Deerfoot Inn & Casino - Swimming Pool

1000 - 11500 35 Street SE Calgary AB T2Z 3W4 · Aquatic Facility

40 inspections

  1. Risk Management Inspection

    1 infraction

    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • 1. The flow metre for the fishy slide was not operational.**April 24, 2026: part has been ordered to repair the flow metre. 2. The flow metre for the waterslide was not operational.**April 24, 2026: flow metre read 0 GPM.COMPLETE THE FOLLOWING:1. Replace/repair the flow metres listed above.
  2. Demand Inspection

    3 infractions

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • The water sample collected on Apr 30, 2026 had a Heterotrophic plate count of 2,280 CFU/mL.-treat and resample; this is the 2nd consecutive unsatisfactory water sample, and a 3rd will result in the closure of the pool.
    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • The water sample collected on Apr 23, 2026 resulted in a Heterotrophic Plate Count of 610 cfu/mL.-treat and resample.
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • 1. The flow metre for the fishy slide was not operational.**April 24, 2026: part has been ordered to repair the flow metre. 2. The flow metre for the waterslide was not operational.**April 24, 2026: flow metre read 0 GPM.COMPLETE THE FOLLOWING:1. Replace/repair the flow metres listed above.
  3. Demand Inspection

    2 infractions

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • The water sample collected on Apr 23, 2026 resulted in a Heterotrophic Plate Count of 610 cfu/mL.-treat and resample.
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • 1. The flow metre for the fishy slide was not operational.**April 24, 2026: part has been ordered to repair the flow metre. 2. The flow metre for the waterslide was not operational.**April 24, 2026: flow metre read 0 GPM.COMPLETE THE FOLLOWING:1. Replace/repair the flow metres listed above.
  4. Risk Management Inspection

    1 infraction

    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • 1. The flow metre for the fishy slide was not operational.**April 24, 2026: part has been ordered to repair the flow metre. 2. The flow metre for the waterslide was not operational.**April 24, 2026: flow metre read 0 GPM.COMPLETE THE FOLLOWING:1. Replace/repair the flow metres listed above.
  5. Risk Management Inspection

    2 infractions

    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • 1. The flow metre for the fishy slide was not operational.2. The flow metre for the waterslide was not operational.3. The Operators stated the main drain valve is opened at 50%. COMPLETE THE FOLLOWING:1. Replace the flow metres listed above.2. Please adjust the main drain valve so that it is opened no more than 30% to increase flow of water through skimmers, as the top portion of the pool water contains greater amounts of contaminants than the bottom.
    • 16. Are proper testing, monitoring, and other records being properly maintained?
      • 1. The small test reagent bottles that were being re-filled from larger bottles were not labeled with the correct dates. COMPLETE THE FOLLOWING:1. Please label the small bottles.
  6. Demand Inspection

    4 infractions

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • The water sample collected on Apr 2, 2026 had a Heterotrophic plate count of 480 cfu/mL.-treat and resample - ensure the water chemistry is perfect. A 3rd consecutive unsatisfactory result will close the pool.
    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • The water sample collected on March 26, 2026 had a Heterotrophic Plate Count of 6040 CFU/mL.-treat and resample.
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • 1. The flow metre for the fishy slide was not operational.2. The flow metre for the waterslide was not operational.3. The Operators stated the main drain valve is opened at 50%. COMPLETE THE FOLLOWING:1. Replace the flow metres listed above.2. Please adjust the main drain valve so that it is opened no more than 30% to increase flow of water through skimmers, as the top portion of the pool water contains greater amounts of contaminants than the bottom.
    • 16. Are proper testing, monitoring, and other records being properly maintained?
      • 1. The small test reagent bottles that were being re-filled from larger bottles were not labeled with the correct dates. COMPLETE THE FOLLOWING:1. Please label the small bottles.
  7. Demand Inspection

    3 infractions

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • The water sample collected on March 26, 2026 had a Heterotrophic Plate Count of 6040 CFU/mL.-treat and resample.
    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • 1. The flow metre for the fishy slide was not operational.2. The flow metre for the waterslide was not operational.3. The Operators stated the main drain valve is opened at 50%. COMPLETE THE FOLLOWING:1. Replace the flow metres listed above.2. Please adjust the main drain valve so that it is opened no more than 30% to increase flow of water through skimmers, as the top portion of the pool water contains greater amounts of contaminants than the bottom.
    • 16. Are proper testing, monitoring, and other records being properly maintained?
      • 1. The small test reagent bottles that were being re-filled from larger bottles were not labeled with the correct dates. COMPLETE THE FOLLOWING:1. Please label the small bottles.
  8. Monitoring Inspection

    2 infractions

    • 07. Are the filtration, circulation and disinfection systems used to maintain water quality working properly (Non-Critical)?
      • 1. The flow metre for the fishy slide was not operational.2. The flow metre for the waterslide was not operational.3. The Operators stated the main drain valve is opened at 50%. COMPLETE THE FOLLOWING:1. Replace the flow metres listed above.2. Please adjust the main drain valve so that it is opened no more than 30% to increase flow of water through skimmers, as the top portion of the pool water contains greater amounts of contaminants than the bottom.
    • 16. Are proper testing, monitoring, and other records being properly maintained?
      • 1. The small test reagent bottles that were being re-filled from larger bottles were not labeled with the correct dates. COMPLETE THE FOLLOWING:1. Please label the small bottles.
  9. Demand Inspection

    2 infractions

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • The water sample collected on Sep 16 resulted in a 800 CFU/mL Heterotrophic Plate Count.-treat and resampleID: 25ES-259E00683
    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • The water sample collected on Sep 11, 2025 had a Heterotrophic Plate Count of 300 CFU/mL.-treat and resampleID: 25ES-254E00192
  10. Demand Inspection

    1 infraction

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • The water sample collected on Sep 11, 2025 had a Heterotrophic Plate Count of 300 CFU/mL.-treat and resampleID: 25ES-254E00192
  11. Risk Management Inspection

    0 infractions

  12. Demand Inspection

    1 infraction

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • The water sample results came back unsatisfactory with HPC 970 CFU/m- Resampling advised.
  13. Risk Management Inspection

    0 infractions

  14. Demand Inspection

    2 infractions

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • The water sample results came unsatisfactory.HPC 2490Collection date; Apr 3, 2025- Resampling advised
    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • Spoke with Chris Booker.Water sample was rejected due to incorrect collection date. The Date Time of sample collection is LATER than the Date Time of receipt.
  15. Demand Inspection

    1 infraction

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • The water sample results came unsatisfactory.HPC 2490Collection date; Apr 3, 2025- Resampling advised
  16. Risk Management Inspection

    0 infractions

  17. Demand Inspection

    1 infraction

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • The bacteriological water sample collected on February 20, 2025, had an HPC of 1520 CFU/mL. Another sample must be submitted immediately. The operator mentioned that they will shock chlorinate the swimming pool, then another water sample will be submitted.
  18. Risk Management Inspection

    0 infractions

  19. Demand Inspection

    1 infraction

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • The sample collected on January 23, 2025 had an HPC count of 1490 CFU/ml.Send in a resample.
  20. Demand Inspection

    1 infraction

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • The sample collected on January 16, 2025 had an HPC count of 1370 CFU/ml.Send in a resample.
  21. Monitoring Inspection

    1 infraction

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • The sample collected on October 10, 2024 had an HPC count of 640 CFU/ml.Send in a resample.
  22. Demand Inspection

    1 infraction

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • The sample collected on October 10, 2024 had an HPC count of 640 CFU/ml.Send in a resample.
  23. Demand Inspection

    2 infractions

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • The sample collected on August 2,9 2024 had an HPC count of 9640 CFU/ml.Treat and submit a resample.
    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • The sample collected on August 22, 2024 had an HPC count of 370 CFU/ml.Resample.
  24. Demand Inspection

    1 infraction

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • The sample collected on August 22, 2024 had an HPC count of 370 CFU/ml.Resample.
  25. Demand Inspection

    1 infraction

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • The sample collected on July 31, 2024 had an HPC count of 2260 CFU/ml.Treat and resample the pool.
  26. Demand Inspection

    1 infraction

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • The sample collected on July 25, 2024 had an HPC count of 6840 CFU/ml.Treat the pool and submit a resample.
  27. Demand Inspection

    1 infraction

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • The sample colelcted on June 20, 2024 had an HPC count of 790 CFU/ml.Treat the pool and submit a resample.
  28. Demand Inspection

    1 infraction

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • The sample colelcted on June 13, 2024 had an HPC count of 640 CFU/ml.Resample.
  29. Risk Management Inspection

    0 infractions

  30. Demand Inspection

    1 infraction

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • The water sample collected on April 25, 2024 had an HPC count of 680 CFU/ml.Treat and resample.
  31. Risk Management Inspection

    0 infractions

  32. Demand Inspection

    1 infraction

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • The sample collected on February 29, 2024 had an HPC count of 260 CFU/ml.Treat and send in a resample.
  33. Risk Management Inspection

    0 infractions

  34. Demand Inspection

    1 infraction

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • The pool water sample collected on February 8, 2024, had an HPC count of 930 CFU/ml.Submit a resample.
  35. Risk Management Inspection

    0 infractions

  36. Demand Inspection

    1 infraction

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • The sample collected on January 11, 2024 had an HPC count of 1510 CFU/ml.Superchlorinate and resample.
  37. Monitoring Inspection

    0 infractions

  38. Demand Inspection

    1 infraction

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • 1. The water sample submitted on November 23, 2023 had an HPC count of 2160 CFU/ml.Treat the pool and send in a resample.
  39. Demand Inspection

    1 infraction

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • 1. The water sample submitted on August 31, 2023 had an HPC count of 1300 CFU/ml.2. The water sample submitted on September 7, 2023 had an HPC count of >57000 CFU/ml.Treat the pool and send in a resample.
  40. Demand Inspection

    1 infraction

    • 03. Is the bacteriological quality of the water in this pool satisfactory (Non-Critical)?
      • The water sample submitted on August 31, 2023 had an HPC count of 1300 CFU/ml.Treat the pool and send in a resample.