at 12ppm (pH was at low end of the acceptable range during inspection). Ensure alkalinity is maintained at all times so that pH stays stable.
    • 06. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Critical)?
      • One of two Triton filters not in use. Due to leaks main drain has been closed and not achieving adequate turnover or filtration. Only achieving approximately 63gpm of flow rate which is half of what is required (112gpm). Unsatisfactory water samples noted in December.**Please provide our office with a written plan within 7 days on how circulation and disinfection will be corrected for this basin (alternatively, whirlpool could be closed until repairs are completed)**
  5. Risk Management Inspection

    1 infraction

    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • FLOW RECORDED AS APPROX 75GPM. FLOW MUST BE ADEQUATE TO PROVIDE REQUIRED TURNOVERS (FLOW SHOULD BE 112GPM)- IF UNSATISFACTORY SAMPLES ARE RECEIVED, UPGRADES WILL BE REQUIRED.
  6. Demand Inspection

    4 infractions

    • 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
      • Oct.1/24; Sample positive for TC.
    • 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
      • Dec.23/24; Pseudomonas isolated. HPC 130cfu/ml.Treat and resample.
    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • Dec.19/24; HPC slightly elevated at 120cfu/ml. Treat and resample.
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • FLOW RECORDED AS APPROX 75GPM. FLOW MUST BE ADEQUATE TO PROVIDE REQUIRED TURNOVERS (FLOW SHOULD BE 112GPM)- IF UNSATISFACTORY SAMPLES ARE RECEIVED, UPGRADES WILL BE REQUIRED.
  7. Demand Inspection

    3 infractions

    • 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
      • Oct.1/24; Sample positive for TC.
    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • Dec.19/24; HPC slightly elevated at 120cfu/ml. Treat and resample.
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • FLOW RECORDED AS APPROX 75GPM. FLOW MUST BE ADEQUATE TO PROVIDE REQUIRED TURNOVERS (FLOW SHOULD BE 112GPM)- IF UNSATISFACTORY SAMPLES ARE RECEIVED, UPGRADES WILL BE REQUIRED.
  8. Demand Inspection

    2 infractions

    • 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
      • Oct.1/24; Sample positive for TC.
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • FLOW RECORDED AS APPROX 75GPM. FLOW MUST BE ADEQUATE TO PROVIDE REQUIRED TURNOVERS (FLOW SHOULD BE 112GPM)- IF UNSATISFACTORY SAMPLES ARE RECEIVED, UPGRADES WILL BE REQUIRED.
  9. Monitoring Inspection

    3 infractions

    • 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
      • pH was under testing range. Controller setpoint 7.4. Calibrate controller and ensure pH stays between 6.8 and 7.6.
    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • Alkalinity measured at 47ppm. Maintain alkalinity between 60ppm and 180ppm (recommended range 80-120ppm). As discussed, reducing aeration of the pool water may aid in reducing loss of alkalinity.
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • FLOW RECORDED AS APPROX 75GPM. FLOW MUST BE ADEQUATE TO PROVIDE REQUIRED TURNOVERS (FLOW SHOULD BE 112GPM)- IF UNSATISFACTORY SAMPLES ARE RECEIVED, UPGRADES WILL BE REQUIRED.
  10. Demand Inspection

    2 infractions

    • 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
      • October 16/23; Sample positive for Pseudomonas, HPC 120 cfu/ml
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • FLOW RECORDED AS APPROX 75GPM. FLOW MUST BE ADEQUATE TO PROVIDE REQUIRED TURNOVERS (FLOW SHOULD BE 112GPM)- IF UNSATISFACTORY SAMPLES ARE RECEIVED, UPGRADES WILL BE REQUIRED.