11 Cranarch Road SE Calgary AB T3M 0S8 · Aquatic Facility

5 inspections

  1. Demand Inspection

    3 infractions

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • Sept 2 2025 sample was positive for 3130 cfu/ml HPC. Treat.
    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • The combined chlorines were measured at 1.8 ppm.- Please ensure that the combined chlorines are maintained under 1ppm.
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • The flow rate was at 275 GPM which is over the max flow allowed through the filters. - Please ensure that the flow rate is maintained between the minimum flow of 48 GPM and max flow of 212.
  2. Demand Inspection

    2 infractions

    • 05. Is the chemical quality of the water in this pool satisfactory (Non-Critical)?
      • The combined chlorines were measured at 1.8 ppm.- Please ensure that the combined chlorines are maintained under 1ppm.
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • The flow rate was at 275 GPM which is over the max flow allowed through the filters. - Please ensure that the flow rate is maintained between the minimum flow of 48 GPM and max flow of 212.
  3. Demand Inspection

    1 infraction

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • The water sample collected on July 7, 2025 was not processed at the lab since it was missing the identifier on the bottle. -resample
  4. Monitoring Inspection

    0 infractions

  5. Monitoring Inspection

    0 infractions