Ramada by Wyndham Hinton - Swimming Pool

149 Woodley Drive Hinton AB T7V 2C5 · Aquatic Facility

24 inspections

  1. Risk Management Inspection

    0 infractions

  2. Monitoring Inspection

    1 infraction

    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • Turnover period: 4.8 hours. - The turnover period must be maintained at no more than 4 hours to ensure water quality. A minimum flow rate of 66 GPM is required to achieve a 4‑hour turnover period.
  3. Risk Management Inspection

    0 infractions

  4. Risk Management Inspection

    1 infraction

    • 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
      • - The pool does not have any visible depth markings. The pool operator reported that new depth markers have been ordered and are expected to arrive within the next few weeks.Install the new depth markings as soon as they are received to ensure swimmer safety and compliance with regulatory requirements. Depth markings must be clearly visible and maintained in good condition at all times.
  5. Monitoring Inspection

    2 infractions

    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • The initial flow rate was observed to be close to 100 gpm. The operator was instructed to adjust the flow rate to 60 gpm. The operator then reduced the flow rate to 70 gpm.Maintain the flow rate at the required 70 gpm and ensure routine monitoring to prevent fluctuations.
    • 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
      • - The pool does not have any visible depth markings. The pool operator reported that new depth markers have been ordered and are expected to arrive within the next few weeks.Install the new depth markings as soon as they are received to ensure swimmer safety and compliance with regulatory requirements. Depth markings must be clearly visible and maintained in good condition at all times.- The facility does not have a Water Quality Incident Response Plan in place for fecal contamination.Develop and implement a Water Quality Incident Response Plan that outlines procedures for responding to fecal contamination incidents. Ensure staff are trained on the plan and that it is kept on-site for reference.
  6. Risk Management Inspection

    0 infractions

  7. Demand Inspection

    1 infraction

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • Water sample collected on Jan 13, 2026 was unsatisfactory: Heterotrophic Plate Count (HPC) was 430.- Please ensure HPC is maintained at no greater than 100.
  8. Risk Management Inspection

    0 infractions

  9. Monitoring Inspection

    1 infraction

    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • Turnover period: 5.3 hours. May 30, 2025: Turnover period: 4.8 hours. - The turnover period needs to be maintained at no more than 4 hours to ensure water quality.Oct 20, 2025: Turnover period: 5.3 hours.
  10. Risk Management Inspection

    1 infraction

    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • Turnover period: 5.3 hours. May 30, 2025: Turnover period: 4.8 hours. - The turnover period needs to be maintained at no more than 4 hours to ensure water quality.
  11. Demand Inspection

    2 infractions

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • The water sample collected on August 26 was not satisfactory - Heterotrophic Plate Count (HPC) was 210.- Please ensure HPC is maintained at no greater than 100. -Investigate the filtration, circulation, and disinfection systems of the pool, and treat the pool water.
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • Turnover period: 5.3 hours. May 30, 2025: Turnover period: 4.8 hours. - The turnover period needs to be maintained at no more than 4 hours to ensure water quality.
  12. Monitoring Inspection

    1 infraction

    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • Turnover period: 5.3 hours. May 30, 2025: Turnover period: 4.8 hours. - The turnover period needs to be maintained at no more than 4 hours to ensure water quality.
  13. Risk Management Inspection

    1 infraction

    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • Turnover period: 5.3 hours. The turnover period needs to be maintained at no more than 4 hours to ensure water quality.
  14. Risk Management Inspection

    1 infraction

    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • The flow meter is not in operation. As a result, the turnover period and rate of filtration of the pool are not determined.Please maintain or replace the flow meter.Feb 5: Manager advised a new flow meter was ordered that would be installed within a week.Feb 12: Manager advised the ordered flow arrived and is pending installation.Feb 24: New flow meter was installed recently, but it was not operational at the time of inspection. Operator advised the plumber who installed the flow meter has been called in to check it.
  15. Monitoring Inspection

    1 infraction

    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • The flow meter is not in operation. As a result, the turnover period and rate of filtration of the pool are not determined.Please maintain or replace the flow meter.Feb 5: Manager advised a new flow meter was ordered that would be installed within a week.Feb 12: Manager advised the ordered flow arrived and is pending installation.
  16. Risk Management Inspection

    1 infraction

    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • The flow meter is not in operation. As a result, the turnover period and rate of filtration of the pool are not determined.Please maintain or replace the flow meter.Feb 5: Manager advised a new flow meter was ordered that would be installed within a week.
  17. Monitoring Inspection

    2 infractions

    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • The flow meter is not in operation. As a result, the turnover period and rate of filtration of the pool are not determined.Please maintain or replace the flow meter.
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • The floating weir (door) of the skimmer (Northwest side of the pool basin) is not floating. - Please repair or replace.
  18. Risk Management Inspection

    0 infractions

  19. Demand Inspection

    1 infraction

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • The water sample collected on July 16, 2024 was not satisfactory - Heterotrophic Plate Count (HPC) was 650.
  20. Risk Management Inspection

    0 infractions

  21. Demand Inspection

    2 infractions

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • The water sample collected on June 4, 2024 was not satisfactory - Heterotrophic Plate Count (HPC) was 490.
    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • The water sample collected on June 11, 2024 was not satisfactory - Heterotrophic Plate Count (HPC) was 700.
  22. Demand Inspection

    1 infraction

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • The water sample collected on June 4, 2024 was not satisfactory - Heterotrophic Plate Count (HPC) was 490.
  23. Risk Management Inspection

    0 infractions

  24. Demand Inspection

    2 infractions

    • 16. Are proper testing, monitoring, and other records being properly maintained?
      • Observed combined chlorine not being tested daily. The need to test combined chlorine to ensure water quality was discussed with the operator.
    • 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
      • No written policies were developed and maintained for: - general sanitation - response to water quality issues including fecal contaminationPlease develop written policies for general sanitation and for response to water quality incident and implement use.