Glenmore Aquatic Centre - Whirlpool
5330 19 Street SW Calgary AB T3E 1P1 · Aquatic Facility
6 inspections
- Demand Inspection
1 infraction
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Water sample was cancelled since time collected was not indicated
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Demand Inspection
2 infractions
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- 1) Water sample collected on Oct 16, 2024 resulted in the presence of Total Coliform.ID: 24ES-290E00698
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- HPC of 140CFU/mLCollected 01/1525ES-015E00390
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Demand Inspection
1 infraction
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- 1) Water sample collected on Oct 16, 2024 resulted in the presence of Total Coliform.ID: 24ES-290E00698
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Demand Inspection
2 infractions
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- **water sample result was discussed on-site.May 29, 2024, ID: 24ES-150E00341; Req ID:2281984Pseudomonas ISOLATEDHPC= >57000 CFU/mL--empty and fill the hot tub, increase chlorine to 25mg/L (provided Pseudomonas Guidance from the EPH Website)
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- **water sample result was discussed on-site.May 29, 2024, ID: 24ES-150E00341; Req ID:2281984Pseudomonas ISOLATEDHPC= >57000 CFU/mL
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Monitoring Inspection
0 infractions
- Risk Management Inspection
1 infraction
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- The filtration rate of the whirlpool was too fast, calculated at 15.65 GPM/Sqft.-Please adjust the filter rate to ensure proper filtration/circulation of the whirlpool water.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?