Lakeland College Aquatic Center - Hot Tub

5707 College Drive Vermilion AB T9X 1K5 · Aquatic Facility

Inspection summary

Lakeland College Aquatic Center - Hot Tub has been inspected 11 times by Alberta Health Services (Environmental Public Health) since November 28, 2023. The most recent inspection, on October 2, 2026, recorded 1 infraction.

6 of 11 inspections on record found no infractions at all. In the past 12 months there were 4 inspections with 3 infractions recorded. The higher-risk findings here relate to: Pool and spa water quality and Chemicals and toxic substances.

The number of infractions per inspection has stayed roughly the same over time.

What these findings mean

Health authorities word their findings differently, so we group them by what they mean for the people using the facility. Higher-risk findings are the ones that could directly cause illness or injury, such as water that is not properly treated.

  • Pool and spa water qualityHigher risk

    For pools, spas and splash pads, inspectors test disinfectant levels, pH and water clarity, and check safety equipment. Water that is not properly treated can spread skin, ear and stomach infections.

    Recorded 5 times across 4 separate inspections, most recently on June 26, 2026. For example: Is the bacteriological quality of the water in this pool satisfactory (Critical)?

  • Chemicals and toxic substancesHigher risk

    Pool chemicals such as chlorine and acid must be labelled, stored apart from each other and handled safely. Mixing them by mistake can release toxic gas, so storage and handling problems are treated seriously.

    Recorded 2 times across 2 separate inspections, most recently on October 2, 2026. For example: Is the chemical quality of the water in this pool satisfactory (Non-Critical)?

About this data

These results come from Alberta Health Services (Environmental Public Health), which inspects food premises and other public facilities in this area. We republish the authority's public disclosure data and refresh it regularly; the official record is the final word.

11 inspections

  1. Demand Inspection

    1 infraction

    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • - Free Chlorine = 1.29mg/L- Combined Chlorine = .39 mg/L- Alkalinity = 38 mg/L well below proper operating threshold.- Discussed and reviewed with system operators, directed them to have pol chemistry adjusted to bring up Alkalinity.
  2. Risk Management Inspection

    0 infractions

  3. Demand Inspection

    2 infractions

    • 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
      • - Most recent water sample presence of Pseudomonas Aeruginosa.- Sample results hand delivered at this time.
    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • - Most recent sample showed elevated levels of HPC bacteria, 57,000.- Sample results reviewed with current staff, Crimson and Allan.
  4. Monitoring Inspection

    0 infractions

  5. Monitoring Inspection

    1 infraction

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • - Premise operators are not submitting water samples at the required frequency- Water samples are to be submitted for bacteriological analysis weekly as required.
  6. Risk Management Inspection

    1 infraction

    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • - Verified that Flow meter in treatment room for this water body has not been repaired or replaced - - Again verbally directed operator present to have a proper flow meter installed, one that can meet system requirements-
  7. Monitoring Inspection

    2 infractions

    • 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
      • - Free Chlorine = 4.2mg/L- Combined Chlorine = .51mg/L- pH = 7.8, discussed and reviewed at this time, operators adjusted/treated water body for pH correction (verbal). Requested increased monitoring of pH as well at this time -
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • - Flow meter in treatment room for this water body observed maxed out (incorrect flow meter installed).- Verbally directed operator present to have a proper flow meter installed, one that can meet system requirements-
  8. Demand Inspection

    0 infractions

  9. Demand Inspection

    0 infractions

  10. Demand Inspection

    0 infractions

  11. Monitoring Inspection

    0 infractions