Baymont Inn & Suites - Swimming Pool
4311 49 Avenue Red Deer AB T4N 5Y7 · Aquatic Facility
32 inspections
- Risk Management Inspection
0 infractions
- Demand Inspection
1 infraction
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Unsatisfactory water sample result:Total coliforms - ABSENTHPC - 200 cfu/100mL *unsatisfactorySample collected June 10, 2026 by Helbert.The pool was closed for the day (Monday, June 15, 2026) for routine weekly cleaning. The facility has experienced maximum bather loads for more than three consecutive weeks. Pool Operator Helbert will ensure the free chlorine concentration is raised to 10 ppm and maintained for one full turnover period, prior rebalancing the pool and taking another sample and reopening the pool.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Risk Management Inspection
0 infractions
- Risk Management Inspection
1 infraction
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Unsatisfactory water sample result:Total coliforms – Present *unsatisfactoryHPC < 10 cfu/100mL ---Sample collected March 25, 2026 by Helbert.Pool operators will complete cleaning of the pool and perform shocking and backwashing on Monday, March 30, prior to resampling on Wednesday, April 1.
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Risk Management Inspection
0 infractions
- Risk Management Inspection
1 infraction
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Unsatisfactory water sample result:Total coliforms - ABSENTHPC - 160 cfu/100mL *unsatisfactorySample collected March 4 2026 by Helbert.---Sample was taken when the hotel was busy during a hockey tournament.The operator has since completed cleaning and shock treatment of the pool and will resample.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Monitoring Inspection
0 infractions
- Risk Management Inspection
0 infractions
- Demand Inspection
1 infraction
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Unsatisfactory bacteriological water sample taken June 18:Total Coliforms - PRESENTContacted operator to shock chlorinate.
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Monitoring Inspection
0 infractions
- Risk Management Inspection
0 infractions
- Demand Inspection
1 infraction
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Unsatisfactory water sample result:Total coliforms - ABSENTHPC - 3110 cfu/100mL *unsatisfactorySample collected Feb 26, 2025.ACTION:Please shock chlorinate the pool using the steps outlined in the document below:https://www.albertahealthservices.ca/assets/wf/eph/wf-eph-interpret-microbiological-sample-results-pools.pdfThis doucment was emailed to operator as well.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Monitoring Inspection
0 infractions
- Risk Management Inspection
0 infractions
- Demand Inspection
1 infraction
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Unsatisfactory water sample received.Total coliforms - ABSENTHPC - 140 CFU/100mLSample collected Oct 9.Please shock chlorinate the pool, return to normal operational chemistry, and submit a new sample.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Risk Management Inspection
0 infractions
- Demand Inspection
1 infraction
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Unsatisfactory water sample received.Total coliforms - ABSENTHPC - 230 CFU/100mLSample collected Sept 18.Please shock the pool and submit a resample after returning to normal operational chemistry.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Risk Management Inspection
0 infractions
- Demand Inspection
1 infraction
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Unsatisfactory water sample received.Total coliforms - ABSENTHPC - 2,200 CFU/100mLSample collected on Aug 21.ACTION: Please shock chlorinate the pool and resample after returning to normal operating chemistry.https://www.albertahealthservices.ca/assets/wf/eph/wf-eph-interpret-microbiological-sample-results-pools.pdf
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Risk Management Inspection
0 infractions
- Risk Management Inspection
1 infraction
- 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
- June 17, 2024The operator mentioned during an email on June 11, 2024, that anti-entrapment information was already sent to inspector Nicole, and the facility is waiting for an assessment from the inspector.  March 21, 2024Additional information is required to complete anti-entrapment review.Please provide requested information.
- 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
- Risk Management Inspection
2 infractions
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- The bacteriological water sample collected on June 5, 2024, has a heterotrophic plate count of 240 CFU/mL. Please ensure that the pool water is resampled.
- 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
- Additional information is required to complete anti-entrapment review.Please provide requested information.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Risk Management Inspection
1 infraction
- 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
- Additional information is required to complete anti-entrapment review.Please provide requested information.
- 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
- Demand Inspection
2 infractions
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- HPC > 1020 CFU/mL
- 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
- Additional information is required to complete anti-entrapment review.Please provide requested information.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Risk Management Inspection
1 infraction
- 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
- Additional information is required to complete anti-entrapment review.Please provide requested information.
- 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
- Demand Inspection
2 infractions
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Water sample result for sample collected / submitted on May 01 2024 with HPC 3150.T C Absent I called Helbert and informed him of the result. Helbert stated that they were very busy last weekend and the fc fell below 1 ppm.A shock treatment was done with a new product.The fc was then raised to 3 ppm.This morning the f c was at 1.19 ppm.Helbert will shock the pool again and also submit another sample. Monday is maintenance day so the pool is closed for the day.
- 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
- Additional information is required to complete anti-entrapment review.Please provide requested information.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Risk Management Inspection
1 infraction
- 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
- Additional information is required to complete anti-entrapment review.Please provide requested information.
- 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
- Demand Inspection
1 infraction
- 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
- Missing information/supporting documents were not attached to the anti-entrapment plan; therefore, a complete review could not occur.Please provide requested information.
- 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
- Risk Management Inspection
0 infractions
- Monitoring Inspection
2 infractions
- 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
- The free available chlorine level were measured at 0.38/0.47/0.3 ppm with pH at 7.5 and ORP at 381mV.- Ensure the FAC is maintain 1ppm or higher, OR higher than 0.5 ppm with ORP higher than 700mV, OR higher than 0.3ppm with pH less than 7.3 and ORP higher than 770mV
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- The total alkalinity level were measured at 188ppm and over range. - Ensure TA level is between 60 - 180ppm
- 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
- Risk Management Inspection
0 infractions
- Risk Management Inspection
1 infraction
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- TC present in the weekly sample July 19, 2023
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?