Skip to content
Loading map…

Radisson Hotel & Suites Fort McMurray - Whirlpool

435 Gregoire Drive Fort McMurray AB T9H 4K7 · Aquatic Facility

Inspection summary

Radisson Hotel & Suites Fort McMurray - Whirlpool has been inspected 8 times by Alberta Health Services (Environmental Public Health) since September 11, 2024. The most recent inspection, on October 16, 2026, recorded 2 infractions.

None of the 8 inspections on record were free of infractions. In the past 12 months there were 4 inspections with 5 infractions recorded. The higher-risk findings here relate to: Pool and spa water quality and Food temperature control.

Recent inspections have recorded fewer infractions than earlier ones, so the record is improving.

What these findings mean

Health authorities word their findings differently, so we group them by what they mean for the people using the facility. Higher-risk findings are the ones that could directly cause illness or injury, such as water that is not properly treated.

  • Pool and spa water qualityHigher risk

    For pools, spas and splash pads, inspectors test disinfectant levels, pH and water clarity, and check safety equipment. Water that is not properly treated can spread skin, ear and stomach infections.

    Recorded 10 times across 5 separate inspections, most recently on October 16, 2026. For example: Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?

  • Food temperature controlHigher risk

    Inspectors check that anything that has to be kept at a set temperature, such as chilled or hot food, or equipment like sterilizers, stays in its safe range and that accurate thermometers are on hand. With food, temperature problems are one of the most common causes of food poisoning.

    Recorded 2 times across 2 separate inspections, most recently on October 30, 2024. For example: Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?

  • Food safety training and certificationLower risk

    Many jurisdictions require trained pool operators and certified lifeguards. These findings mean required training, certification or staffing records were missing at the time of inspection.

    Recorded 6 times across 6 separate inspections, most recently on October 16, 2026. For example: Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?

About this data

These results come from Alberta Health Services (Environmental Public Health), which inspects food premises and other public facilities in this area. We republish the authority's public disclosure data and refresh it regularly; the official record is the final word.

8 inspections

  1. Demand Inspection

    2 infractions

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • The microbiological water result submitted for the pool(s) was unsatisfactoryUnsatisfactory Lab Test Result:Collection Date: 2026-10-13Location: Swimming Pool** Heterotrophic Plate Count: 210 CFU/mLThe Heterotrophic Plate Count must be less than 100 CFU/ml in a pool water sample.Take all required measures to ensure water safety and submit your next water sample on regular sampling time.
    • 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
      • Facility lacked complete and updated documents for the written anti-entrapment plans. A secondary anti-entrapment device safety vacuum release system was observed.Complete and submit the written anti-entrapment plans to the public health inspector. Update July 10, 2026 - the anti entrapment plans were not completed and there are missing information. Main drains (suction outlets) indicated more than 26 inches apart and have a secondary anti-entrapment device safety vacuum release system was observed.Update October 1, 2026: The current anti-entrapment plans were observed not completed. There wasseveral missing information including maximum flow ratings, submerged outlet cover specifications, and sump details.
  2. Risk Management Inspection

    1 infraction

    • 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
      • Facility lacked complete and updated documents for the written anti-entrapment plans. A secondary anti-entrapment device safety vacuum release system was observed.Complete and submit the written anti-entrapment plans to the public health inspector. Update July 10, 2026 - the anti entrapment plans were not completed and there are missing information. Main drains (suction outlets) indicated more than 26 inches apart and have a secondary anti-entrapment device safety vacuum release system was observed.Update October 1, 2026: The current anti-entrapment plans were observed not completed. There wasseveral missing information including maximum flow ratings, submerged outlet cover specifications, and sump details.
  3. Monitoring Inspection

    1 infraction

    • 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
      • Facility lacked complete and updated documents for the written anti-entrapment plans. A secondary anti-entrapment device safety vacuum release system was observed.Complete and submit the written anti-entrapment plans to the public health inspector. Update July 10, 2026 - the anti entrapment plans were not completed and there are missing information. Main drains (suction outlets) indicated more than 26 inches apart and have a secondary anti-entrapment device safety vacuum release system was observed.
  4. Monitoring Inspection

    1 infraction

    • 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
      • Facility lacked complete and updated documents for the written anti-entrapment plans. A secondary anti-entrapment device safety vacuum release system was observed.Complete and submit the written anti-entrapment plans to the public health inspector.
  5. Risk Management Inspection

    3 infractions

    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • The turnover period was calculated at 18 minutes. (The hot tub volume is 400US gallons = 1.5 cubic meters.)Ensure that 100% of the water volume passes through treatment and is recirculated within 15 minutes.
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • The automated system for testing pH was observed leaking in the maintenance room. Ensure that the automated system is working and maintained in good condition.
    • 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
      • The hot tub basin paint was observed to be stripped off the surfaces. Refinish the basin and ensure it is maintained in good condition.
  6. Monitoring Inspection

    2 infractions

    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • The turnover period was calculated at 18 minutes. (The hot tub volume is 400US gallons = 1.5 cubic meters.)Ensure that 100% of the water volume passes through treatment and is recirculated within 15 minutes.
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • The automated system for testing pH was observed leaking in the maintenance room. Ensure that the automated system is working and maintained in good condition.
  7. Risk Management Inspection

    3 infractions

    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • The water circulation system lacked a flow meter. Obtain and install a functioning flow meter prior to opening the pool to determine the recirculation rate that is acceptable and complies with the Pool Standard. Ensure the flow meter is installed according to the manufacturing instructions. Note (Oct 9, 2024): facility operator has provided an invoice and manual for the flow meter. Operator states the meter will be received within the next week.
    • 12. Are the general safety devices and physical conditions in this pool providing a safe environment (Critical)?
      • Hot tub lacked a secondary anti-entrapment device.Obtain and install an anti-entrapment device according to the manufacturing instructions prior to opening the hot tub.Note: Facility operator provided the invoice for the purchased device. Operator stated it will take 5-6 weeks to be delivered.
    • 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
      • A "no diving" sign is not located near the whirlpool. However, depth markings were observed. Ensure that a "no diving" sign is posted on the wall near the whirlpool.Note: facility operator stated a sign has been ordered and will arrive within the next week.
  8. Demand Inspection

    5 infractions

    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • Rust like staining observed on the covers of the jet pump, skimmer, and suction outlets. Ensure that the covers are in good condition. If the covers are to be replaced, ensure they are installed according to the manufacturing instructions.
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • The water circulation system lacked a flow meter. Install a flow determine the recirculation rate that is acceptable and complies with the Pool Standard.
    • 10. Are general nuisance conditions, other than those noted in other violations, being prevented at this pool (Non-Critical)?
      • The circulation plumbing system did not clearly label the direction of water flow. Label the circulation direction of water flow and provide the PHI with the written plumbing schematics detailing the plumbing design of the pool and whirlpool. Including the water circulation and treatment systems, waterslides and list described in the Information to Support a Public Pool Permit Application document.
    • 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
      • Previously noted basin condition violations were not observed. However, it was discussed that the pool basin would be refurnished. The whirlpool basin must be free from cracks, non-absorbent, easily cleanable, and non-slip.
    • 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
      • 1. There are no depth markings on the deck around the whirlpool. 2. A "no diving" sign is not located near the whirlpool.1. Ensure that depth markings are located around the whirlpool deck. 2. Ensure that a "no diving" sign is posted on the wall near the whirlpool.

Nearby inspected facilities