14810 51 Avenue NW - Whirlpool

14810 51 Avenue NW Edmonton AB T6H 5G5 · Aquatic Facility

9 inspections

  1. Demand Inspection

    0 infractions

  2. Risk Management Inspection

    0 infractions

  3. Monitoring Inspection

    2 infractions

    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • Total alkalinity was 38 ppm. Please ensure that it is maintained between 60 and 180 ppm.
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • There was a discrepancy between the manual pH reading 6.69 and the automated controller reading pH 7.2. Please address.
  4. Risk Management Inspection

    1 infraction

    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • With flow rate 65 gpm, the rate of filtration was 13.27 gpm/ft2. To ensure that the filtration rate does not exceed maximum allowed 12.5 gpm/ft2, the flow rate should not exceed 61 gpm. Note: according to the provided information, filter flow rate should be 50 gpm (see notes).
  5. Demand Inspection

    2 infractions

    • 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
      • the sample 24EN-250E00370 submitted on September 6, 2024, was unsatisfactory: Total coliforms present.
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • With flow rate 65 gpm, the rate of filtration was 13.27 gpm/ft2. To ensure that the filtration rate does not exceed maximum allowed 12.5 gpm/ft2, the flow rate should not exceed 61 gpm. Note: according to the provided information, filter flow rate should be 50 gpm (see notes).
  6. Risk Management Inspection

    1 infraction

    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • With flow rate 65 gpm, the rate of filtration was 13.27 gpm/ft2. To ensure that the filtration rate does not exceed maximum allowed 12.5 gpm/ft2, the flow rate should not exceed 61 gpm. Note: according to the provided information, filter flow rate should be 50 gpm (see notes).
  7. Demand Inspection

    2 infractions

    • 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
      • The microbiological water sample submitted on 9 Aug 2024 was unsatisfactory: Pseudomonas aeruginosa isolated, Take all necessary action to ensure microbiologically safe water. Submit a new microbiological water sample at your earliest convenience once the water chemistry is balanced.
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • With flow rate 65 gpm, the rate of filtration was 13.27 gpm/ft2. To ensure that the filtration rate does not exceed maximum allowed 12.5 gpm/ft2, the flow rate should not exceed 61 gpm. Note: according to the provided information, filter flow rate should be 50 gpm (see notes).
  8. Risk Management Inspection

    1 infraction

    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • With flow rate 65 gpm, the rate of filtration was 13.27 gpm/ft2. To ensure that the filtration rate does not exceed maximum allowed 12.5 gpm/ft2, the flow rate should not exceed 61 gpm. Note: according to the provided information, filter flow rate should be 50 gpm (see notes).
  9. Monitoring Inspection

    4 infractions

    • 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
      • 1. Free Chlorine was 0.38 ppm (corrected to 2.8 ppm during the inspection). Ensure that free chlorine is maintained above 2 ppm.2. The pH was 6.5 (corrected to 6.91 during the inspection). Ensure that pH is maintained between 6.8 and 7.6.
    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • Total Alkalinity was 10 ppm (corrected to 58 ppm during the inspection). Ensure that total alkalinity is maintained between 60 and 180 ppm.
    • 16. Are proper testing, monitoring, and other records being properly maintained?
      • There were no records of testing the secondary layer of anti-entrapment protection device available. The testing was conducted during the inspection. Ensure that the device is tested as per manufacturer's instructions, and the results of testing are recorded.
    • 18. Have plans for construction, renovations or alteration for the pool been submitted for written approval?
      • * Rate of filtration for the filtration system could not be determined - a new filter was installed, and no information regarding a filtration area was provided.* A new disinfection system was installed (Pulsar Infinity pack system) but no information regarding the alteration was submitted to AHS.