Country Lane Estates - Whirlpool

370165 79 Street E Foothills No 31 AB T0L 0A0 · Aquatic Facility

14 inspections

  1. Demand Inspection

    1 infraction

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • Bacteriological sample submitted on June 1 2026 did not get processed due to missing time of collection. Spoke to Jack.
  2. Risk Management Inspection

    0 infractions

  3. Demand Inspection

    1 infraction

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • Bacteriological water sample submitted on May 11 2026 came back with 170 CFU/mL HPC. **Resample as soon as possible.
  4. Monitoring Inspection

    0 infractions

  5. Risk Management Inspection

    0 infractions

  6. Demand Inspection

    2 infractions

    • 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
      • The bacterial water sample taken on July 7, 2025 was present for total coliform bacteria. - Satisfactory bacterial water sample required. Further chemical treatment and rebalancing of pool chemistry recommended prior to resample.
    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • The bacterial water sample taken on July 7, 2025 had an HPC count of 2140 CFU/mL.- A satisfactory bacterial water sample is required.
  7. Risk Management Inspection

    0 infractions

  8. Demand Inspection

    2 infractions

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • Bacteriological water sample submitted on June 16 2025 came back with a Heterotrophic Plate Count of 450CFU/mL. **Submit resample as soon as possible.
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • Flow rate measured at 50 GPM at the time of inspection.**Ensure the flow rate if maintained at a minimum of 57 GPM to meet the 15 min turnover rate.
  9. Monitoring Inspection

    1 infraction

    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • Flow rate measured at 50 GPM at the time of inspection.**Ensure the flow rate if maintained at a minimum of 57 GPM to meet the 15 min turnover rate.
  10. Risk Management Inspection

    1 infraction

    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • Whirlpool pump is unable to maintain required flow rate of 57 GPM. Flow rate measured at 47 GPM at the time of inspection.- Staff aware of the aforementioned issue and will be replacing the pump at the start of next season to get the required flow rate.
  11. Demand Inspection

    2 infractions

    • 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
      • The most recent bacteriological water sample indicates a presence of Pseudomonas aeruginosa.
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • Whirlpool pump is unable to maintain required flow rate of 57 GPM. Flow rate measured at 47 GPM at the time of inspection.- Staff aware of the aforementioned issue and will be replacing the pump at the start of next season to get the required flow rate.
  12. Risk Management Inspection

    0 infractions

  13. Monitoring Inspection

    1 infraction

    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • Whirlpool pump is unable to maintain required flow rate of 57 GPM. Flow rate measured at 47 GPM at the time of inspection.- Staff aware of the aforementioned issue and will be replacing the pump at the start of next season to get the required flow rate.
  14. Demand Inspection

    2 infractions

    • 02. Is the bacteriological quality of the water in this pool satisfactory (Critical)?
      • The most recent bacteriological water sample indicates a presence of Pseudomonas aeruginosa.
    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • The most recent bacteriological water sample indicated a Heterotropic Plate Count of 130.