Valley View Regional Spray Park - Spray Park

3224 26 Street SE Calgary AB T2B 0L4 · Aquatic Facility

28 inspections

  1. Monitoring Inspection

    2 infractions

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • 1. The water sample collected on June 15, 2026 was not tested, because the date and time of collection was not provided in the requisition form.**June 18, 2026: a new sample was collected and submitted this week.
    • 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
      • **CORRECTED**1. The free chlorine measured 0.57ppm. Water chemistry adjusted during the inspection and measured 4.54ppm.
  2. Demand Inspection

    1 infraction

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • 1. The water sample collected on June 15, 2026 was not tested, because the date and time of collection was not provided in the requisition form.
  3. Demand Inspection

    2 infractions

    • 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
      • Collection date: Aug 26, 2025ID 25ES238E00814TC PositiveAdvised resampling
    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • The facility is closed for the season. Sample ID 25ES-240E00197Date Aug 28, 2025HPC 270CFU/100mLSample collection date: Aug 26, 2025ID 25ES238E00814HPC 670CFU/100mL
  4. Demand Inspection

    2 infractions

    • 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
      • Collection date: Aug 26, 2025ID 25ES238E00814TC PositiveAdvised resampling
    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • HPC 670CFU/100mL
  5. Risk Management Inspection

    0 infractions

  6. Demand Inspection

    2 infractions

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • *** The violation still exists***ID: 25ES-226E00166Sample date Aug 13, 2025HPC 700- The facility is still closed as the closure order was issued on Aug 15, 2025**The violation still exists**Sample collection date: Aug 12, 2025Sample ID: 25ES-225E00315HPC 700- Closure order was issued.HPC 760 CFUID 25ES-220E00028- Resampling advised.
    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • Resample rejected.-ID 25ES-224E00583Sample was rejected due ID label does not match with ID label with requisition form.Advised resampling.
  7. Demand Inspection

    2 infractions

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • **The violation still exists**Sample collection date: Aug 12, 2025Sample ID: 25ES-225E00315HPC 700- Closure order was issued.HPC 760 CFUID 25ES-220E00028- Resampling advised.
    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • Resample rejected.-ID 25ES-224E00583Sample was rejected due ID label does not match with ID label with requisition form.Advised resampling.
  8. Demand Inspection

    2 infractions

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • HPC 760 CFUID 25ES-220E00028Resampling advised.
    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • Resample rejected.-ID 25ES-224E00583Sample was rejected due ID label does not match with ID label with requisition form.Advised resampling.
  9. Demand Inspection

    1 infraction

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • HPC 760 CFUID 25ES-220E00028Resampling advised.
  10. Demand Inspection

    2 infractions

    • 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
      • ID 25ES-217E00230TC presentAdvised resample.
    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • HPC 580Resampling advised
  11. Demand Inspection

    0 infractions

  12. Demand Inspection

    2 infractions

    • 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
      • The water sample submitted on Jun 30, 2025, came back TC positive. Resampling advised.
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • The probe container and filter had murky water. Ensure this is cleaned to allow for accurate readings.
  13. Risk Management Inspection

    1 infraction

    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • The probe container and filter had murky water. Ensure this is cleaned to allow for accurate readings.
  14. Demand Inspection

    2 infractions

    • 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
      • TC was present in sample collected on Jun 17, 2025.- Advised resampling.
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • The probe container and filter had murky water. Ensure this is cleaned to allow for accurate readings.
  15. Monitoring Inspection

    1 infraction

    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • The probe container and filter had murky water. Ensure this is cleaned to allow for accurate readings.
  16. Demand Inspection

    2 infractions

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • Sample collected on August 23, 2024, showed Heterotrophic Plate Count (HPC) was enumerated to be 1680 CFU/mL.-Please treat according to AHS guidelines and submit another water sample, label as resample.
    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • The result of water sample collected on August 20, 2024, showed that Heterotrophic Plate Count (HPC) was enumerated at 3040 CFU/mL.-Please treat according to AHS guidelines and submit another water sample, label as resample.
  17. Demand Inspection

    1 infraction

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • The result of water sample collected on August 20, 2024, showed that Heterotrophic Plate Count (HPC) was enumerated at 3040 CFU/mL.-Please treat according to AHS guidelines and submit another water sample, label as resample.
  18. Risk Management Inspection

    0 infractions

  19. Risk Management Inspection

    0 infractions

  20. Demand Inspection

    1 infraction

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • The result of water sample collected on August 6, 2024, showed that Heterotrophic Plate Count (HPC) was enumerated at 1180 CFU/mL.-Please submit another water sample and label as resample.
  21. Demand Inspection

    1 infraction

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • Water sample collected on July 30, 2024, had HPC enumerated at 2370 CFU/mL.-Please treat in accordance with AHS guidelines before dumping the water in the tank, clean and sanitize the water tank after the water is dumped out, ensure adequate free available chlorine of above 2.0ppm is maintained in the water tank after the tank is refilled, and submit another water sample.
  22. Risk Management Inspection

    0 infractions

  23. Demand Inspection

    1 infraction

    • 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
      • Water sample collected on July 23, 2024, showed the presence of Total Coliforms per 100mL.-Please treat in accordance with AHS guidelines before dumping the water in the tank, clean and sanitize the water tank after the water is dumped out, ensure adequate free available chlorine of above 2.0ppm is maintained in the water tank after the tank is refilled, and submit another water sample.Please label the sample as resample.
  24. Monitoring Inspection

    0 infractions

  25. Demand Inspection

    3 infractions

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • The water sample collected on Jun 29, 2024 was dropped off at the lab on the weekend so it was not processed.
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • The pool recirculation system flow rate was exceeding the maximum rate of filtration.REQUIREMENT: Ensure the maximum rate of filtration for a high-rate sand filter in a recirculating water spray parks is not greater than 10 litres per second per square meter (15 US gallons per minute per square foot).
    • 10. Are general nuisance conditions, other than those noted in other violations, being prevented at this pool (Non-Critical)?
      • The top opening to the holding tank is constantly left open to monitor the water levels. There is no screen on the opening to prevent objects from accidentally entering into the holding tank, which may cause damage to the system.REQUIREMENT: If the holding tank top opening is to remain open, place a screen on the top to prevent any objects from entering into the tank.
  26. Demand Inspection

    3 infractions

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • The water sample collected on 2023-08-29, had HPC detected at 1560 CFU/mL. -Please super chlorinating the water and let it run through the lines for several hours, then adjust the water balance to operating parameters and submit another water sample labeled as resample.
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • The pool recirculation system flow rate was exceeding the maximum rate of filtration.REQUIREMENT: Ensure the maximum rate of filtration for a high-rate sand filter in a recirculating water spray parks is not greater than 10 litres per second per square meter (15 US gallons per minute per square foot).
    • 10. Are general nuisance conditions, other than those noted in other violations, being prevented at this pool (Non-Critical)?
      • The top opening to the holding tank is constantly left open to monitor the water levels. There is no screen on the opening to prevent objects from accidentally entering into the holding tank, which may cause damage to the system.REQUIREMENT: If the holding tank top opening is to remain open, place a screen on the top to prevent any objects from entering into the tank.
  27. Demand Inspection

    3 infractions

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • The water sample collected on July 28, 2023, had HPC detected at 700 CFU/mL. This is the second consecutive unsatisfactory water sample.REQUIREMENT: Review the water chemistry for any problems and balancing as needed. Consider super chlorinating the water and let it run through the lines for several hours, then drain the water – This may help to break down any biofilms that may have developed. Additionally, make sure the flow rate is being maintained between 15-74 USGPM.
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • The pool recirculation system flow rate was exceeding the maximum rate of filtration.REQUIREMENT: Ensure the maximum rate of filtration for a high-rate sand filter in a recirculating water spray parks is not greater than 10 litres per second per square meter (15 US gallons per minute per square foot).
    • 10. Are general nuisance conditions, other than those noted in other violations, being prevented at this pool (Non-Critical)?
      • The top opening to the holding tank is constantly left open to monitor the water levels. There is no screen on the opening to prevent objects from accidentally entering into the holding tank, which may cause damage to the system.REQUIREMENT: If the holding tank top opening is to remain open, place a screen on the top to prevent any objects from entering into the tank.
  28. Demand Inspection

    3 infractions

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • HPC was measured/isolated to be 950CFU/mL.-Please treat the water and resample.
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • The pool recirculation system flow rate was exceeding the maximum rate of filtration.REQUIREMENT: Ensure the maximum rate of filtration for a high-rate sand filter in a recirculating water spray parks is not greater than 10 litres per second per square meter (15 US gallons per minute per square foot).
    • 10. Are general nuisance conditions, other than those noted in other violations, being prevented at this pool (Non-Critical)?
      • The top opening to the holding tank is constantly left open to monitor the water levels. There is no screen on the opening to prevent objects from accidentally entering into the holding tank, which may cause damage to the system.REQUIREMENT: If the holding tank top opening is to remain open, place a screen on the top to prevent any objects from entering into the tank.