Lakeland College Aquatic Centre - Swimming Pool
5707 College Drive Vermilion AB T9X 1K5 · Aquatic Facility
11 inspections
- Risk Management Inspection
0 infractions
- Monitoring Inspection
1 infraction
- 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
- - Free Chlorine = 3.13 mg/L- Combined Chlorine = 0.24 mg/L- pH = 7.8 HIGH at this time, requires review. Directed operators at this time to adjust pool chemistry to reduce pH.
- 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
- Monitoring Inspection
1 infraction
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- - Discussed and reviewed required water sampling frequency with primary site manager again, water samples are required to be submitted on a weekly basis -- Request that premise operators submit water samples as required.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Monitoring Inspection
0 infractions
- Demand Inspection
0 infractions
- Demand Inspection
0 infractions
- Risk Management Inspection
1 infraction
- 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
- - Pool has had a structural failure of possibly all four main drains, sumps have severe degradation.- Discussed concerns with individuals present, informed that proper assessment will need to be done pertaining to the pools sub surface,- Informed that main drains will still need to be scoped for potential damage as well. - Pool assessment and repair work proposal to be conducted by Automated Aquatics and JAC Inc.
- 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
- Risk Management Inspection
1 infraction
- 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
- - Pool has had a structural failure of possibly all four main drains, sumps have severe degradation.- Discussed concerns with individuals present, informed that proper assessment will need to be done pertaining to the pools sub surface,- Informed that main drains will still need to be scoped for potential damage as well. - Pool assessment and repair work proposal to be conducted by Automated Aquatics and JAC Inc.
- 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
- Demand Inspection
1 infraction
- 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
- - Pool has had a structural failure of possibly all four main drains, sumps have severe degradation.- Discussed concerns with individuals present, informed that proper assessment will need to be done pertaining to the pools sub surface, will need to dry out more for any further assessment.- Informed that main drains will be scoped for potential damage as well. - Pool assessment and repair work proposal to be conducted by Automated Aquatics and JAC Inc.
- 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
- Demand Inspection
1 infraction
- 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
- - Pool has had a structural failure of possibly two floor main drains.- Informed this has been confirmed by divers who inspected pool drains due to excessive water loss from pool.- Operators in process of accessing extent of sump failure.
- 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
- Monitoring Inspection
0 infractions