1100 8 Avenue SW - Whirlpool

1100 8 Avenue SW Calgary AB T2P 3T9 · Aquatic Facility

1 inspection

  1. Demand Inspection

    3 infractions

    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • TOTAL ALKALINITY MEASURED 19 mg/L. MAINTAIN TOTAL ALKALINITY BETWEEN 60 - 180 mg/L.
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • TURNOVER FOR THE WHIRLPOOL EXCEEDS 20 MINUTES. MAINTAIN THE SYSTEM SO THAT 100% OF THE WATER VOLUME PASSES THROUGH THE TREATMENT SYSTEM WITHIN 20 MINUTES.
    • 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
      • WRITTEN POLICIES AND PLANS ARE NOT AVAILABLE UPON REQUEST. LOCATE OR DEVELOP PLANS AS PER THE POOL STANDARDS SECTION 9, 10, 11, 12 AND 13.