Lakeland College Aquatic Center - Hot Tub
5707 College Drive Vermilion AB T9X 1K5 · Aquatic Facility
9 inspections
- Demand Inspection
2 infractions
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- - Most recent water sample presence of Pseudomonas Aeruginosa.- Sample results hand delivered at this time.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- - Most recent sample showed elevated levels of HPC bacteria, 57,000.- Sample results reviewed with current staff, Crimson and Allan.
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Monitoring Inspection
0 infractions
- Monitoring Inspection
1 infraction
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- - Premise operators are not submitting water samples at the required frequency- Water samples are to be submitted for bacteriological analysis weekly as required.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Risk Management Inspection
1 infraction
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- - Verified that Flow meter in treatment room for this water body has not been repaired or replaced - - Again verbally directed operator present to have a proper flow meter installed, one that can meet system requirements-
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Monitoring Inspection
2 infractions
- 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
- - Free Chlorine = 4.2mg/L- Combined Chlorine = .51mg/L- pH = 7.8, discussed and reviewed at this time, operators adjusted/treated water body for pH correction (verbal). Requested increased monitoring of pH as well at this time -
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- - Flow meter in treatment room for this water body observed maxed out (incorrect flow meter installed).- Verbally directed operator present to have a proper flow meter installed, one that can meet system requirements-
- 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
- Demand Inspection
0 infractions
- Demand Inspection
0 infractions
- Demand Inspection
0 infractions
- Monitoring Inspection
0 infractions