Cranston Spray Park
11 Cranarch Road SE Calgary AB T3M 0S8 · Aquatic Facility
5 inspections
- Demand Inspection
3 infractions
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Sept 2 2025 sample was positive for 3130 cfu/ml HPC. Treat.
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- The combined chlorines were measured at 1.8 ppm.- Please ensure that the combined chlorines are maintained under 1ppm.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- The flow rate was at 275 GPM which is over the max flow allowed through the filters. - Please ensure that the flow rate is maintained between the minimum flow of 48 GPM and max flow of 212.
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Demand Inspection
2 infractions
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- The combined chlorines were measured at 1.8 ppm.- Please ensure that the combined chlorines are maintained under 1ppm.
- 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
- The flow rate was at 275 GPM which is over the max flow allowed through the filters. - Please ensure that the flow rate is maintained between the minimum flow of 48 GPM and max flow of 212.
- 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
- Demand Inspection
1 infraction
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- The water sample collected on July 7, 2025 was not processed at the lab since it was missing the identifier on the bottle. -resample
- 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
- Monitoring Inspection
0 infractions
- Monitoring Inspection
0 infractions