World Mark - Swimming Pool

91 Three Sisters Drive Canmore AB T1W 2X4 · Aquatic Facility

20 inspections

  1. Risk Management Inspection

    3 infractions

    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • The flow rate (98gpm) was exceeding the maximum flow allowed through the filter (74gpm). Maintain the flow rate between 66-74gpm.
    • 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
      • There is a large chip out of the bottom of the swimming pool that is rusting. Repair bottom of the pool.
    • 16. Are proper testing, monitoring, and other records being properly maintained?
      • Cyanuric acid is apparently being tested but the records are consistently indicating it is 0ppm, but when tested today got 31ppm. Was advised that possibly the reagents for testing need to be replaced. Replace reagents and not recommended to store them in the mechanical room which is a very hot area.
  2. Demand Inspection

    4 infractions

    • 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
      • The water sample taken on May 19, 2026 had total coliforms present. Treat water to remove contamination. Resample.
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • The flow rate (98gpm) was exceeding the maximum flow allowed through the filter (74gpm). Maintain the flow rate between 66-74gpm.
    • 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
      • There is a large chip out of the bottom of the swimming pool that is rusting. Repair bottom of the pool.
    • 16. Are proper testing, monitoring, and other records being properly maintained?
      • Cyanuric acid is apparently being tested but the records are consistently indicating it is 0ppm, but when tested today got 31ppm. Was advised that possibly the reagents for testing need to be replaced. Replace reagents and not recommended to store them in the mechanical room which is a very hot area.
  3. Demand Inspection

    5 infractions

    • 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
      • The water sample taken on April 16, 2026 had total coliforms present. Treat water to remove contamination. Resample.
    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • The water sample taken on April 16, 2026 had a heterotrophic plate count of 220cfu/ml. Treat water to remove contamination. Resample.
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • The flow rate (98gpm) was exceeding the maximum flow allowed through the filter (74gpm). Maintain the flow rate between 66-74gpm.
    • 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
      • There is a large chip out of the bottom of the swimming pool that is rusting. Repair bottom of the pool.
    • 16. Are proper testing, monitoring, and other records being properly maintained?
      • Cyanuric acid is apparently being tested but the records are consistently indicating it is 0ppm, but when tested today got 31ppm. Was advised that possibly the reagents for testing need to be replaced. Replace reagents and not recommended to store them in the mechanical room which is a very hot area.
  4. Risk Management Inspection

    3 infractions

    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • The flow rate (98gpm) was exceeding the maximum flow allowed through the filter (74gpm). Maintain the flow rate between 66-74gpm.
    • 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
      • There is a large chip out of the bottom of the swimming pool that is rusting. Repair bottom of the pool.
    • 16. Are proper testing, monitoring, and other records being properly maintained?
      • Cyanuric acid is apparently being tested but the records are consistently indicating it is 0ppm, but when tested today got 31ppm. Was advised that possibly the reagents for testing need to be replaced. Replace reagents and not recommended to store them in the mechanical room which is a very hot area.
  5. Demand Inspection

    4 infractions

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • Water sample taken on January 5, 2026 had a heterotrophic plate count of 140 cfu/ml. Treat water to remove contamination. Resample.
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • The flow rate (98gpm) was exceeding the maximum flow allowed through the filter (74gpm). Maintain the flow rate between 66-74gpm.
    • 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
      • There is a large chip out of the bottom of the swimming pool that is rusting. Repair bottom of the pool.
    • 16. Are proper testing, monitoring, and other records being properly maintained?
      • Cyanuric acid is apparently being tested but the records are consistently indicating it is 0ppm, but when tested today got 31ppm. Was advised that possibly the reagents for testing need to be replaced. Replace reagents and not recommended to store them in the mechanical room which is a very hot area.
  6. Demand Inspection

    4 infractions

    • 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
      • Water sample taken on Monday December 8th, 2025, had Total Coliforms present. Treat the swimming pool water to remove contamination and re-sample.
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • The flow rate (98gpm) was exceeding the maximum flow allowed through the filter (74gpm). Maintain the flow rate between 66-74gpm.
    • 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
      • There is a large chip out of the bottom of the swimming pool that is rusting. Repair bottom of the pool.
    • 16. Are proper testing, monitoring, and other records being properly maintained?
      • Cyanuric acid is apparently being tested but the records are consistently indicating it is 0ppm, but when tested today got 31ppm. Was advised that possibly the reagents for testing need to be replaced. Replace reagents and not recommended to store them in the mechanical room which is a very hot area.
  7. Demand Inspection

    4 infractions

    • 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
      • Water sample from Monday November 24th, 2025, had Total Coliforms present. - Operators were informed to treat and re-sample.
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • The flow rate (98gpm) was exceeding the maximum flow allowed through the filter (74gpm). Maintain the flow rate between 66-74gpm.
    • 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
      • There is a large chip out of the bottom of the swimming pool that is rusting. Repair bottom of the pool.
    • 16. Are proper testing, monitoring, and other records being properly maintained?
      • Cyanuric acid is apparently being tested but the records are consistently indicating it is 0ppm, but when tested today got 31ppm. Was advised that possibly the reagents for testing need to be replaced. Replace reagents and not recommended to store them in the mechanical room which is a very hot area.
  8. Risk Management Inspection

    5 infractions

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • Water sample from September 4, 2025, had a heterotrophic plate count of over 57,000 cfu/ml. Swimming pool water to be treated to remove contamination and resample taken.
    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • Water sample taken September 11, 2025 had a heterotrophic plate count of 2,000 cfu/ml. Treat water to remove contamination. Resample.
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • The flow rate (98gpm) was exceeding the maximum flow allowed through the filter (74gpm). Maintain the flow rate between 66-74gpm.
    • 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
      • There is a large chip out of the bottom of the swimming pool that is rusting. Repair bottom of the pool.
    • 16. Are proper testing, monitoring, and other records being properly maintained?
      • Cyanuric acid is apparently being tested but the records are consistently indicating it is 0ppm, but when tested today got 31ppm. Was advised that possibly the reagents for testing need to be replaced. Replace reagents and not recommended to store them in the mechanical room which is a very hot area.
  9. Demand Inspection

    3 infractions

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • Water sample taken September 11, 2025 had a heterotrophic plate count of 2,000 cfu/ml. Treat water to remove contamination. Resample.
    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • Water sample from September 4, 2025, had a heterotrophic plate count of over 57,000 cfu/ml. Swimming pool water to be treated to remove contamination and resample taken.
    • 16. Are proper testing, monitoring, and other records being properly maintained?
      • Cyanuric acid is being added to the swimming pool but levels are not being tested and recorded. To test and record level of cyanuric acid when added. Was advised the equipment needed to test CYA has been ordered.*Ongoing violation. Test cyanuric acid as part of pool chemistry checks and maintain log of readings to verify that concentration does not exceed 50mg/L. *
  10. Monitoring Inspection

    5 infractions

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • Water sample from September 4, 2025, had a heterotrophic plate count of over 57,000 cfu/ml. Swimming pool water to be treated to remove contamination and resample taken.
    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • Water sample taken September 11, 2025 had a heterotrophic plate count of 2,000 cfu/ml. Treat water to remove contamination. Resample.
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • The flow rate (80gpm) was exceeding the maximum flow allowed through the filter (74gpm). Maintain the flow rate at 66-74gpm.
    • 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
      • The skimmer baskets need cleaning. Also need to ensure the weirs are sitting properly for proper skimming action.There is also a large chip out of the bottom of the swimming pool that is rusting. Repair bottom of the pool.
    • 16. Are proper testing, monitoring, and other records being properly maintained?
      • Cyanuric acid is apparently being tested but the records are consistently indicating it is 0ppm, but when tested today got 31ppm. Ensure staff are properly testing the cyanuric acid level.
  11. Demand Inspection

    2 infractions

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • Water sample from September 4, 2025, had a heterotrophic plate count of over 57,000 cfu/ml. Swimming pool water to be treated to remove contamination and resample taken.
    • 16. Are proper testing, monitoring, and other records being properly maintained?
      • Cyanuric acid is being added to the swimming pool but levels are not being tested and recorded. To test and record level of cyanuric acid when added. Was advised the equipment needed to test CYA has been ordered.*Ongoing violation. Test cyanuric acid as part of pool chemistry checks and maintain log of readings to verify that concentration does not exceed 50mg/L. *
  12. Demand Inspection

    2 infractions

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • Water sample from August 7, 2025, had an HPC of 760 CFU/ml. Swimming pool water to be treated and resample taken.
    • 16. Are proper testing, monitoring, and other records being properly maintained?
      • Cyanuric acid is being added to the swimming pool but levels are not being tested and recorded. To test and record level of cyanuric acid when added. Was advised the equipment needed to test CYA has been ordered.*Ongoing violation. Test cyanuric acid as part of pool chemistry checks and maintain log of readings to verify that concentration does not exceed 50mg/L. *
  13. Demand Inspection

    2 infractions

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • Water sample from Thursday March 27th, 2025, had an HPC of 160 CFU/ml. Swimming pool water to be treated and resample taken.
    • 16. Are proper testing, monitoring, and other records being properly maintained?
      • Cyanuric acid is being added to the swimming pool but levels are not being tested and recorded. To test and record level of cyanuric acid when added. Was advised the equipment needed to test CYA has been ordered.*Ongoing violation. Test cyanuric acid as part of pool chemistry checks and maintain log of readings to verify that concentration does not exceed 50mg/L. *
  14. Demand Inspection

    2 infractions

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • Water sample from Thursday January 16th, 2025, had an HPC of 670 CFU/ml. - Operators were informed to treat and re-sample.
    • 16. Are proper testing, monitoring, and other records being properly maintained?
      • Cyanuric acid is being added to the swimming pool but levels are not being tested and recorded. To test and record level of cyanuric acid when added. Was advised the equipment needed to test CYA has been ordered.*Ongoing violation. Test cyanuric acid as part of pool chemistry checks and maintain log of readings to verify that concentration does not exceed 50mg/L. *
  15. Risk Management Inspection

    1 infraction

    • 16. Are proper testing, monitoring, and other records being properly maintained?
      • Cyanuric acid is being added to the swimming pool but levels are not being tested and recorded. To test and record level of cyanuric acid when added. Was advised the equipment needed to test CYA has been ordered.*Ongoing violation. Test cyanuric acid as part of pool chemistry checks and maintain log of readings to verify that concentration does not exceed 50mg/L. *
  16. Monitoring Inspection

    6 infractions

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • No water sample was submitted the week of November 11-14, 2024. A water sample is to be submitted weekly (unless the pool is closed for maintenance).
    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • The alkalinity was measured as 41ppm. To be kept at a minimum of 60ppm.
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • Both the skimmer and main drain lines were fully open. Are to maximize the flow through the skimmers.
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • The pH was measured as 6.85 but the controller was showing 7.42. Controller was calibrated during inspection.
    • 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
      • Some of the skimmer baskets were full of leaves. Please ensure the skimmer baskets are cleaned often.
    • 16. Are proper testing, monitoring, and other records being properly maintained?
      • Cyanuric acid is being added to the swimming pool but levels are not being tested and recorded. To test and record level of cyanuric acid when added.*Ongoing violation. Test cyanuric acid as part of pool chemistry checks and maintain log of readings to verify that concentration does not exceed 50mg/L. *
  17. Demand Inspection

    2 infractions

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • September 19, 2024 water sample had a plate count of 670cfu/ml. Treat water to remove contamination. Resample.
    • 16. Are proper testing, monitoring, and other records being properly maintained?
      • Cyanuric acid is being added to the swimming pool but levels are not being tested and recorded. To test and record level of cyanuric acid when added.*Ongoing violation. Test cyanuric acid as part of pool chemistry checks and maintain log of readings to verify that concentration does not exceed 50mg/L. *
  18. Demand Inspection

    3 infractions

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • Water sample taken this week (Aug. 29th) was not tested as the requisition form stated the sample was taken on Oct. 29th) and the identification number from the form was not put on the sample bottle. Resample to be submitted.
    • 13. Are the general safety devices and physical conditions in this pool providing a safe environment (Non-Critical)?
      • The water clarity and condition of the main drains were not being recorded daily. Ensure water clarity is checked at least once per day, along with a visual inspection of main drain covers for any damage or defects.
    • 16. Are proper testing, monitoring, and other records being properly maintained?
      • Cyanuric acid is being added to the swimming pool but levels are not being tested and recorded. To test and record level of cyanuric acid when added.*Ongoing violation. Test cyanuric acid as part of pool chemistry checks and maintain log of readings to verify that concentration does not exceed 50mg/L. *
  19. Risk Management Inspection

    2 infractions

    • 13. Are the general safety devices and physical conditions in this pool providing a safe environment (Non-Critical)?
      • The water clarity and condition of the main drains were not being recorded daily. Ensure water clarity is checked at least once per day, along with a visual inspection of main drain covers for any damage or defects.
    • 16. Are proper testing, monitoring, and other records being properly maintained?
      • Cyanuric acid is being added to the swimming pool but levels are not being tested and recorded. To test and record level of cyanuric acid when added.*Ongoing violation. Test cyanuric acid as part of pool chemistry checks and maintain log of readings to verify that concentration does not exceed 50mg/L. *
  20. Demand Inspection

    4 infractions

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • HPC count was 690 cfu. Treat and re-sample.
    • 13. Are the general safety devices and physical conditions in this pool providing a safe environment (Non-Critical)?
      • The water clarity and condition of the main drains were not being recorded daily. Ensure water clarity is checked at least once per day, along with a visual inspection of main drain covers for any damage or defects.
    • 16. Are proper testing, monitoring, and other records being properly maintained?
      • Cyanuric acid is being added to the swimming pool but levels are not being tested and recorded. To test and record level of cyanuric acid when added.*Ongoing violation. Test cyanuric acid as part of pool chemistry checks and maintain log of readings to verify that concentration does not exceed 50mg/L. *
    • 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
      • The anti-entrapment plan for this pool basin was incomplete, as it did not specify the model or expiration date of the main drain covers. Complete anti-entrapment plan and send it to the undersigned health inspector for review.