Fairmont Palliser - Swimming Pool
133 9 Avenue SW Calgary AB T2P 2M3 · Aquatic Facility
22 inspections
- Risk Management Inspection
0 infractions
- Demand Inspection
1 infraction
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Water sample collected on June 30/26 was not processed because there was no time of collection indicated on the requisition form. - Submit a resample.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Monitoring Inspection
0 infractions
- Risk Management Inspection
0 infractions
- Demand Inspection
1 infraction
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Water sample collected Dec 31, 2025 came back unsatisfactory as the HPC was elevated (210CFU/mL). The maximum acceptable concentration for the HPC is 100CFU/mL.Please resample the swimming pool as soon as possible.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Risk Management Inspection
0 infractions
- Demand Inspection
1 infraction
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Unsatisfactory water sample #2: Water sample (25ES-350E00673) collected on December 16th, 2025, came back unsatisfactory as the HPC was elevated (250CFL/mL). The maximum acceptable concentration for the HPC is 100CFU/mL. Please treat, rebalance, and resample the swimming pool as soon as possible.Unsatisfactory water sample #1: Water sample (25ES-343E00732) collected on December 9th, 2025, came back unsatisfactory as the HPC was elevated (260CFL/mL). The maximum acceptable concentration for the HPC is 100CFU/mL. Please resample the swimming pool as soon as possible.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Demand Inspection
1 infraction
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Water sample (25ES-343E00732) collected on December 9th, 2025, came back unsatisfactory as the HPC was elevated (260CFL/mL). The maximum acceptable concentration for the HPC is 100CFU/mL. Please resample the swimming pool as soon as possible.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Risk Management Inspection
0 infractions
- Demand Inspection
1 infraction
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Water sample collected on April 29th, 2025, came back unsatisfactory as an elevated HPC of 130CFU/mL was detected.Please re-sample the swimming pool.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Monitoring Inspection
0 infractions
- Risk Management Inspection
1 infraction
- 06. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Critical)?
- The flow meter for the pool basin was stuck at the highest reading. Flow meters track the flow rate of the pool to measure correct circulation and identify issues like clogged pumps or inefficient chemical dispersion.***Repair or replace the flow meter and ensure staff are recording the flow daily
- 06. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Critical)?
- Demand Inspection
2 infractions
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Water sample collected on February 4th, 2025, has an HPC count of 240 CFU/ml. Please re-sample the pool immediately.
- 06. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Critical)?
- The flow meter for the pool basin was stuck at the highest reading. Flow meters track the flow rate of the pool to measure correct circulation and identify issues like clogged pumps or inefficient chemical dispersion.***Repair or replace the flow meter and ensure staff are recording the flow daily
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Demand Inspection
2 infractions
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Water sample taken Jan 14, 2025 - total coliforms present.-Treat and resample
- 06. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Critical)?
- The flow meter for the pool basin was stuck at the highest reading. Flow meters track the flow rate of the pool to measure correct circulation and identify issues like clogged pumps or inefficient chemical dispersion.***Repair or replace the flow meter and ensure staff are recording the flow daily
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Risk Management Inspection
1 infraction
- 06. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Critical)?
- The flow meter for the pool basin was stuck at the highest reading. Flow meters track the flow rate of the pool to measure correct circulation and identify issues like clogged pumps or inefficient chemical dispersion.***Repair or replace the flow meter and ensure staff are recording the flow daily
- 06. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Critical)?
- Demand Inspection
1 infraction
- 06. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Critical)?
- The flow meter for the pool basin was stuck at the highest reading. Flow meters track the flow rate of the pool to measure correct circulation and identify issues like clogged pumps or inefficient chemical dispersion.***Repair or replace the flow meter and ensure staff are recording the flow daily
- 06. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Critical)?
- Monitoring Inspection
1 infraction
- 06. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Critical)?
- The flow meter for the pool basin was stuck at the highest reading. Flow meters track the flow rate of the pool to measure correct circulation and identify issues like clogged pumps or inefficient chemical dispersion.***Repair or replace the flow meter and ensure staff are recording the flow daily
- 06. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Critical)?
- Demand Inspection
1 infraction
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- HPC 130 CFU/mL-Resample
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Monitoring Inspection
0 infractions
- Demand Inspection
5 infractions
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Sample collected and analyzed on 2023-09-11 shows the presence of HPC 180 cfu/ml. Treat the pool and resample.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- The water sample dated September 18, 2023, was not processed (date and time was not provided).REQUIREMENT: Ensure water samples are properly taken and paperwork properly filled out.
- 12. Are the general safety devices and physical conditions in this pool providing a safe environment (Critical)?
- Different screw holes are used to secure the main drain covers than what is specified in the manufacturer's instructions. Confirm the proper installation procedures with the manufacturer and ensure the main drain cover is installed accordingly.
- 16. Are proper testing, monitoring, and other records being properly maintained?
- Main drain checks are not conducted daily. Ensure staff are conducted main drain checks daily and are accurately recording the results.
- 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
- Written policies and plans are incomplete. An anti-entrapment plan has been started, but some additional information is required. Refer to sections 9, 10, 11, 12 and 13 of the pool standards for what information is required in the written policies and plans.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Demand Inspection
4 infractions
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Sample collected and analyzed on 2023-09-11 shows the presence of HPC 180 cfu/ml. Treat the pool and resample.
- 12. Are the general safety devices and physical conditions in this pool providing a safe environment (Critical)?
- Different screw holes are used to secure the main drain covers than what is specified in the manufacturer's instructions. Confirm the proper installation procedures with the manufacturer and ensure the main drain cover is installed accordingly.
- 16. Are proper testing, monitoring, and other records being properly maintained?
- Main drain checks are not conducted daily. Ensure staff are conducted main drain checks daily and are accurately recording the results.
- 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
- Written policies and plans are incomplete. An anti-entrapment plan has been started, but some additional information is required. Refer to sections 9, 10, 11, 12 and 13 of the pool standards for what information is required in the written policies and plans.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Demand Inspection
4 infractions
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- HPC >57000 CFU/mL-Resample
- 12. Are the general safety devices and physical conditions in this pool providing a safe environment (Critical)?
- Different screw holes are used to secure the main drain covers than what is specified in the manufacturer's instructions. Confirm the proper installation procedures with the manufacturer and ensure the main drain cover is installed accordingly.
- 16. Are proper testing, monitoring, and other records being properly maintained?
- Main drain checks are not conducted daily. Ensure staff are conducted main drain checks daily and are accurately recording the results.
- 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
- Written policies and plans are incomplete. An anti-entrapment plan has been started, but some additional information is required. Refer to sections 9, 10, 11, 12 and 13 of the pool standards for what information is required in the written policies and plans.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?