Super 8 High Level - Whirlpool
9502 114 Avenue High Level AB T0H 1Z0 · Aquatic Facility
3 inspections
- Monitoring Inspection
0 infractions
- Risk Management Inspection
0 infractions
- Monitoring Inspection
4 infractions
- 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
- Free chlorine measured 9.5 ppm. pH measured 7.8Pool operator closed the whirlpool at time of inspection. Whirlpool will be drained. Ensure that the pool chemistry meets the Alberta Pool Standards prior to re-opening.
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- Alkalinity measured highCombine chlorines measured 0.05 ppm
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- The water level in the whirlpool was too high. This does not allow the skimmer to properly draw in surface water and suck it through the whirlpool's filtration system.
- 16. Are proper testing, monitoring, and other records being properly maintained?
- The water chemistry is not tested frequently enough. Parameters must be monitored 30 minutes prior to opening and every 2 hours thereafter.
- 04. Is the chemical quality of the water in this pool satisfactory (Critical)?