1100 8 Avenue SW - Swimming Pool
1100 8 Avenue SW Calgary AB T2P 3T9 · Aquatic Facility
10 inspections
- Risk Management Inspection
0 infractions
- Demand Inspection
1 infraction
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- The water sample test result of the water sample collected on May 9, 2025, had a presence of Total Coliforms. Another water sample must be submitted immediately for another bacteriological water analysis.
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Risk Management Inspection
0 infractions
- Demand Inspection
1 infraction
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Water sample collected on February 19th, 2025, came back unsatisfactory as Total Coliforms were present in the sample.Please treat the swimming pool and re-sample immediately.
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Demand Inspection
2 infractions
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Water sample taken Nov 20, 2024 - total coliforms present.-Treat and resample
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Water sample taken Nov 20, 2024 - HPC 110 CFU/mL.-Resample
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Demand Inspection
1 infraction
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Water sample taken Oct 29, 2024 - total coliforms present.-Treat and resample
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Monitoring Inspection
0 infractions
- Risk Management Inspection
3 infractions
- 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
- pH measured at 8.17-pH to be maintained between 6.8 to 7.6
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Automated reader for chlorine showed pH 7.2. Inspector and operator's test kits both showed 8.0+.-Ensure automated readers are properly adjusted. Operator may need to clean, recalibrate, or replace probes
- 10. Are general nuisance conditions, other than those noted in other violations, being prevented at this pool (Non-Critical)?
- A moderate amount of white powder was observed at the bottom of the pool. Some of it was clumped together.-If chemicals are added, ensure they are dispersed and fully dissolved
- 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
- Demand Inspection
0 infractions
- Risk Management Inspection
1 infraction
- 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
- Update Aug 16, 2023Patron Education and WQIRP require additional information.------------WRITTEN POLICIES AND PLANS ARE NOT AVAILABLE UPON REQUEST. LOCATE OR DEVELOP PLANS AS PER THE POOL STANDARDS SECTION 9, 10, 11, 12 AND 13.
- 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?