Booster Juice Recreation Centre in Terwillegar - Whirlpool
2051 Leger Road NW Edmonton AB T6R 0R9 · Aquatic Facility
Inspection summary
Booster Juice Recreation Centre in Terwillegar - Whirlpool has been inspected 11 times by Alberta Health Services (Environmental Public Health) since January 24, 2024. The most recent inspection, on February 25, 2026, recorded 4 infractions.
None of the 11 inspections on record were free of infractions. In the past 12 months there were 6 inspections with 29 infractions recorded. The higher-risk findings here relate to: Pool and spa water quality and Chemicals and toxic substances.
Recent inspections have recorded more infractions than earlier ones, so it is worth reading the latest reports closely.
What these findings mean
Health authorities word their findings differently, so we group them by what they mean for the people using the facility. Higher-risk findings are the ones that could directly cause illness or injury, such as water that is not properly treated.
Pool and spa water qualityHigher risk
For pools, spas and splash pads, inspectors test disinfectant levels, pH and water clarity, and check safety equipment. Water that is not properly treated can spread skin, ear and stomach infections.
Recorded 41 times across 11 separate inspections, most recently on February 25, 2026. For example:
Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
Chemicals and toxic substancesHigher risk
Pool chemicals such as chlorine and acid must be labelled, stored apart from each other and handled safely. Mixing them by mistake can release toxic gas, so storage and handling problems are treated seriously.
Recorded once on February 25, 2026. For example:
Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
Food safety training and certificationLower risk
Many jurisdictions require trained pool operators and certified lifeguards. These findings mean required training, certification or staffing records were missing at the time of inspection.
Recorded once on February 25, 2026. For example:
Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
About this data
These results come from Alberta Health Services (Environmental Public Health), which inspects food premises and other public facilities in this area. We republish the authority's public disclosure data and refresh it regularly; the official record is the final word.
11 inspections
- Monitoring Inspection
4 infractions
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- Combined chlorine residual was 1.49 ppm. Ensure that the combined chlorine residual is maintained as low as possible, and below 1 ppm.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Rate of filtration for the filtration system was 13.4 gpm/sq ft based on a filtration area of 67.6 sq ft - noted to be 18.65 gpm/ft2 on February 27, 2017.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Rate of filtration for the filtration system was 16.68 gpm/sq ft based on a filtration area of 33.8 sq ft (one out of two filters was not operational). If both filters were in operation, the filtration rate would be 8.34 gpm/ft2. Updated on January 24, 2024: Rate of filtration for the filtration system was 18.05 gpm/sq ft based on a filtration area of 33.8 sq ft (one out of two filters was not operational) (flow rate 612 gpm). If both filters were in operation, the filtration rate would be 9.02 gpm/ft2. Update on February 6, 2025:Rate of filtration for the filtration system was 17.22 gpm/sq ft based on a filtration area of 33.8 sq ft (one out of two filters was not operational) and flow rate 582 gpm. If both filters were in operation, the filtration rate would be 8.6 gpm/ft2. Ensure that the rate of filtration is 12.5 gpm/sq ft or less. Updated on February 25, 2026: Rate of filtration for the filtration system was 18.11 gpm/sq ft based on a filtration area of 33.8 sq ft (one out of two filters was not operational) and flow rate 612 gpm. If both filters were in operation, the filtration rate would be 9.05 gpm/ft2. Ensure that the rate of filtration is 12.5 gpm/sq ft or less.
- 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
- The current Anti-Entrapment Compliance Plan did not include the information for the jet pump, which resulted in incorrect calculation of the combined flow rate through the main drains. Please update.
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- Risk Management Inspection
4 infractions
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Rate of filtration for the filtration system was 13.4 gpm/sq ft based on a filtration area of 67.6 sq ft - noted to be 18.65 gpm/ft2 on February 27, 2017.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Rate of filtration for the filtration system was 16.68 gpm/sq ft based on a filtration area of 33.8 sq ft (one out of two filters was not operational). If both filters were in operation, the filtration rate would be 8.34 gpm/ft2. Updated on January 24, 2024: Rate of filtration for the filtration system was 18.05 gpm/sq ft based on a filtration area of 33.8 sq ft (one out of two filters was not operational) (flow rate 612 gpm). If both filters were in operation, the filtration rate would be 9.02 gpm/ft2. Update on February 6, 2025:Rate of filtration for the filtration system was 17.22 gpm/sq ft based on a filtration area of 33.8 sq ft (one out of two filters was not operational) and flow rate 582 gpm. If both filters were in operation, the filtration rate would be 8.6 gpm/ft2. Ensure that the rate of filtration is 12.5 gpm/sq ft or less.
- 10. Are general nuisance conditions, other than those noted in other violations, being prevented at this pool (Non-Critical)?
- Cleaning inside skimmers was required.
- 12. Are the general safety devices and physical conditions in this pool providing a safe environment (Critical)?
- The water clarity was reduced but a main drain was still visible. Please improve the water clarity.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Demand Inspection
6 infractions
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- the sample 26EN-034E00795 submitted on February 3, 2026, was unsatisfactory: HPC 280.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- the sample 26EN-037E00073 submitted on February 6, 2026, was unsatisfactory: HPC 390.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Rate of filtration for the filtration system was 13.4 gpm/sq ft based on a filtration area of 67.6 sq ft - noted to be 18.65 gpm/ft2 on February 27, 2017.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Rate of filtration for the filtration system was 16.68 gpm/sq ft based on a filtration area of 33.8 sq ft (one out of two filters was not operational). If both filters were in operation, the filtration rate would be 8.34 gpm/ft2. Updated on January 24, 2024: Rate of filtration for the filtration system was 18.05 gpm/sq ft based on a filtration area of 33.8 sq ft (one out of two filters was not operational) (flow rate 612 gpm). If both filters were in operation, the filtration rate would be 9.02 gpm/ft2. Update on February 6, 2025:Rate of filtration for the filtration system was 17.22 gpm/sq ft based on a filtration area of 33.8 sq ft (one out of two filters was not operational) and flow rate 582 gpm. If both filters were in operation, the filtration rate would be 8.6 gpm/ft2. Ensure that the rate of filtration is 12.5 gpm/sq ft or less.
- 10. Are general nuisance conditions, other than those noted in other violations, being prevented at this pool (Non-Critical)?
- Cleaning inside skimmers was required.
- 12. Are the general safety devices and physical conditions in this pool providing a safe environment (Critical)?
- The water clarity was reduced but a main drain was still visible. Please improve the water clarity.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Demand Inspection
5 infractions
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- the sample 26EN-034E00795 submitted on February 3, 2026, was unsatisfactory: HPC 280.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Rate of filtration for the filtration system was 13.4 gpm/sq ft based on a filtration area of 67.6 sq ft - noted to be 18.65 gpm/ft2 on February 27, 2017.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Rate of filtration for the filtration system was 16.68 gpm/sq ft based on a filtration area of 33.8 sq ft (one out of two filters was not operational). If both filters were in operation, the filtration rate would be 8.34 gpm/ft2. Updated on January 24, 2024: Rate of filtration for the filtration system was 18.05 gpm/sq ft based on a filtration area of 33.8 sq ft (one out of two filters was not operational) (flow rate 612 gpm). If both filters were in operation, the filtration rate would be 9.02 gpm/ft2. Update on February 6, 2025:Rate of filtration for the filtration system was 17.22 gpm/sq ft based on a filtration area of 33.8 sq ft (one out of two filters was not operational) and flow rate 582 gpm. If both filters were in operation, the filtration rate would be 8.6 gpm/ft2. Ensure that the rate of filtration is 12.5 gpm/sq ft or less.
- 10. Are general nuisance conditions, other than those noted in other violations, being prevented at this pool (Non-Critical)?
- Cleaning inside skimmers was required.
- 12. Are the general safety devices and physical conditions in this pool providing a safe environment (Critical)?
- The water clarity was reduced but a main drain was still visible. Please improve the water clarity.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Risk Management Inspection
4 infractions
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Rate of filtration for the filtration system was 13.4 gpm/sq ft based on a filtration area of 67.6 sq ft - noted to be 18.65 gpm/ft2 on February 27, 2017.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Rate of filtration for the filtration system was 16.68 gpm/sq ft based on a filtration area of 33.8 sq ft (one out of two filters was not operational). If both filters were in operation, the filtration rate would be 8.34 gpm/ft2. Updated on January 24, 2024: Rate of filtration for the filtration system was 18.05 gpm/sq ft based on a filtration area of 33.8 sq ft (one out of two filters was not operational) (flow rate 612 gpm). If both filters were in operation, the filtration rate would be 9.02 gpm/ft2. Update on February 6, 2025:Rate of filtration for the filtration system was 17.22 gpm/sq ft based on a filtration area of 33.8 sq ft (one out of two filters was not operational) and flow rate 582 gpm. If both filters were in operation, the filtration rate would be 8.6 gpm/ft2. Ensure that the rate of filtration is 12.5 gpm/sq ft or less.
- 10. Are general nuisance conditions, other than those noted in other violations, being prevented at this pool (Non-Critical)?
- Cleaning inside skimmers was required.
- 12. Are the general safety devices and physical conditions in this pool providing a safe environment (Critical)?
- The water clarity was reduced but a main drain was still visible. Please improve the water clarity.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Demand Inspection
6 infractions
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- the microbiological water sample 26EN-027E00671 submitted on January 27, 2026, was unsatisfactory: Total coliforms were present, Pseudomonas aeruginosa was isolated, and HPC was 1560.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- the microbiological water sample 26EN-027E00671 submitted on January 27, 2026, was unsatisfactory: Total coliforms were present, Pseudomonas aeruginosa was isolated, and HPC was 1560.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Rate of filtration for the filtration system was 13.4 gpm/sq ft based on a filtration area of 67.6 sq ft - noted to be 18.65 gpm/ft2 on February 27, 2017.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Rate of filtration for the filtration system was 16.68 gpm/sq ft based on a filtration area of 33.8 sq ft (one out of two filters was not operational). If both filters were in operation, the filtration rate would be 8.34 gpm/ft2. Updated on January 24, 2024: Rate of filtration for the filtration system was 18.05 gpm/sq ft based on a filtration area of 33.8 sq ft (one out of two filters was not operational) (flow rate 612 gpm). If both filters were in operation, the filtration rate would be 9.02 gpm/ft2. Update on February 6, 2025:Rate of filtration for the filtration system was 17.22 gpm/sq ft based on a filtration area of 33.8 sq ft (one out of two filters was not operational) and flow rate 582 gpm. If both filters were in operation, the filtration rate would be 8.6 gpm/ft2. Ensure that the rate of filtration is 12.5 gpm/sq ft or less.
- 10. Are general nuisance conditions, other than those noted in other violations, being prevented at this pool (Non-Critical)?
- Cleaning inside skimmers was required.
- 12. Are the general safety devices and physical conditions in this pool providing a safe environment (Critical)?
- The water clarity was reduced but a main drain was still visible. Please improve the water clarity.
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Monitoring Inspection
4 infractions
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Rate of filtration for the filtration system was 13.4 gpm/sq ft based on a filtration area of 67.6 sq ft - noted to be 18.65 gpm/ft2 on February 27, 2017.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Rate of filtration for the filtration system was 16.68 gpm/sq ft based on a filtration area of 33.8 sq ft (one out of two filters was not operational). If both filters were in operation, the filtration rate would be 8.34 gpm/ft2. Updated on January 24, 2024: Rate of filtration for the filtration system was 18.05 gpm/sq ft based on a filtration area of 33.8 sq ft (one out of two filters was not operational) (flow rate 612 gpm). If both filters were in operation, the filtration rate would be 9.02 gpm/ft2. Update on February 6, 2025:Rate of filtration for the filtration system was 17.22 gpm/sq ft based on a filtration area of 33.8 sq ft (one out of two filters was not operational) and flow rate 582 gpm. If both filters were in operation, the filtration rate would be 8.6 gpm/ft2. Ensure that the rate of filtration is 12.5 gpm/sq ft or less.
- 10. Are general nuisance conditions, other than those noted in other violations, being prevented at this pool (Non-Critical)?
- Cleaning inside skimmers was required.
- 12. Are the general safety devices and physical conditions in this pool providing a safe environment (Critical)?
- The water clarity was reduced but a main drain was still visible. Please improve the water clarity.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Risk Management Inspection
2 infractions
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Rate of filtration for the filtration system was 13.4 gpm/sq ft based on a filtration area of 67.6 sq ft - noted to be 18.65 gpm/ft2 on February 27, 2017.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Rate of filtration for the filtration system was 16.68 gpm/sq ft based on a filtration area of 33.8 sq ft (one out of two filters was not operational). If both filters were in operation, the filtration rate would be 8.34 gpm/ft2. Updated on January 24, 2024: Rate of filtration for the filtration system was 18.05 gpm/sq ft based on a filtration area of 33.8 sq ft (one out of two filters was not operational) (flow rate 612 gpm). If both filters were in operation, the filtration rate would be 9.02 gpm/ft2.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Demand Inspection
3 infractions
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- the sample 24EN-275E00222 submitted on October 1, 2024, was unsatisfactory: HPC 11860. Previous sample was satisfactory.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Rate of filtration for the filtration system was 13.4 gpm/sq ft based on a filtration area of 67.6 sq ft - noted to be 18.65 gpm/ft2 on February 27, 2017.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Rate of filtration for the filtration system was 16.68 gpm/sq ft based on a filtration area of 33.8 sq ft (one out of two filters was not operational). If both filters were in operation, the filtration rate would be 8.34 gpm/ft2. Updated on January 24, 2024: Rate of filtration for the filtration system was 18.05 gpm/sq ft based on a filtration area of 33.8 sq ft (one out of two filters was not operational) (flow rate 612 gpm). If both filters were in operation, the filtration rate would be 9.02 gpm/ft2.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Demand Inspection
3 infractions
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- the sample 24EN-240E00870 submitted on August 27, 2024, was unsatisfactory: Total coliforms present.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Rate of filtration for the filtration system was 13.4 gpm/sq ft based on a filtration area of 67.6 sq ft - noted to be 18.65 gpm/ft2 on February 27, 2017.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Rate of filtration for the filtration system was 16.68 gpm/sq ft based on a filtration area of 33.8 sq ft (one out of two filters was not operational). If both filters were in operation, the filtration rate would be 8.34 gpm/ft2. Updated on January 24, 2024: Rate of filtration for the filtration system was 18.05 gpm/sq ft based on a filtration area of 33.8 sq ft (one out of two filters was not operational) (flow rate 612 gpm). If both filters were in operation, the filtration rate would be 9.02 gpm/ft2.
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Demand Inspection
2 infractions
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Rate of filtration for the filtration system was 13.4 gpm/sq ft based on a filtration area of 67.6 sq ft - noted to be 18.65 gpm/ft2 on February 27, 2017.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Rate of filtration for the filtration system was 16.68 gpm/sq ft based on a filtration area of 33.8 sq ft (one out of two filters was not operational). If both filters were in operation, the filtration rate would be 8.34 gpm/ft2. Updated on January 24, 2024: Rate of filtration for the filtration system was 18.05 gpm/sq ft based on a filtration area of 33.8 sq ft (one out of two filters was not operational) (flow rate 612 gpm). If both filters were in operation, the filtration rate would be 9.02 gpm/ft2.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
Nearby inspected facilities
- Booster Juice Recreation Centre in Terwillegar - Competition Pool
2051 Leger Road NW Edmonton AB T6R 0R9
11 inspections
- Subway 72887
2 - 2051 Leger Road NW Edmonton AB T6R 0R9
3 inspections
- Booster Juice Recreation Centre in Terwillegar - Common Area
2051 Leger Road NW Edmonton AB T6R 0R9
3 inspections
- Booster Juice 638
2051 Leger Road NW Edmonton AB T6R 0R9
3 inspections
- Booster Juice Recreation Centre in Terwillegar - Tot Pool
2051 Leger Road NW Edmonton AB T6R 0R9
7 inspections
- Second Cup Cafe
3 - 2051 Leger Road NW Edmonton AB T6R 0R9
2 inspections
- Booster Juice Recreation Centre in Terwillegar - Leisure Pool
2051 Leger Road NW Edmonton AB T6R 0R9
5 inspections
- Franatics Food Service
2019 Leger Road NW Edmonton AB T6R 0R9
3 inspections