Skip to content
Loading map…

Super 8 Motel-Hot Tub

5129 Highway 21 S, Port Elgin ON N0H 2C0 · Indoor

Inspection summary

Super 8 Motel-Hot Tub has been inspected 11 times by Grey Bruce Health Unit (Grey Bruce Public Health) since October 16, 2023. The most recent inspection, on September 28, 2026, found no infractions.

6 of 11 inspections on record found no infractions at all. In the past 12 months there were 5 inspections with 14 infractions recorded. The higher-risk findings here relate to: Pool and spa water quality and Chemicals and toxic substances.

The last 2 inspections in a row found no infractions. Recent inspections have recorded more infractions than earlier ones, so it is worth reading the latest reports closely.

What these findings mean

Health authorities word their findings differently, so we group them by what they mean for the people using the facility. Higher-risk findings are the ones that could directly cause illness or injury, such as water that is not properly treated.

  • Pool and spa water qualityHigher risk

    For pools, spas and splash pads, inspectors test disinfectant levels, pH and water clarity, and check safety equipment. Water that is not properly treated can spread skin, ear and stomach infections.

    Recorded 6 times across 4 separate inspections, most recently on July 2, 2026. For example: Spa is maintained in safe and sanitary condition, free from hazards and rendered inaccessible when not in use

  • Chemicals and toxic substancesHigher risk

    Pool chemicals such as chlorine and acid must be labelled, stored apart from each other and handled safely. Mixing them by mistake can release toxic gas, so storage and handling problems are treated seriously.

    Recorded once on June 30, 2026. For example: Continuous operation of circulation system and chemical feeders

  • Permits, records and postingLower risk

    Operating permits, water-test logs, posted bather rules and emergency procedures. Daily test logs are how operators show the water was checked and treated between inspections.

    Recorded 3 times across 2 separate inspections, most recently on June 30, 2026. For example: Operator trained in operation, maintenance, filtration systems, water chemistry and all relevant safety & emergency procedures

  • Equipment and utensilsLower risk

    Pumps, filters, chemical feeders and safety equipment such as lifebuoys, reaching poles and first-aid kits must be present and working. Missing safety equipment can matter a great deal in an emergency.

    Recorded once on June 30, 2026. For example: Records of safety related equipment inspection maintained at a frequency of once every 30 day operating period

  • Other findingsLower risk

    Findings that do not fit the categories above, such as follow-ups that confirm an earlier violation was corrected, or requirements specific to this type of facility.

    Recorded 7 times across 5 separate inspections, most recently on July 2, 2026. For example: Total bromine maintained between 5-10 ppm

About this data

These results come from Grey Bruce Health Unit (Grey Bruce Public Health), which inspects food premises and other public facilities in this area. We republish the authority's public disclosure data and refresh it regularly; the official record is the final word.

11 inspections

  1. Routine

    0 infractions

  2. Routine

    0 infractions

  3. Follow-up

    2 infractions

    • Spa is maintained in safe and sanitary condition, free from hazards and rendered inaccessible when not in use
    • Total bromine maintained between 5-10 ppm
  4. Routine

    8 infractions

    • Operator provided required notification
      • Fail to notify of intended re-opening date of public spa for use [clause 5 (1) (c)]
    • Operator trained in operation, maintenance, filtration systems, water chemistry and all relevant safety & emergency procedures
      • Operator not trained in public spa water chemistry subsection [6 (2)]
    • Spa is maintained in safe and sanitary condition, free from hazards and rendered inaccessible when not in use
      • Fail to ensure spa rendered inaccessible, outside of daily use period, to persons not involved with its operation, inspection or maintenance [clause 6 (3) (b)]
    • Continuous operation of circulation system and chemical feeders
      • Fail to ensure continuous, 24-hour operation of chemical feeders each day except for necessary stoppage [clause 6 (3) (d)]
    • All components of spa are maintained in proper working order
      • Fail to ensure all components of spa maintained in proper working order [clause 6 (6) (a)]
    • Total bromine maintained between 5-10 ppm
      • Fail to ensure total bromine of public spa water maintained between 5 – 10 ppm [clause 7 (8) (c)]
    • Required manual tests completed at least 30 minutes before opening and values recorded
      • Fail to manually test total chlorine or bromine residual at least 30 minutes before opening public spa [paragraph 3 of subsection 7 (11)]
      • Fail to record total chlorine or bromine residual at least 30 minutes before opening public spa [paragraph 3 of subsection 7 (11)]
    • Records of safety related equipment inspection maintained at a frequency of once every 30 day operating period
      • Operator fail to record results of inspection of safety related equipment present in the facility at frequency determined by public health inspector [subsection 26.5]
  5. Routine

    4 infractions

    • Operator provided required notification
    • pH maintained between 7.2-7.8
    • Free available chlorine maintained between 5-10 ppm
    • Water heater cut off switch requirements met
      • Fail to ensure public spa water heater equipped with tamper-proof upper limit cut off switch [section 21]
      • Fail to ensure tamper-proof upper limit cut off switch limits maximum temperature of public spa water to 40 degrees Celsius [clause 21 (a)]
      • Fail to ensure tamper-proof upper limit cut off switch independent of public spa’s water temperature thermostat [clause 21 (b)]
  6. Follow-up

    0 infractions

  7. Complaint

    1 infraction

    • Emergency stop button requirements met
      • Emergency stop button — does not activate audible signal when used [clause 26 (1) (c)]
      • Emergency stop button — does not activate visual signal when used [clause 26 (1) (c)]
  8. Routine

    0 infractions

  9. Follow-up

    0 infractions

  10. Routine

    3 infractions

    • Operator trained in operation, maintenance, filtration systems, water chemistry and all relevant safety & emergency procedures
      • Operator not trained in public spa water chemistry subsection [6 (2)]
      • Operator not trained in all relevant public spa safety procedures subsection [6 (2)]
      • Operator not trained in all relevant public spa emergency procedures subsection [6 (2)]
    • Total alkalinity maintained between 80-120 ppm
      • Fail to ensure alkalinity of public spa water maintained in range of 80 – 120 ppm [clause 7 (8) (a)]
    • Total bromine maintained between 5-10 ppm
      • Fail to ensure total bromine of public spa water maintained between 5 – 10 ppm [clause 7 (8) (c)]
      • Fail to ensure public spa water maintained so that bromine residual levels satisfy M.O.H. requirement [clause 7 (8) (g)]
  11. Routine

    0 infractions

Nearby inspected facilities