  1. Monitoring Inspection

    2 infractions

    • 15. Has an owner or owner's agent, if any, been identified and is the pool operated and maintained by a qualified pool operator?
      • There is no trained pool operator to oversee the daily operation and maintenance of the facility.Ensure a qualified pool operator who has successfully completed a recognized pool operator education course must be provided to oversee and maintain the pool on a day-to-day basis. The pool operator must:i) Provide proof of successful completion of the course.ii) Demonstrate to the Executive Officer the ability to perform daily operations, including correct water sample collection, accurate manual pool chemistry testing and record keeping.
    • 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
      • -Written water quality incidence plan was reviewed with the operator.-Written sanitation plan was reviewed with the operator. -A recent anti-entrapment plan was not available for review.-Records were observed onsite for daily monitoring of automated readings and associated set points.-No records were observed onsite for daily visual checks and inspection of submerged suction outlets.Ensure written plans are developed and daily monitoring records are maintained.
  2. Demand Inspection

    4 infractions

    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • Total alkalinity was measured at 33ppm.Ensure TA is in the 60-180ppm range.
    • 15. Has an owner or owner's agent, if any, been identified and is the pool operated and maintained by a qualified pool operator?
      • There is no trained pool operator to oversee the daily operation and maintenance of the facility.Ensure a qualified pool operator who has successfully completed a recognized pool operator education course must be provided to oversee and maintain the pool on a day-to-day basis. The pool operator must:i) Provide proof of successful completion of the course.ii) Demonstrate to the Executive Officer the ability to perform daily operations, including correct water sample collection, accurate manual pool chemistry testing and record keeping.
    • 16. Are proper testing, monitoring, and other records being properly maintained?
      • -The facility is not testing total alkalinity regularly.Ensure total alkalinity is verified at least once a week.-Actions taken to balance water chemistry in case of water chemistry imbalance were not recorded.Ensure all the events related to water chemistry imbalance are documented.
    • 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
      • -Written water quality incidence plan was reviewed with the operator.-Written sanitation plan was reviewed with the operator. -A recent anti-entrapment plan was not available for review.-Records were observed onsite for daily monitoring of automated readings and associated set points.-No records were observed onsite for daily visual checks and inspection of submerged suction outlets.Ensure written plans are developed and daily monitoring records are maintained.
  3. Risk Management Inspection

    1 infraction

    • 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
      • -Written water quality incidence plan was reviewed with the operator.-Written sanitation plan was reviewed with the operator. -A recent anti-entrapment plan was not available for review.-Records were observed onsite for daily monitoring of automated readings and associated set points.-No records were observed onsite for daily visual checks and inspection of submerged suction outlets.Ensure written plans are developed and daily monitoring records are maintained.
  4. Demand Inspection

    3 infractions

    • 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
      • Sample submitted on Feb 11 was rejected.Previous inspection:Total coliforms present.
    • 12. Are the general safety devices and physical conditions in this pool providing a safe environment (Critical)?
      • -Submerged suction outlet (Main drain) covers were replaced. It is still to be determined if the drain covers are compliant. Ensure the drain covers are replaced. The main drain covers must meet the following requirements:-All submerged suction outlet covers must comply with ANSI/APSP-16 2011 performance standards.-Replacement covers must be compatible with sump type and dimensions.-The flow rate of each outlet must meet or exceed the maximum flow rate divided across interconnected outlets.-An anti-entrapment device must be installed and maintained in accordance with manufacturer specifications whenever the pool is in use.
    • 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
      • -Written water quality incidence plan was reviewed with the operator.-Written sanitation plan was reviewed with the operator. -A recent anti-entrapment plan was not available for review.-No records were observed onsite for daily monitoring of automated readings and associated set points.-No records were observed onsite for daily visual checks and inspection of submerged suction outlets.Ensure written plans are developed and daily monitoring records are maintained.
  5. Risk Management Inspection

    3 infractions

    • 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
      • Total coliforms present.
    • 12. Are the general safety devices and physical conditions in this pool providing a safe environment (Critical)?
      • -Submerged suction outlet (Main drain) covers were replaced. It is still to be determined if the drain covers are compliant. Ensure the drain covers are replaced. The main drain covers must meet the following requirements:-All submerged suction outlet covers must comply with ANSI/APSP-16 2011 performance standards.-Replacement covers must be compatible with sump type and dimensions.-The flow rate of each outlet must meet or exceed the maximum flow rate divided across interconnected outlets.-An anti-entrapment device must be installed and maintained in accordance with manufacturer specifications whenever the pool is in use.
    • 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
      • -Written water quality incidence plan was reviewed with the operator.-Written sanitation plan was reviewed with the operator. -A recent anti-entrapment plan was not available for review.-No records were observed onsite for daily monitoring of automated readings and associated set points.-No records were observed onsite for daily visual checks and inspection of submerged suction outlets.Ensure written plans are developed and daily monitoring records are maintained.
  6. Demand Inspection

    4 infractions

    • 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
      • Total coliforms present.
    • 12. Are the general safety devices and physical conditions in this pool providing a safe environment (Critical)?
      • -Submerged suction outlet (Main drain) covers were replaced. It is still to be determined if the drain covers are compliant. Ensure the drain covers are replaced. The main drain covers must meet the following requirements:-All submerged suction outlet covers must comply with ANSI/APSP-16 2011 performance standards.-Replacement covers must be compatible with sump type and dimensions.-The flow rate of each outlet must meet or exceed the maximum flow rate divided across interconnected outlets.-An anti-entrapment device must be installed and maintained in accordance with manufacturer specifications whenever the pool is in use.
    • 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
      • -One of the skimmer baskets was broken.Ensure the broken skimmer basket is replaced with a new one.
    • 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
      • -The facility had no written water quality incidence plan onsite.-The facility had no written sanitation plan onsite. -A recent anti-entrapment plan was not available for review.-No records were observed onsite for daily monitoring of automated readings and associated set points.-No records were observed onsite for daily visual checks and inspection of submerged suction outlets.Ensure written plans are developed and daily monitoring records are maintained.
  7. Risk Management Inspection

    3 infractions

    • 12. Are the general safety devices and physical conditions in this pool providing a safe environment (Critical)?
      • -Submerged suction outlet (Main drain) covers were replaced. It is still to be determined if the drain covers are compliant. Ensure the drain covers are replaced. The main drain covers must meet the following requirements:-All submerged suction outlet covers must comply with ANSI/APSP-16 2011 performance standards.-Replacement covers must be compatible with sump type and dimensions.-The flow rate of each outlet must meet or exceed the maximum flow rate divided across interconnected outlets.-An anti-entrapment device must be installed and maintained in accordance with manufacturer specifications whenever the pool is in use.
    • 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
      • -One of the skimmer baskets was broken.Ensure the broken skimmer basket is replaced with a new one.
    • 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
      • -The facility had no written water quality incidence plan onsite.-The facility had no written sanitation plan onsite. -A recent anti-entrapment plan was not available for review.-No records were observed onsite for daily monitoring of automated readings and associated set points.-No records were observed onsite for daily visual checks and inspection of submerged suction outlets.Ensure written plans are developed and daily monitoring records are maintained.
  8. Monitoring Inspection

    8 infractions

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • -Pool water samples are not being submitted weekly to the Provincial lab for microbiological testing.Ensure the water is sampled weekly.
    • 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
      • -Free available chlorine was measured at 0.2 ppm.Ensure FAC is at least 1ppm for the pool that operates <30 degrees temperature.
    • 06. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Critical)?
      • -No skimming action was observed during the inspection. The water level was too low to enter the skimmers.Ensure the water level is at least halfway through the skimmers.
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • -The turnover rate with a flow rate of 25 gpm was 11.7 hours.Ensure the flow rate is increased and the turnover rate is close to 4 hours.
    • 12. Are the general safety devices and physical conditions in this pool providing a safe environment (Critical)?
      • -Submerged suction outlet (Main drain) covers were expired.Ensure the drain covers are replaced. The main drain covers must meet the following requirements:-All submerged suction outlet covers must comply with ANSI/APSP-16 2011 performance standards.-Replacement covers must be compatible with sump type and dimensions.-The flow rate of each outlet must meet or exceed the maximum flow rate divided across interconnected outlets.-An anti-entrapment device must be installed and maintained in accordance with manufacturer specifications whenever the pool is in use.
    • 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
      • -One of the skimmer baskets was broken.Ensure the broken skimmer basket is replaced with a new one.
    • 16. Are proper testing, monitoring, and other records being properly maintained?
      • -Daily manual chemical testing records were incomplete.Ensure the records are complete and available for review by an Executive Officer.
    • 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
      • -The facility had no written water quality incidence plan onsite.-The facility had no written sanitation plan onsite. -A recent anti-entrapment plan was not available for review.-No records were observed onsite for daily monitoring of automated readings and associated set points.-No records were observed onsite for daily visual checks and inspection of submerged suction outlets.Ensure written plans are developed and daily monitoring records are maintained.
  9. Risk Management Inspection

    0 infractions

  10. Demand Inspection

    1 infraction

    • 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
      • A Light Fixture was out of it's Socket in the Pool at the time of Inspection.Ensure that the Light Fixture is fully reattached in order to prevent potential injuries.The Light Fixture was off at the time of Inspection was the Operator stated that the Light Fixture is water proof and thus there should be no electrical hazard.
  11. Risk Management Inspection

    0 infractions

  12. Risk Management Inspection

    2 infractions

    • 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
      • There was a minor buildup of sand/dirt in the bottom corners of the pool at the time of Inspection.Ensure that the pool is being cleaned more regularly in order to facilitate proper operating chemistry/disinfection in the pool.Change Rooms, Bathrooms, and Pool Deck areas were clean and well maintained at the time of Inspection.Functional Shower and Hand Sinks were available and fully stocked with supplies.
    • 16. Are proper testing, monitoring, and other records being properly maintained?
      • Testing Reagents were running low at the time of Inspection.Ensure that more Testing Reagents are kept in stock in order to facilitate proper pool chemistry testing. Up to date Testing Records were available on site at the time of Inspection.Reagents on order at the time of Inspection.
  13. Monitoring Inspection

    4 infractions

    • 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
      • Water Temperature: 27.5 degrees Celsius.pH: 6.5 - Too Low.Alk: 55 ppm - Too Low.Cl: 1.35 ppm.ORP: 720.Ensure that the pH is brought up into the 6.8-7.6 range in order to facilitate proper operating chemistry/disinfection in the pool.
    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • Water Temperature: 27.5 degrees Celsius.pH: 6.5 - Too Low.Alk: 55 ppm - Too Low.Cl: 1.35 ppm.ORP: 720.Ensure that the Alkalinity is brought up into the 60-180 range in order to facilitate proper operating chemistry/disinfection in the pool.
    • 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
      • There was a minor buildup of sand/dirt in the bottom corners of the pool at the time of Inspection.Ensure that the pool is being cleaned more regularly in order to facilitate proper operating chemistry/disinfection in the pool.Change Rooms, Bathrooms, and Pool Deck areas were clean and well maintained at the time of Inspection.Functional Shower and Hand Sinks were available and fully stocked with supplies.
    • 16. Are proper testing, monitoring, and other records being properly maintained?
      • Testing Reagents were running low at the time of Inspection.Ensure that more Testing Reagents are kept in stock in order to facilitate proper pool chemistry testing. Up to date Testing Records were available on site at the time of Inspection.
  14. Risk Management Inspection

    0 infractions

  15. Demand Inspection

    1 infraction

    • 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
      • TC Present.
  16. Risk Management Inspection

    0 infractions

  17. Demand Inspection

    1 infraction

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • 1. HPC > 57,000
  18. Demand Inspection

    1 infraction

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • 1. HPC = 3170
  19. Risk Management Inspection

    0 infractions

  20. Demand Inspection

    1 infraction

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • HPC @ 220.
  21. Risk Management Inspection

    0 infractions

  22. Demand Inspection

    1 infraction

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • HPC 460
  23. Monitoring Inspection

    1 infraction

    • 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
      • The Corners of the Pool had an accumulation of Sand/Dirt at the time of Inspection.Ensure that the Pool is being cleaned more regularly in order to meet requirements.This was Corrected during the Inspection.
  24. Monitoring Inspection

    2 infractions

    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • One of the Pool Skimmers was partially blocked with debris at the time of Inspection.Ensure that the Skimmers are being cleaned out more regularly in order to maintain adequate flow. This was Corrected during the Inspection.
    • 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
      • The Scum line was dirty at the time of Inspection.Ensure that the Scum line is being cleaned more regularly in order to prevent potential contamination of the pool water.This was Corrected during the Inspection.
  25. Risk Management Inspection

    0 infractions

  26. Risk Management Inspection

    1 infraction

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • 1. HPC 500Check water chemistry (FC and pH) and resample.
  27. Risk Management Inspection

    0 infractions

  28. Monitoring Inspection

    1 infraction

    • 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
      • The Skimmers for the Pool had an accumulation of debris at the time of Inspection.Ensure that the Skimmers area cleaned more regularly in order to facilitate proper functioning.
  29. Risk Management Inspection

    0 infractions

  30. Monitoring Inspection

    0 infractions

  31. Risk Management Inspection

    0 infractions

  32. Demand Inspection

    1 infraction

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • HPC @ 580.
  33. Monitoring Inspection

    2 infractions

    • 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
      • Description: Water Temperature: 19.8 degrees Celsius.pH: 6.4.Alk: 52 ppm.Cl: 7.0 ppm.ORP: 778. Water chemistry was tested onsite, pH and Alkalinity were found to be low at 6.4 and 52 respectively, at the time of Inspection.Ensure that pH is kept within the safe range of 6.8-7.6 at all times. Ensure that Alkalinity is kept within the safe range of 60-180 at all times. This was Corrected during the Inspection and re-measured to be at: pH : 7.0, and ALK: 72.Recommend lowering Chlorine levels slightly as well.
    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • Description: Water Temperature: 19.8 degrees Celsius.pH: 6.4.Alk: 52 ppm.Cl: 7.0 ppm.ORP: 778. Water chemistry was tested onsite, pH and Alkalinity were found to be low at 6.4 and 52 respectively, at the time of Inspection.Ensure that pH is kept within the safe range of 6.8-7.6 at all times. Ensure that Alkalinity is kept within the safe range of 60-180 at all times. This was Corrected during the Inspection and re-measured to be at: pH : 7.0, and ALK: 72.Recommend lowering Chlorine levels slightly as well.