Best Western Airport Inn - Swimming Pool
1947 18 Avenue NE Calgary AB T2E 7T8 · Aquatic Facility
31 inspections
- Demand Inspection
1 infraction
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- The water sample collected on June 4, 2026, was unsatisfactory with an HPC of 2,360 CFU/mL.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Risk Management Inspection
0 infractions
- Demand Inspection
1 infraction
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- The water sample collected on May 21, 2026, was unsatisfactory with an HPC of 1,690 CFU/mL.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Risk Management Inspection
0 infractions
- Demand Inspection
1 infraction
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- The water sample collected on April 2, 2026, was not tested because it was a non-urgent sample received during the holiday without approval from AHS/ProvLab.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Risk Management Inspection
0 infractions
- Demand Inspection
1 infraction
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- The water sample collected on February 26, 2026, was unsatisfactory with an HPC of 450 CFU/mL.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Demand Inspection
1 infraction
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- The water sample collected on December 26, 2025, was not tested because the non-urgent sample was received during the weekend/holiday without approval.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Risk Management Inspection
0 infractions
- Demand Inspection
1 infraction
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- The water sample collected on September 25, 2025, was unsatisfactory with an HPC of 510 CFU/mL.**OUTSTANDING (2025-10-02). The water sample submitted on October 2, 2025, was rejected because the date of collection was not indicated on the requisition form.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Demand Inspection
1 infraction
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- The water sample collected on September 25, 2025, was unsatisfactory with an HPC of 510 CFU/mL.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Risk Management Inspection
0 infractions
- Risk Management Inspection
0 infractions
- Demand Inspection
1 infraction
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Water sample collected on May 29, 2025, had a HPC count = 800 CFU/ml, which is higher than the required limit. **Please begin treatment for the pool immediately. **Submit a re-sample after the treatment is completed and water chemistry is re-balanced
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Demand Inspection
1 infraction
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- **UNSATISFACTORY WATER SAMPLE TEST RESULT**1. The water sample collected on May 8, 2025, was unsatisfactory with an HPC of 3120 CFU/mL. Another water sample must be submitted immediately.2. The water sample collected on May 15, 2025, was unsatisfactory with an HPC of 1,390 CFU/mL. Another water sample must be submitted immediately. The operator mentioned that they had a new staff that were not yet properly trained, and that their chlorine container was discovered to be empty for the past two weeks. The inspector informed the operator that the chlorine level, and all other chemical parameters in the pool, must be maintained at proper concentrations.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Demand Inspection
1 infraction
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- **UNSATISFACTORY WATER SAMPLE TEST RESULT**1. The water sample collected on May 8, 2025, was unsatisfactory with an HPC of 3120 CFU/mL. Another water sample must be submitted immediately.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Risk Management Inspection
0 infractions
- Demand Inspection
1 infraction
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- The water sample collected on March 26, 2025, came back with an HPC of 3,720 CFU/mL.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Risk Management Inspection
0 infractions
- Demand Inspection
2 infractions
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- The pool water sample result submitted on September 4. 2024, had Heterotrophic Plate Count (HPC) enumerated at 160CFU/mL.-Please resample and ensure proper sampling protocol is maintained, label as resample.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Water sample submitted on September 9, 2024, had Heterotrophic Plate Count (HPC) enumerated at 1950 CFU/mL.-Treat the pool in accordance with the AHS guidelines and submit another water sample after the treatment, label as resample. Please be aware that a consecutive HPC unsatisfactory water sample will lead to the pool closure.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Demand Inspection
1 infraction
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- The pool water sample result submitted on September 4. 2024, had Heterotrophic Plate Count (HPC) enumerated at 160CFU/mL.-Please resample and ensure proper sampling protocol is maintained, label as resample.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Risk Management Inspection
0 infractions
- Monitoring Inspection
3 infractions
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- The pool combined chlorine was not maintained as low as possible, it measured at 1.26 milligram per litre.-Please reduce and maintain the combined chlorine at the lowest possible level.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- 1. The automatic chemical controller for the pool was not in good working condition, the automatic controller was not feeding chemicals into the pool. Operator manually dozing chemicals into the pool.-Please replace or repair the automatic controller and ensure it is in good working condition.2. The flow meter was not working properly.-Please repair or replace the flow meter and ensure it is in proper working condition
- 12. Are the general safety devices and physical conditions in this pool providing a safe environment (Critical)?
- The swimming pool water was cloudy.-Please treat or repair the whirlpool system, eliminate any possible source of contamination and to restore clarity.
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- Demand Inspection
1 infraction
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- The water sample collected on April 25th, 2024, had an HPC count of 2720 CFU/mL detected in the sample.REQUIREMENT: Review the water chemistry and treat the water as required. Collect and send in a re-sample once treatments are complete and the water chemistry is rebalanced.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Demand Inspection
2 infractions
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Pool water sample collected on March 14, 2024, showed that HPC was enumerated at 320 CFU/mL.-Please resample and follow proper sample procedure to ensure sample is not contaminated.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Pool water sample collected on March 18, 2024, showed that HPC was enumerated at 160 CFU/mL.-Please treat the pool in accordance with AHS unsatisfactory pool water sample and resample.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Demand Inspection
1 infraction
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Pool water sample collected on March 14, 2024, showed that HPC was enumerated at 320 CFU/mL.-Please resample and follow proper sample procedure to ensure sample is not contaminated.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Demand Inspection
1 infraction
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Sample was not processed because date and time of collection not provided.-Please resample and ensure proper sampling protocol is followed.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Risk Management Inspection
1 infraction
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Pool water HPC was enumerated at above 5700CFU/mL.-Please treat the pool water in accordance with AHS unsatisfactory water sample and retake the water sample.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Demand Inspection
2 infractions
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Pool water HPC was enumerated at above 5700CFU/mL.-Please treat the pool water in accordance with AHS unsatisfactory water sample and retake the water sample.
- 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
- Anti-entrapment compliance plan was incomplete.-Please complete the pool anti-entrapment compliance risk assessment and send the complete plan to the district inspector to ensure compliance.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Risk Management Inspection
1 infraction
- 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
- Anti-entrapment compliance plan was incomplete.-Please complete the pool anti-entrapment compliance risk assessment and send the complete plan to the district inspector to ensure compliance.
- 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
- Initial Inspection
5 infractions
- 04. Is the chemical quality of the water in this pool satisfactory (Critical)?
- 1. PH manual measurement was at 6.4.Please adjust the pool water balance and ensure the pool pH is maintained between 6.8 and 7.6 as required in the Pool Standards.2. There was no disinfectant in the pool water at the time of the inspection, the free available chlorine was measured 0.00ppm.Please ensure pool's free available chlorine is maintained at or above 1.0 milligram per litre to ensure continuous pool disinfection and prevent spread of infection.
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- The pool total alkalinity was measured at 35ppm during the inspection.-Please maintain the total alkalinity of the pool between 60 -180 milligrams per litre to ensure proper water chemical balance.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- The automatic chemical feeding injector was not in good working condition.Please repair or replace the chemical injector and ensure it is in good working condition.
- 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
- The pool flow meter was not in good working condition.Please ensure it is repaired or replaced.
- 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
- 1. Anti-entrapment compliance plan was incomplete.-Please complete the pool anti-entrapment compliance risk assessment and send the complete plan to the district inspector to ensure compliance.2. There was no water quality incident response plans for fecal, vomit or blood incidents onsite-Please development these water incident plans.Also, develop response plans for unsatisfactory bacteriological water sample such as presence of Total Coliform and Heterotrophic Plate count that is greater than the requirement/Standards in the pool.3. There was no general sanitation plan for the pool areas onsite.-Develop and ensure this plan is available onsite.
- 04. Is the chemical quality of the water in this pool satisfactory (Critical)?