Royal Glenora Club - Main Whirlpool
11160 River Valley Road NW Edmonton AB T5J 2G7 · Aquatic Facility
9 inspections
- Risk Management Inspection
0 infractions
- Demand Inspection
2 infractions
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- The microbiological water sample collected on Apr. 14, 2026, was unsatisfactory: Pseudomonas aeruginosa isolated. Take all necessary action to ensure microbiologically safe water. Submit a new microbiological water sample at your earliest convenience once the water chemistry is balanced.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- The microbiological water sample collected on Apr. 14, 2026, was unsatisfactory: HPC >100 CFU/mL. Take all necessary action to ensure microbiologically safe water. Submit a new microbiological water sample at your earliest convenience once the water chemistry is balanced.
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Monitoring Inspection
0 infractions
- Monitoring Inspection
0 infractions
- Risk Management Inspection
0 infractions
- Monitoring Inspection
1 infraction
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Adjust the flow of the pool to less than 388 GPM to ensure the filtration rate does not exceed 12.5 GPM/sq ft.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Monitoring Inspection
3 infractions
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- Alkalinity:44 ppm
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Filtration rate (13.3gpm/sq ft) does not complies with the manufactures specifications (12.5gpm/sq ft). The flow rate was higher than the maximum flow listed of 387.5GPM.Adjust the flow rate to achieve the required filtration rate of 12.5 gpm/sq ft or below.
- 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
- Gout was missing between the tiles at floor of the basin. Repair required.
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- Monitoring Inspection
1 infraction
- 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
- Gout was missing between the tiles at floor of the basin. Repair required.
- 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
- Monitoring Inspection
0 infractions