Copperstone Resort Hotel - Whirlpool
250 2 Avenue Dead Man's Flats AB T1W 2W4 · Aquatic Facility
39 inspections
- Risk Management Inspection
1 infraction
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- The skimmer on the east side of the whirlpool (to the right of the stair railing) does not appear to be drawing much water into it. Please fix so that is it properly skimming.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Demand Inspection
2 infractions
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Water sample from Thursday June 25th, 2026, had Pseudomonas isolated.- Operators were informed to treat and re-sample.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- The skimmer on the east side of the whirlpool (to the right of the stair railing) does not appear to be drawing much water into it. Please fix so that is it properly skimming.
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Risk Management Inspection
1 infraction
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- The skimmer on the east side of the whirlpool (to the right of the stair railing) does not appear to be drawing much water into it. Please fix so that is it properly skimming.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Demand Inspection
3 infractions
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Water sample taken on June 8, 2026 had Pseudomonas isolated. Close whirlpool until a treatment is done to remove contamination. Submit a new water sample after treatment.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Water sample taken on June 8, 2026 had a heterotrophic plate count of 280cfu/ml. Treatment to be done to remove contamination. Submit a new water sample after treatment.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- The skimmer on the east side of the whirlpool (to the right of the stair railing) does not appear to be drawing much water into it. Please fix so that is it properly skimming.
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Risk Management Inspection
1 infraction
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- The skimmer on the east side of the whirlpool (to the right of the stair railing) does not appear to be drawing much water into it. Please fix so that is it properly skimming.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Demand Inspection
2 infractions
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- The water sample submitted this week was not tested as the date of collection was written on the form as April 4th (not May 4th). Please submit a new sample this week.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- The skimmer on the east side of the whirlpool (to the right of the stair railing) does not appear to be drawing much water into it. Please fix so that is it properly skimming.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Risk Management Inspection
1 infraction
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- The skimmer on the east side of the whirlpool (to the right of the stair railing) does not appear to be drawing much water into it. Please fix so that is it properly skimming.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Demand Inspection
2 infractions
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Water sample taken on April 23, 2026 had a heterotrophic plate count of 160 cfu/ml. Treat water to remove contamination. Resample.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- The skimmer on the east side of the whirlpool (to the right of the stair railing) does not appear to be drawing much water into it. Please fix so that is it properly skimming.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Risk Management Inspection
1 infraction
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- The skimmer on the east side of the whirlpool (to the right of the stair railing) does not appear to be drawing much water into it. Please fix so that is it properly skimming.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Demand Inspection
2 infractions
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- The water sample taken on April 6, 2026 had a heterotrophic plate count of 320cfu/ml. Treat water to remove contamination. Resample.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- The skimmer on the east side of the whirlpool (to the right of the stair railing) does not appear to be drawing much water into it. Please fix so that is it properly skimming.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Risk Management Inspection
1 infraction
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- The skimmer on the east side of the whirlpool (to the right of the stair railing) does not appear to be drawing much water into it. Please fix so that is it properly skimming.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Demand Inspection
2 infractions
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- The water sample submitted on March 23, 2026 had a heterotrophic plate count of 270 cfu/ml. Treatment to be done to remove contamination. Resample.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- The skimmer on the east side of the whirlpool (to the right of the stair railing) does not appear to be drawing much water into it. Please fix so that is it properly skimming.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Risk Management Inspection
1 infraction
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- The skimmer on the east side of the whirlpool (to the right of the stair railing) does not appear to be drawing much water into it. Please fix so that is it properly skimming.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Demand Inspection
2 infractions
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- The water sample submitted this week was not tested as the date of collection was written as February 2, 2026 (instead of March 2, 2026) on the requisition form. New sample to be submitted this week.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- The skimmer on the east side of the whirlpool (to the right of the stair railing) does not appear to be drawing much water into it. Please fix so that is it properly skimming.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Demand Inspection
2 infractions
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- The water sample submitted on February 19, 2026 had a heterotrophic plate count of 340cfu/ml. Treat water to remove contamination. Resample.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- The skimmer on the east side of the whirlpool (to the right of the stair railing) does not appear to be drawing much water into it. Please fix so that is it properly skimming.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Risk Management Inspection
1 infraction
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- The skimmer on the east side of the whirlpool (to the right of the stair railing) does not appear to be drawing much water into it. Please fix so that is it properly skimming.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Demand Inspection
3 infractions
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Water sample taken on January 6, 2026 was not tested as it was received by the lab over 24 hours after collection. Water sample was dropped off on a day that they are not accepted/couriered to the lab so it was received by the lab over 24 hours after collection. New water sample to be submitted and water samples are not to be dropped off
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- No water samples were submitted for testing the weeks of December 22nd or Dec. 29th, 2025. Water samples from the whirlpool are to be submitted each week for bacteriological testing.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- The skimmer on the east side of the whirlpool (to the right of the stair railing) does not appear to be drawing much water into it. Please fix so that is it properly skimming.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Monitoring Inspection
1 infraction
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- The skimmer on the east side of the whirlpool (to the right of the stair railing) does not appear to be drawing much water into it. Please fix so that is it properly skimming.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Demand Inspection
3 infractions
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- The water sample taken on October 14, 2025 had a heterotrophic plate count of 440cfu/ml. Treatment had already been done. New sample to be submitted.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Flow rate is being exceeded through the filters. Maximum flow rate for each filter is 61gpm; the flow rate through the filters was 75gpm. Ensure overall flow rate if at least 111 gpm, without exceeding 61gpm through either filter.
- 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
- Some tiles are missing from the interior of the whirlpool basin. To be repaired.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Demand Inspection
3 infractions
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Water sample submitted this week was not tested as it was received by the lab over 24 hours after collection (incorrect date may have been written on the requisition form). New sample to be submitted this week.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Flow rate is being exceeded through the filters. Maximum flow rate for each filter is 61gpm; the flow rate through the filters was 75gpm. Ensure overall flow rate if at least 111 gpm, without exceeding 61gpm through either filter.
- 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
- Some tiles are missing from the interior of the whirlpool basin. To be repaired.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Risk Management Inspection
2 infractions
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Flow rate is being exceeded through the filters. Maximum flow rate for each filter is 61gpm; the flow rate through the filters was 75gpm. Ensure overall flow rate if at least 111 gpm, without exceeding 61gpm through either filter.
- 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
- Some tiles are missing from the interior of the whirlpool basin. To be repaired.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Demand Inspection
3 infractions
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Water sample from Monday June 23rd, 2025, had pseudomonas isolated.- Operators were informed to treat and re-sample.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Flow rate is being exceeded through the filters. Maximum flow rate for each filter is 61gpm; the flow rate through the filters was 75gpm. Ensure overall flow rate if at least 111 gpm, without exceeding 61gpm through either filter.
- 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
- Some tiles are missing from the interior of the whirlpool basin. To be repaired.
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Risk Management Inspection
2 infractions
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Flow rate is being exceeded through the filters. Maximum flow rate for each filter is 61gpm; the flow rate through the filters was 75gpm. Ensure overall flow rate if at least 111 gpm, without exceeding 61gpm through either filter.
- 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
- Some tiles are missing from the interior of the whirlpool basin. To be repaired.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Demand Inspection
4 infractions
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- December 30, 2024 water sample had Pseudomonas isolated. Close whirlpool until a Pseudomonas disinfection is done. Resample.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- December 30, 2024 water sample had a plate count of 510cfu/ml. Treat water to remove contamination. Resample.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Flow rate is being exceeded through the filters. Maximum flow rate for each filter is 61gpm; the flow rate through the filters was 75gpm. Ensure overall flow rate if at least 111 gpm, without exceeding 61gpm through either filter.
- 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
- Some tiles are missing from the interior of the whirlpool basin. To be repaired.
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Demand Inspection
3 infractions
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Water sample submitted this week was not tested as an incorrect day of collection had been written down (Dec. 1/24) so it appeared the lab received the sample over 24hours after its collection. Resample to be submitted this week.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Flow rate is being exceeded through the filters. Maximum flow rate for each filter is 61gpm; the flow rate through the filters was 75gpm. Ensure overall flow rate if at least 111 gpm, without exceeding 61gpm through either filter.
- 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
- Some tiles are missing from the interior of the whirlpool basin. To be repaired.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Demand Inspection
3 infractions
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Water sample submitted this week was not tested as an incorrect day of collection had been written down so it appeared the lab received the sample over 24hours after its collection. Resample to be submitted this week.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Flow rate is being exceeded through the filters. Maximum flow rate for each filter is 61gpm; the flow rate through the filters was 75gpm. Ensure overall flow rate if at least 111 gpm, without exceeding 61gpm through either filter.
- 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
- Some tiles are missing from the interior of the whirlpool basin. To be repaired.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Demand Inspection
3 infractions
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Water sample submitted this week was not tested as there was no date of collection on the requisition form. Resample to be submitted this week.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Flow rate is being exceeded through the filters. Maximum flow rate for each filter is 61gpm; the flow rate through the filters was 75gpm. Ensure overall flow rate if at least 111 gpm, without exceeding 61gpm through either filter.
- 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
- Some tiles are missing from the interior of the whirlpool basin. To be repaired.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Demand Inspection
3 infractions
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Water sample submitted this week was not sampled as it was received by the lab more than 24 hours after date of collection written on the requisition form. Resample to be submitted this week.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Flow rate is being exceeded through the filters. Maximum flow rate for each filter is 61gpm; the flow rate through the filters was 75gpm. Ensure overall flow rate if at least 111 gpm, without exceeding 61gpm through either filter.
- 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
- Some tiles are missing from the interior of the whirlpool basin. To be repaired.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Demand Inspection
3 infractions
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Water sample taken on March 28/24 was not tested as was submitted on wrong day of the week (due to lab holiday). Advised to resample.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Flow rate is being exceeded through the filters. Maximum flow rate for each filter is 61gpm; the flow rate through the filters was 75gpm. Ensure overall flow rate if at least 111 gpm, without exceeding 61gpm through either filter.
- 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
- Some tiles are missing from the interior of the whirlpool basin. To be repaired.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Demand Inspection
3 infractions
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Last water sample submitted was not tested as the date of collection was written as Feb. 15/24 (date in the future) so the sample was not processed by the lab.Resample to be taken this week.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Flow rate is being exceeded through the filters. Maximum flow rate for each filter is 61gpm; the flow rate through the filters was 75gpm. Ensure overall flow rate if at least 111 gpm, without exceeding 61gpm through either filter.
- 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
- Some tiles are missing from the interior of the whirlpool basin. To be repaired.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Risk Management Inspection
2 infractions
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Flow rate is being exceeded through the filters. Maximum flow rate for each filter is 61gpm; the flow rate through the filters was 75gpm. Ensure overall flow rate if at least 111 gpm, without exceeding 61gpm through either filter.
- 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
- Some tiles are missing from the interior of the whirlpool basin. To be repaired.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Demand Inspection
4 infractions
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Pseudomonas was isolated in the sample from November 27th, 2023.- Operators have performed a pseudomonas disinfection and will re-sample.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Water sample from November 27, 2023 had an HPC of 340 CFU/ml. Chlorine injectors went down this week, has since been repaired. - Operators were informed to treat and re-sample
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Flow rate is being exceeded through the filters. Maximum flow rate for each filter is 61gpm; the flow rate through the filters was 75gpm. Ensure overall flow rate if at least 111 gpm, without exceeding 61gpm through either filter.
- 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
- Some tiles are missing from the interior of the whirlpool basin. To be repaired.
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Demand Inspection
3 infractions
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Water sample from November 27, 2023 had an HPC of 340 CFU/ml. Chlorine injectors went down this week, has since been repaired. - Operators were informed to treat and re-sample
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Flow rate is being exceeded through the filters. Maximum flow rate for each filter is 61gpm; the flow rate through the filters was 75gpm. Ensure overall flow rate if at least 111 gpm, without exceeding 61gpm through either filter.
- 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
- Some tiles are missing from the interior of the whirlpool basin. To be repaired.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Risk Management Inspection
2 infractions
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Flow rate is being exceeded through the filters. Maximum flow rate for each filter is 61gpm; the flow rate through the filters was 75gpm. Ensure overall flow rate if at least 111 gpm, without exceeding 61gpm through either filter.
- 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
- Some tiles are missing from the interior of the whirlpool basin. To be repaired.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Monitoring Inspection
4 infractions
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Flow rate is being exceeded through the filters. Maximum flow rate for each filter is 61gpm; the flow rate through the filters was 75gpm. Ensure overall flow rate if at least 111 gpm, without exceeding 61gpm through either filter.
- 12. Are the general safety devices and physical conditions in this pool providing a safe environment (Critical)?
- Drain covers were installed June 2016. Manufacturer states suction cover life of 7 years so covers are "expired" and must be replaced with new covers.
- 14. Is the pool maintained in a clean and sanitary condition, good repair and are temperatures being properly regulated?
- Some tiles are missing from the interior of the whirlpool basin. To be repaired.
- 17. Does the pool have adequate written policies, plans and posted rules and safety information to ensure that the pool is operating in a safe manner?
- Anti-entrapment plan to be redone using current template. Older template used does not have all the information required. Ensure anti-entrapment plan is updated when new covers installed.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Risk Management Inspection
1 infraction
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Required minimum flow rate is 420LPM; flow meter is reading only 367LPM/97gpm.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Demand Inspection
2 infractions
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Oct. 12/23 water sample had Pseudomonas isolated. Treat water to remove contamination.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Required minimum flow rate is 420LPM; flow meter is reading only 367LPM/97gpm.
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Risk Management Inspection
1 infraction
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Required minimum flow rate is 420LPM; flow meter is reading only 367LPM/97gpm.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Demand Inspection
2 infractions
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
- Pseudomonas was isolated in the August 29, 2023, sample. - Close and treat the whirlpool and resample.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- Required minimum flow rate is 420LPM; flow meter is reading only 367LPM/97gpm.
- 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?